Usage:

3406B 4JK
Conditions Which Generate This Code:

The CTR is used to indicate that the engine is beginning to run without cranking. The GSC activates the CTR when the engine speed is greater than the crank terminate adjustment. (Setpoint P011 should be 400 RPM.) Also, the starting motor relay has been deactivated. The CTR deactivates when the engine RPM reaches 0.

Note: Whenever the GSC activates the CTR, "K3" is shown on the lower display. When the CTR is not activated, "K3" is not shown.

The possible cause of a CID 0443 FMI 12 is an open coil or a shorted coil of the CTR.

The system responses to this diagnostic code are listed below.

  • If the CTR is activated and a CID 0443 FMI 12 occurs the engine will continue to run.

  • If a CID 0443 FMI 12 occurs and the CTR is not activated, then the engine is able to start and the engine is able to run.

The GSC treats a CID 0443 FMI 12 as an alarm fault. Active alarm faults are shown on the display when the "Alarm Codes" key is pressed. Also, the active alarm faults are shown when the ECS is in any position except the OFF/RESET position. Clear the diagnostic code from the fault log after troubleshooting is complete.

This troubleshooting procedure is used to correct an active CID 0443 FMI 12 or the troubleshooting procedure is for an inactive CID 0443 FMI 12.

Test Step 1. CHECK THE STATUS OF THE DIAGNOSTIC CODE.

  1. Turn the ECS to the OFF/RESET position and then turn the ECS to the STOP position.

  1. Press the "Alarm Codes" key.

  1. Observe the upper display. Check that the CID 0443 FMI 12 is active.

  1. If the diagnostic code is not active, enter the Service Mode. View the fault log for a OP1. Check that the diagnostic code is inactive.

Expected Result:

A CID 0443 FMI 12 is displayed as an active diagnostic code or CID 0443 FMI 12 is displayed as an inactive diagnostic code.

Results:

  • OK - The CID 0443 FMI 12 is active or the CID 0443 FMI 12 is inactive. Proceed to test step 2.

  • NOT OK - The CID 0443 FMI 12 has not occurred. The diagnostic code is not active and the diagnostic code is not inactive. Stop.

Test Step 2. CHECK THE INTERNAL CABLE OF THE RELAY MODULE.

Note: Only open the relay module in a dry environment. If the relay module is open for more than twenty minutes, replace the desiccant bag which is located within the housing of the GSC. See Testing And Adjusting, "Relay Module - Replace".

  1. Turn the ECS to the OFF/RESET position.

  1. Disconnect the battery negative cable.

  1. Temporarily, remove the relay module from the GSC. See Testing And Adjusting, "Relay Module - Replace".

  1. Check the cable that attaches the relay module to the GSC.

Expected Result:

The cable should be firmly seated in the connector. The clamp should be in place. The cable should not be damaged.

Results:

  • OK - The cable is firmly seated in the connector. The clamp is in place. The cable is not damaged. Reassemble the relay module to the GSC. Proceed to test step 3.

  • NOT OK - One or more of the components are damaged or the components are missing.

    Repair: Replace the clamp if the clamp is missing. If the cable is damaged, replace the GSC. See Testing and Adjusting, "EMCP Electronic Control (Generator Set) - Replace".

    Stop.

Test Step 3. PERFORM A FUNCTIONAL CHECK ON THE CTR.

  1. Turn the ECS to the OFF/RESET position.

  1. Reconnect the battery negative cable.

  1. Disconnect all wires from RM-16 of the relay module.

  1. Remove fuse "F1" from the relay module.

  1. At the relay module, measure the resistance from RM-16 to RM-3. Make a note of the resistance measurement.

  1. Start and run the engine. Ensure that the engine speed is greater than the crank terminate speed (P011).

  1. At the relay module, measure the resistance from RM-22 to RM-7. Make a note of the resistance measurement.

Expected Result:

The initial resistance measurement after removing the wires from the relay module should be greater than 5000 ohms. The resistance measurement should be less than 5 ohms after the crank terminate speed is exceeded.

Results:

  • OK - The resistance measurements are correct. The problem does not exist at this time. The initial problem was probably caused by a poor electrical connection or a short at one of the harness connectors that was disconnected and reconnected. Resume normal operation and watch for a recurrence. Stop.

  • NOT OK - Either one of the resistance measurements are NOT correct. The relay module has failed.

    Repair: Replace the relay module. See Testing And Adjusting, "Relay Module - Replace".

    Stop.

Caterpillar Information System:

SPS342 Skid Mounted Pumper Junction Box
SPS342 Skid Mounted Pumper Universal Remote Control Console
SPS342 Skid Mounted Pumper Emergency Stopping
SPS342 Skid Mounted Pumper Gauges and Indicators
Electronic Modular Control Panel II (EMCP II) GSC CID 0442 - FMI 12
3412C Engine Electronic Control System Components
325D and 329D Excavators and 325D Material Handler Machine System Specifications Relief Valve (Negative Flow Control) - Auxiliary, Combined Function
3606, 3608, 3612 and 3616 Engines and C280-12, C280-16, C280-6 and C280-8 Marine Engines Control Panel Normal Operation
3034 Marine Engine Engine Air Cleaner Element - Clean/Replace
Air/Fuel Ratio Control (Oxygen Feedback) Home Screen
Air/Fuel Ratio Control (Oxygen Feedback) Control Method
3606, 3608, 3612 and 3616 Engines and C280-12, C280-16, C280-6 and C280-8 Marine Engines Control Panel Service Tools
3034 Marine Engine Engine Crankcase Breather - Clean/Replace
2003/12/29 New Process for Reporting Incidents {0337}
G3600 Engines Valve Mechanism
SPS342 Skid Mounted Pumper Manual Stop Procedure
3606, 3608, 3612 and 3616 Engines and C280-12, C280-16, C280-6 and C280-8 Marine Engines Control Panel Abbreviations
3412C Engine Camshaft Idler Gear - Remove and Install
3606, 3608, 3612 and 3616 Engines and C280-12, C280-16, C280-6 and C280-8 Marine Engines Control Panel Schematics and Wiring Diagrams
Troubleshooting for Marine Engine Electronic Displays Cat Data Link Circuit - Test
Product Identification Numbers (PIN) Location Guide General Information
Electronic Modular Control Panel II+ (EMCP II+) GSC CID 0444 - FMI 12
3512B Marine Auxiliary Engine Engine Will Not Crank
Product Identification Numbers (PIN) Location Guide Excavator (Mining)
Back to top
The names Caterpillar, John Deere, JD, JCB, Hyundai or any other original equipment manufacturers are registered trademarks of the respective original equipment manufacturers. All names, descriptions, numbers and symbols are used for reference purposes only.
CH-Part.com is in no way associated with any of the manufacturers we have listed. All manufacturer's names and descriptions are for reference only.