Winding Data for 5N-9081 Generator through 5N-9432 Generator
5N-9081 Generator
Show/hide table
MAIN STATOR AND ROTOR WINDING DATA     | ||||
ITEM     | STATOR     | ROTOR (RANDOM WOUND)     |
ROTOR (FORM WOUND)     |
|
Stack Height     | 152.4 mm (6.0 inch)     |
152.4 mm (6.0 inch)     |
-     | |
Slots     | 60     | -     | -     | |
Coil Throw     | 1 - 12     | -     | -     | |
Turns/Coil     | 5.6 (6,6,4,6,6)     | -     | -     | |
Turns/Pole     | -     | 110     | -     | |
No. & Wire Size     | 6 - #15     | 1 - #17     | -     | |
Mean Length Turn     | 934.7 mm (36.8 inch)     |
-     | -     | |
Copper Weight     | 29.2 kg (64.3 lb)     |
438.1 kg (965.9 lb)     |
-     | |
Inside Connection (1)     | 4/2 Parallel Star     | 4 in Series     | -     | |
Line Leads (No. & Size)     | 10 - #4     | -     | -     | |
Terminal bolt size     | 3/8 inch     | -     | -     | |
Low Voltage connected line resistance at 25 ° C (77 ° F)     | 0.025 ohms     | -     | -     | |
Field lead resistance at 25 ° C (77 ° F)     | -     | 0.56 ohms     | -     | |
EXCITER WINDING DATA     | ||||
Exciter Frequency (Hz)     | 90 Hz     | |||
Exciter Poles     | 6     | |||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | ||
Stack Length     | 76.2 mm (3.0 inch)     |
76.2 mm (3.0 inch)     |
||
Coils/Group     | 1     | 2     | ||
Slots (Coils)     | 6     | 36     | ||
Turns (Coils)     | 105     | 6     | ||
No. & Size Wire     | 1 - #15     | 2 - #14.5     | ||
Coil Throw     | 1 - 2     | 1 - 6     | ||
Mean Length Turn (Calc.)     | 365.8 mm (14.4 inch)     |
304.8 mm (12.0 inch)     |
||
Copper Weight     | 3.9 kg (8.5 lb)     |
3.4 kg (7.5 lb)     |
||
Insulation     | Heavy Nytherm     | |||
Connection (2)     | Series     | 2 Parallel Star     | ||
Line Leads     | #14 - 965.2 mm (38.0 inch)     |
#10 - 152.4 mm (6.0 inch)     |
Show/hide table
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram #31 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram A |
5N-9082 Generator
Show/hide table
MAIN STATOR AND ROTOR WINDING DATA     | ||||
ITEM     | STATOR     | ROTOR (RANDOM WOUND)     |
ROTOR (FORM WOUND)     |
|
Stack Height     | 228.6 mm (9.0 inch)     |
228.6 mm (9.0 inch)     |
-     | |
Slots     | 60     | -     | -     | |
Coil Throw     | 1 - 12     | -     | -     | |
Turns/Coil     | 3.4(3,4,3,4,3)     | -     | -     | |
Turns/Pole     | -     | 96     | -     | |
No. & Wire Size     | 6 - #15     | 1 - #9     | -     | |
Mean Length Turn     | 960.1 mm (37.8 inch)     |
-     | -     | |
Copper Weight     | 18.6 kg (40.95 lb)     |
18.2 kg (40.04 lb)     |
-     | |
Inside Connection (1)     | 4/2 Parallel Star     | 4 in Series     | -     | |
Line Leads (No. & Size)     | 10 - #4     | -     | -     | |
Terminal bolt size     | 3/8 inch     | -     | -     | |
Low Voltage connected line resistance at 25 ° C (77 ° F)     |
0.0148 ohms     | -     | -     | |
Field lead resistance at 25 ° C (77 ° F)     |
-     | 0.80 ohms     | -     | |
EXCITER WINDING DATA     | ||||
Exciter Frequency (Hz)     | 90 Hz     | |||
Exciter Poles     | 6     | |||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | ||
Stack Length     | 50.8 mm (2.0 inch)     |
50.8 mm (2.0 inch)     |
||
Coils/Group     | 1     | 2     | ||
Slots (Coils)     | 6     | 36     | ||
Turns (Coils)     | 160     | 9     | ||
No. & Size Wire     | 1 - #16.5     | 1 - #14     | ||
Coil Throw     | 1 - 2     | 1 - 6     | ||
Mean Length Turn (Calculated)     |
113.3 mm (4.46 inch)     |
254.0 mm (10.0 inch)     |
||
Copper Weight     | 2.7 kg (6.0 lb)     |
1.5 kg (3.4 lb)     |
||
Insulation     | Heavy Nytherm     | |||
Connection (2)     | Series     | 2 Parallel Star     | ||
Line Leads     | #14 914.4 mm (36.0 inch)     |
#10 139.7 mm (5.5 inch)     |
Show/hide table
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram #31 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram E |
5N-9083 Generator
Show/hide table
MAIN STATOR AND ROTOR WINDING DATA     | ||||
ITEM     | STATOR     | ROTOR (RANDOM WOUND)     |
ROTOR (FORM WOUND)     |
|
Stack Height     | 203.2 mm (8.0 inch)     |
203.2 mm (8.0 inch)     |
-     | |
Slots     | 60     | -     | -     | |
Coil Throw     | 1 - 14     | -     | -     | |
Turns/Coil     | 3.4(4,3,3,3,4)     | -     | -     | |
Turns/Pole     | -     | 110     | -     | |
No. & Wire Size     | 8 - #14     | 1 - #7     | -     | |
Mean Length Turn     | 1135.4 mm (44.7 inch)     |
-     | -     | |
Copper Weight     | 34.9 kg (77.0 lb)     |
34.2 kg (75.4 lb)     |
-     | |
Inside Connection (1)     | 4/2 Parallel Star     | 4 in Series     | -     | |
Line Leads (No. & Size)     | 20 - #6     | -     | -     | |
Terminal bolt size     | 3/8 inch     | -     | -     | |
Low Voltage connected line resistance at 25 ° C (77 ° F)     |
0.01 ohms     | -     | -     | |
Field lead resistance at 25 ° C (77 ° F)     |
-     | 0.63 ohms     | -     | |
EXCITER WINDING DATA     | ||||
Exciter Frequency (Hz)     | 90 Hz     | |||
Exciter Poles     | 6     | |||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | ||
Stack Length     | 76.2 mm (3.0 inch)     |
76.2 mm (3.0 inch)     |
||
Coils/Group     | 1     | 2     | ||
Slots (Coils)     | 6     | 36     | ||
Turns (Coils)     | 95     | 6     | ||
No. & Size Wire     | 1 - #14.5     | 2 - #14.5     | ||
Coil Throw     | 1 - 2     | 1 - 6     | ||
Mean Length Turn (Calculated)     |
365.8 mm (14.4 inch)     |
304.8 mm (12.0 inch)     |
||
Copper Weight     | 3.9 kg (8.7 lb)     |
3.4 kg (7.5 lb)     |
||
Insulation     | Heavy Nytherm     | |||
Connection (2)     | Series     | 2 Parallel Star     | ||
Line Leads     | #14 965.2 mm (38.0 inch)     |
#10 152.4 mm (6.0 inch)     |
Show/hide table
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram #01 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram A |
5N-9084 Generator
Show/hide table
MAIN STATOR AND ROTOR WINDING DATA     | ||||
ITEM     | STATOR     | ROTOR (RANDOM WOUND)     |
ROTOR (FORM WOUND)     |
|
Stack Height     | 152.4 mm (6.0 inch)     |
152.4 mm (6.0 inch)     |
-     | |
Slots     | 60     | -     | -     | |
Coil Throw     | 1 - 12     | -     | -     | |
Turns/Coil     | 5     | -     | -     | |
Turns/Pole     | -     | 110     | -     | |
No. & Wire Size     | 7 - #15     | 1 - #7     | -     | |
Mean Length Turn     | 934.7 mm (36.8 inch)     |
-     | -     | |
Copper Weight     | 29.3 kg (64.7 lb)     |
29.9 kg (65.9 lb)     |
-     | |
Inside Connection (1)     | 4/2 Parallel Star     | 4 in Series     | -     | |
Line Leads (No. & Size)     | 20 - #6     | -     | -     | |
Terminal bolt size     | 3/8 inch     | -     | -     | |
Low Voltage connected line resistance at 25 ° C (77 ° F)     |
0.01 ohms     | -     | -     | |
Field lead resistance at 25 ° C (77 ° F)     |
-     | 0.63 ohms     | -     | |
EXCITER WINDING DATA     | ||||
Exciter Frequency (Hz)     | 90 Hz     | |||
Exciter Poles     | 6     | |||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | ||
Stack Length     | 76.2 mm (3.0 inch)     |
76.2 mm (3.0 inch)     |
||
Coils/Group     | 1     | 2     | ||
Slots (Coils)     | 6     | 36     | ||
Turns (Coils)     | 95     | 6     | ||
No. & Size Wire     | 1 - #14.5     | 2 - #14.5     | ||
Coil Throw     | 1 - 2     | 1 - 6     | ||
Mean Length Turn (Calculated)     |
365.8 mm (14.4 inch)     |
304.8 mm (12.0 inch)     |
||
Copper Weight     | 3.9 kg (8.7 lb)     |
3.4 kg (7.5 lb)     |
||
Insulation     | Heavy Nytherm     | |||
Connection (2)     | Series     | 2 Parallel Star     | ||
Line Leads     | #14 965.2 mm (38.0 inch)     |
#10 152.4 mm (6.0 inch)     |
Show/hide table
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram #31 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram A |
5N-9085 Generator
Show/hide table
MAIN STATOR AND ROTOR WINDING DATA     | ||||
ITEM     | STATOR     | ROTOR (RANDOM WOUND)     |
ROTOR (FORM WOUND)     |
|
Stack Height     | 228.6 mm (9.0 inch)     |
228.6 mm (9.0 inch)     |
-     | |
Slots     | 60     | -     | -     | |
Coil Throw     | 1 - 12     | -     | -     | |
Turns/Coil     | 5     | -     | -     | |
Turns/Pole     | -     | 96     | -     | |
No. & Wire Size     | 5 - #15     | 1 - #9     | -     | |
Mean Length Turn     | 960.1 mm (37.8 inch)     |
-     | -     | |
Copper Weight     | 17.2 kg (37.98 lb)     |
18.2 kg (40.04 lb)     |
-     | |
Inside Connection (1)     | 4/2 Parallel Star     | 4 in Series     | -     | |
Line Leads (No. & Size)     | 10 - #6     | -     | -     | |
Terminal bolt size     | 3/8 inch     | -     | -     | |
Low Voltage connected line resistance at 25 ° C (77 ° F)     |
0.033 ohms     | -     | -     | |
Field lead resistance at 25 ° C (77 ° F)     |
-     | 0.80 ohms     | -     | |
EXCITER WINDING DATA     | ||||
Exciter Frequency (Hz)     | 90 Hz     | |||
Exciter Poles     | 6     | |||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | ||
Stack Length     | 50.8 mm (2.0 inch)     |
50.8 mm (2.0 inch)     |
||
Coils/Group     | 1     | 2     | ||
Slots (Coils)     | 6     | 36     | ||
Turns (Coils)     | 160     | 9     | ||
No. & Size Wire     | 1 - #16.5     | 1 - #14     | ||
Coil Throw     | 1 - 2     | 1 - 6     | ||
Mean Length Turn (Calculated)     |
113.3 mm (4.46 inch)     |
254.0 mm (10.0 inch)     |
||
Copper Weight     | 2.7 kg (6.0 lb)     |
1.5 kg (3.4 lb)     |
||
Insulation     | Heavy Nytherm     | |||
Connection (2)     | Series     | 2 Parallel Star     | ||
Line Leads     | #14 914.4 mm (36.0 inch)     |
#10 139.7 mm (5.5 inch)     |
Show/hide table
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram #05 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram E |
Note: Wires 20, 22, and 24 are brought out as tap connections between 4th and 5th coil (18 turns from T0).
5N-9086 Generator
Show/hide table
MAIN STATOR AND ROTOR WINDING DATA     | ||||
ITEM     | STATOR     | ROTOR (RANDOM WOUND)     |
ROTOR (FORM WOUND)     |
|
Stack Height     | 203.2 mm (8.0 inch)     |
203.2 mm (8.0 inch)     |
-     | |
Slots     | 60     | -     | -     | |
Coil Throw     | 1 - 12     | -     | -     | |
Turns/Coil     | 4.65(4,4,5,5,5)     | -     | -     | |
Turns/Pole     | -     | 110     | -     | |
No. & Wire Size     | 7 - #15     | 1 - #7     | -     | |
Mean Length Turn     | 1036.3 mm (40.8 inch)     |
-     | -     | |
Copper Weight     | 27.2 kg (60.0 lb)     |
34.2 kg (75.4 lb)     |
-     | |
Inside Connection (1)     | 4/2 Parallel Star     | 4 in Series     | -     | |
Line Leads (No. & Size)     | 10 - #4     | -     | -     | |
Terminal bolt size     | 3/8 inch     | -     | -     | |
Low Voltage connected line resistance at 25 ° C (77 ° F)     |
0.0192 ohms     | -     | -     | |
Field lead resistance at 25 ° C (77 ° F)     |
-     | 0.630 ohms     | -     | |
EXCITER WINDING DATA     | ||||
Exciter Frequency (Hz)     | 90 Hz     | |||
Exciter Poles     | 6     | |||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | ||
Stack Length     | 76.2 mm (3.0 inch)     |
76.2 mm (3.0 inch)     |
||
Coils/Group     | 1     | 2     | ||
Slots (Coils)     | 6     | 36     | ||
Turns (Coils)     | 105     | 6     | ||
No. & Size Wire     | 1 - #15     | 2 - #14.5     | ||
Coil Throw     | 1 - 2     | 1 - 6     | ||
Mean Length Turn (Calculated)     |
365.8 mm (14.4 inch)     |
304.8 mm (12.0 inch)     |
||
Copper Weight     | 3.9 kg (8.5 lb)     |
3.4 kg (7.5 lb)     |
||
Insulation     | Heavy Nytherm     | |||
Connection (2)     | Series     | 2 Parallel Star     | ||
Line Leads     | #14 965.2 mm (38.0 inch)     |
#10 152.4 mm (6.0 inch)     |
Show/hide table
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram #05 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram A |
Note: Wires 20, 22, and 24 are brought out as tap connections between 4th and 5th coil (18 turns from T0).
5N-9087 Generator
Show/hide table
MAIN STATOR AND ROTOR WINDING DATA     | ||||
ITEM     | STATOR     | ROTOR (RANDOM WOUND)     |
ROTOR (FORM WOUND)     |
|
Stack Height     | 152.4 mm (6.0 inch)     |
152.4 mm (6.0 inch)     |
-     | |
Slots     | 60     | -     | -     | |
Coil Throw     | 1 - 12     | -     | -     | |
Turns/Coil     | 7     | -     | -     | |
Turns/Pole     | -     | 110     | -     | |
No. & Wire Size     | 6 - #16     | 1 - #7     | -     | |
Mean Length Turn     | 934.7 mm (36.8 inch)     |
-     | -     | |
Copper Weight     | 27.9 kg (61.6 lb)     |
29.9 kg (65.9 lb)     |
-     | |
Inside Connection (1)     | 4/2 Parallel Star     | 4 in Series     | -     | |
Line Leads (No. & Size)     | 10 - #6     | -     | -     | |
Terminal bolt size     | 3/8 inch     | -     | -     | |
Low Voltage connected line resistance at 25 ° C (77 ° F)     |
0.0366 ohms     | -     | -     | |
Field lead resistance at 25 ° C (77 ° F)     |
-     | 0.56 ohms     | -     | |
EXCITER WINDING DATA     | ||||
Exciter Frequency (Hz)     | 90 Hz     | |||
Exciter Poles     | 6     | |||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | ||
Stack Length     | 76.2 mm (3.0 inch)     |
76.2 mm (3.0 inch)     |
||
Coils/Group     | 1     | 2     | ||
Slots (Coils)     | 6     | 36     | ||
Turns (Coils)     | 105     | 6     | ||
No. & Size Wire     | 1 - #15     | 2 - #14.5     | ||
Coil Throw     | 1 - 2     | 1 - 6     | ||
Mean Length Turn (Calculated)     |
365.8 mm (14.4 inch)     |
304.8 mm (12.0 inch)     |
||
Copper Weight     | 3.9 kg (8.5 lb)     |
3.4 kg (7.5 lb)     |
||
Insulation     | Heavy Nytherm     | |||
Connection (2)     | Series     | 2 Parallel Star     | ||
Line Leads     | #14 965.2 mm (38.0 inch)     |
#10 152.4 mm (6.0 inch)     |
Show/hide table
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram #31 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram A |
Note: Wires 20, 22, and 24 are brought out as tap connections between 4th and 5th coil (18 turns from T0).
5N-9088 Generator
Show/hide table
MAIN STATOR AND ROTOR WINDING DATA     | ||||
ITEM     | STATOR     | ROTOR (RANDOM WOUND)     |
ROTOR (FORM WOUND)     |
|
Stack Height     | 228.6 mm (9.0 inch)     |
228.6 mm (9.0 inch)     |
-     | |
Slots     | 60     | -     | -     | |
Coil Throw     | 1 - 12     | -     | -     | |
Turns/Coil     | 4     | -     | -     | |
Turns/Pole     | -     | 96     | -     | |
No. & Wire Size     | 5 - #15     | 1 - #9     | -     | |
Mean Length Turn     | 960.1 mm (37.8 inch)     |
-     | -     | |
Copper Weight     | 17.2 kg (37.98 lb)     |
18.2 kg (40.04 lb)     |
-     | |
Inside Connection (1)     | 4/2 Parallel Star     | 4 in Series     | -     | |
Line Leads (No. & Size)     | 10 - #6     | -     | -     | |
Terminal bolt size     | 3/8 inch     | -     | -     | |
Low Voltage connected line resistance at 25 ° C (77 ° F)     |
0.021 ohms     | -     | -     | |
Field lead resistance at 25 ° C (77 ° F)     |
-     | 0.80 ohms     | -     | |
EXCITER WINDING DATA     | ||||
Exciter Frequency (Hz)     | 90 Hz     | |||
Exciter Poles     | 6     | |||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | ||
Stack Length     | 50.8 mm (2.0 inch)     |
50.8 mm (2.0 inch)     |
||
Coils/Group     | 1     | 2     | ||
Slots (Coils)     | 6     | 36     | ||
Turns (Coils)     | 160     | 9     | ||
No. & Size Wire     | 1 - #16.5     | 1 - #14     | ||
Coil Throw     | 1 - 2     | 1 - 6     | ||
Mean Length Turn (Calculated)     |
113.3 mm (4.46 inch)     |
254.0 mm (10.0 inch)     |
||
Copper Weight     | 2.7 kg (6.0 lb)     |
1.5 kg (3.4 lb)     |
||
Insulation     | Heavy Nytherm     | |||
Connection (2)     | Series     | 2 Parallel Star     | ||
Line Leads     | #14 914.4 mm (36.0 inch)     |
#10 139.7 mm (5.5 inch)     |
Show/hide table
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram #31 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram E |
5N-9089 Generator
Show/hide table
MAIN STATOR AND ROTOR WINDING DATA     | ||||
ITEM     | STATOR     | ROTOR (RANDOM WOUND)     |
ROTOR (FORM WOUND)     |
|
Stack Height     | 203.2 mm (8.0 inch)     |
203.2 mm (8.0 inch)     |
-     | |
Slots     | 60     | -     | -     | |
Coil Throw     | 1 - 12     | -     | -     | |
Turns/Coil     | 3.6(3,3,4,4,4)     | -     | -     | |
Turns/Pole     | -     | 110     | -     | |
No. & Wire Size     | 7 - #14     | 1 - #7     | -     | |
Mean Length Turn     | 1036.3 mm (40.8 inch)     |
-     | -     | |
Copper Weight     | 30.5 kg (67.2 lb)     |
442.4 kg (975.4 lb)     |
-     | |
Inside Connection (1)     | 4/2 Parallel Star     | 4 in Series     | -     | |
Line Leads (No. & Size)     | 10 - #2     | -     | -     | |
Terminal bolt size     | 3/8 inch     | -     | -     | |
Low Voltage connected line resistance at 25 ° C (77 ° F)     |
0.012 ohms     | -     | -     | |
Field lead resistance at 25 ° C (77 ° F)     |
-     | 0.63 ohms     | -     | |
EXCITER WINDING DATA     | ||||
Exciter Frequency (Hz)     | 90 Hz     | |||
Exciter Poles     | 6     | |||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | ||
Stack Length     | 76.2 mm (3.0 inch)     |
76.2 mm (3.0 inch)     |
||
Coils/Group     | 1     | 2     | ||
Slots (Coils)     | 6     | 36     | ||
Turns (Coils)     | 105     | 6     | ||
No. & Size Wire     | 1 - #15     | 2 - #14.5     | ||
Coil Throw     | 1 - 2     | 1 - 6     | ||
Mean Length Turn (Calculated)     |
365.8 mm (14.4 inch)     |
304.8 mm (12.0 inch)     |
||
Copper Weight     | 3.9 kg (8.5 lb)     |
3.4 kg (7.5 lb)     |
||
Insulation     | Heavy Nytherm     | |||
Connection (2)     | Series     | 2 Parallel Star     | ||
Line Leads     | #14 965.2 mm (38.0 inch)     |
#10 152.4 mm (6.0 inch)     |
Show/hide table
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram #02 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram A |
5N-9432 Generator
Show/hide table
MAIN STATOR AND ROTOR WINDING DATA     | ||||
ITEM     | STATOR     | ROTOR (RANDOM WOUND)     |
ROTOR (FORM WOUND)     |
|
Stack Height     | 424.2 mm (16.7 inch)     |
431.8 mm (17.0 inch)     |
-     | |
Slots     | 54 (1)     | -     | -     | |
Coil Throw     | 1 - 12     | -     | -     | |
Turns/Coil     | 1     | -     | -     | |
Turns/Pole     | -     | 160     | -     | |
No. & Wire Size     | 30 - #13     | 1 - #7 sq     | -     | |
Mean Length Turn     | 1648.5 mm (64.9 inch)     |
-     | -     | |
Copper Weight     | 64.2 kg (141.5 lb)     |
98.4744 kg (217.1 lb)     |
-     | |
Inside Connection (1)     | 4 in Series     | 4 in Series     | -     | |
Line Leads (No. & Size)     | 20 - #00     | -     | -     | |
Terminal bolt size     | 3/8 inch     | -     | -     | |
Low Voltage connected line resistance at 25 ° C (77 ° F)     |
.0131     | -     | -     | |
Field lead resistance at 25 ° C (77 ° F)     |
-     | 1.17     | -     | |
EXCITER WINDING DATA     | ||||
Exciter Frequency (Hz)     | 90 Hz     | |||
Exciter Poles     | 6     | |||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | ||
Stack Length     | 127.0000 mm (5.0 inch)     |
127.0000 mm (5.0 inch)     |
||
Coils/Group     | 1     | 2     | ||
Slots (Coils)     | 6     | 36     | ||
Turns (Coils)     | 250     | 6     | ||
No. & Size Wire     | 1 - #18     | 2 - #15     | ||
Coil Throw     | 1 - 2     | 1 - 6     | ||
Mean Length Turn (Calculated)     |
464.8 mm (18.3 inch)     |
406.4 mm (16.0 inch)     |
||
Copper Weight     | 5.2 kg (11.5 lb)     |
2.7 kg (5.9 lb)     |
||
Insulation     | Heavy Nytherm     | |||
Connection (2)     | Series     | 2 Parallel Star     | ||
Line Leads     | #14 965.2 mm (38.0 inch)     |
#10 152.4 mm (6.0 inch)     |
Show/hide table
( 1 ) | Wind 6 coil groups with 4 coils per group, wind 6 coil groups with 5 coils per group. Put coil groups in stator (4,5,4,5-etc). |
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram #36 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram H |
Note: Wires 20, 22, and 24 are brought out as tap connections between the 9th and 10th coil (9 turns from T0).
Caterpillar Information System:
980G Wheel Loader, 824G Wheel Dozer, 825G Soil Compactor and 826G Landfill Compactor Implement Electronic Control System MID 082 - CID 0498 - FMI 06
525B Wheel Skidder and 535B Wheel Skidder Power Train Differential Pinion Preload - Adjust
980G Wheel Loader, 824G Wheel Dozer, 825G Soil Compactor and 826G Landfill Compactor Implement Electronic Control System MID 082 - CID 0498 - FMI 05
525B Wheel Skidder and 535B Wheel Skidder Power Train Bearing End Play (Output Transfer Gears) - Adjust
980G Wheel Loader, 824G Wheel Dozer, 825G Soil Compactor and 826G Landfill Compactor Implement Electronic Control System MID 082 - CID 0498 - FMI 03
651E and 657E Wheel Tractor-Scrapers Power Train Retarder
2000/05/01 The VIMSpc99 Software Version 1.1.7a Is Now Available {7601}
2000/05/29 New Turbocharger Oil Lines Groups {1052, 1307}
525B Wheel Skidder and 535B Wheel Skidder Power Train Transmission Clutch Running Clearance - Check
2000/05/01 Correction to Specifications Manual SENR9404 {4153}
2010/11/15 Correction to Specifications , "Pivot Shaft and Roller Frame" {4153}
D7R Series II Track-Type Tractor Rollover Protective Structure (ROPS) and Falling Object Protective Structure (FOPS) - Inspect
834G Wheel Dozer and 836G Landfill Compactor Electrohydraulic System MID 082 - CID 0498 - FMI 13
525B Wheel Skidder and 535B Wheel Skidder Power Train Differential Backlash and Bearings - Adjust
525B Wheel Skidder and 535B Wheel Skidder Power Train Axle Housing and Bearing Preload - Adjust
988G Wheel Loader Electrohydraulic System MID 082 - CID 0499 - FMI 03
651E and 657E Wheel Tractor-Scrapers Power Train Transmission Hydraulic Control Operation
525B Wheel Skidder and 535B Wheel Skidder Power Train Differential Lock Pressure - Check
D7R Series II Track-Type Tractor Transmission Breather - Clean
988G Wheel Loader Electrohydraulic System MID 082 - CID 0499 - FMI 05
D8R Series II Track-Type Tractor Engine Supplement Vibration Damper and Pulley - Remove and Install
988G Wheel Loader Machine Systems Bucket Links - Install
D7R Series II Track-Type Tractor Walk-Around Inspection
980G Wheel Loader, 824G Wheel Dozer, 825G Soil Compactor and 826G Landfill Compactor Implement Electronic Control System MID 082 - CID 0358 - FMI 03