3606, 3608, 3612 and 3616 Engines and C280-12, C280-16, C280-6 and C280-8 Marine Engines Control Panel Caterpillar


Normal Operation

Usage:

3616 1FN
The engine control panel (ECP) is a monitoring system and the ECP is a protection system for the engine. The ECP also controls the starting of the engine and the stopping of the engine. Before the engine can be started, the engine must be prelubed.

Prelubrication System

There are two types of prelubrication systems: continuous and intermittent.

Continuous Prelubrication

The continuous prelubrication system is designed to run whenever the engine is not running. The following conditions must be met in order for the prelube pump to run:

  • The engine is not running.

  • Any active engine shutdowns are reset.

Therefore, only electric powered motors are used. The engine is modified so that oil can only rise to the top of the block. This is accomplished by using a dump valve that dumps excess oil back to the sump. This dump valve closes when engine oil pressure is sensed. When the engine is not running there is essentially no pressure that exists in this system. Therefore, an oil sensor "SODS" is used in order to detect lubrication in the engine. When the detector senses oil, the indicator lamp for the engine prelubrication will be illuminated.

Intermittent Prelubrication

The intermittent prelubrication system is designed to run before the engine is started. The following conditions must be met in order for the prelube pump to run:

  • The engine is not running.

  • Any active engine shutdowns are reset.

  • The ECS is located in the LOCAL position or the REMOTE position.

If the ECS is located in the LOCAL position, the prelubrication switch must be located in the PRELUBE position. If the ECS is located in the REMOTE position, the automatic start/stop relay must be energized.

The system can use either an air motor or an electric motor in order to power the prelube pump. The system pumps the engine oil through the engine. Therefore, a pressure switch "SOPS" is used in order to detect the oil pressure. When the oil pressure in the main oil gallery of the engine reaches 9 kPa (1.3 psi), the indicator lamp for the engine prelubrication will be illuminated.

Engine Start

The engine can be started in two modes: local and remote.

Local Mode

The local mode indicates that the engine must be started from the engine control panel. The following conditions must be met in order to start the engine in the local mode.

  • The engine control switch is located in the LOCAL position.

  • The engine is prelubed.

  • The fuel control switch is located in the ON position.

The engine can be started by holding the prelubrication switch in the START position. When the engine reaches 170 Rpm, the switch can be released.

Remote Mode

The remote mode indicates that the engine can be started from a remote location by not using the engine control panel. The following conditions must be met in order to start the engine in the remote mode:

  • The engine control switch is located in the REMOTE position.

  • The fuel control switch is located in the ON position.

The engine can be started by actuating the customer supplied start switch. When the engine reaches 170 Rpm, the switch can be released.

Engine Stopping

Note: Refer to the engine Operation and Maintenance Manual for proper engine stopping procedure.

The engine will remain running until one of the following conditions are met:

  • Emergency stop is activated.

  • Normal stop is activated.

  • Shutdown mode is initiated.

Emergency Stopping

If an emergency stop is activated, the system will cause the governor actuator to shut off the fuel to the engine. The air shutoff at the intake of the engine will also be activated in order to shut off air supply to the engine.

Note: The engine control switch must be placed in the OFF/RESET position and the air shutoff must be manually reset before the engine can be restarted.

Normal Stopping

The engine is normally shut down in the following ways:

  • In local mode, the fuel control switch is placed in the OFF position.

  • In the remote mode, the customer supplied start/stop switch is used in order to de-energize the automatic start/stop relay.

When the conditions are met, the system will cause the governor actuator to shut off the fuel to the engine.

Engine Shutdown

If a fault shutdown occurs, the system will cause the governor actuator to shut off the fuel to the engine. The fault must be corrected before the engine can be operated.

Post Lubrication

After the engine comes to a stop, the postlube cycle will begin. The postlube is used in order to lubricate the turbochargers by utilizing the prelubrication oil pumps. The lubrication will run for a period of time after the engine stops. In the event of an emergency stop, the postlube cycle will not cycle.

Annunciator

The ECP can be ordered with an annunciator. The annunciator is controlled by the programmable logic controller (PLC). When an alarm or shutdown condition exists, an input into the PLC will go high. This will cause the output that is associated with the input to start flashing an indicator and an output from the PLC will energize the horn relay. The output will continue to flash until the "Acknowledge/Lamp Test" switch is momentarily switched to the Acknowledge position. The output will then remain illuminated and the horn relay will be de-energized. Once the alarm or shutdown condition has been cleared, pushing the reset button will cause the outputs of the PLC to shut off.

When the "Acknowledge/Lamp Test" switch is held in the Lamp Test position, the outputs of the PLC will be active. This will illuminate all the lights of the annunciator and the horn relay.

Caterpillar Information System:

3034 Marine Engine Engine Air Cleaner Element - Clean/Replace
Air/Fuel Ratio Control (Oxygen Feedback) Home Screen
Air/Fuel Ratio Control (Oxygen Feedback) Control Method
3606, 3608, 3612 and 3616 Engines and C280-12, C280-16, C280-6 and C280-8 Marine Engines Control Panel Service Tools
Electronic Modular Control Panel II (EMCP II) GSC CID 0441 - FMI 12 (for EUI Engines)
Electronic Modular Control Panel II (EMCP II) GSC CID 0336 - FMI 02
Electronic Modular Control Panel II (EMCP II) GSC CID 0334 - FMI 04 (for EUI Engines)
Electronic Modular Control Panel II+ (EMCP II+) GSC CID 0334 - FMI 03 (for MUI and PEEC Engines)
3412C Engine General Information
Air/Fuel Ratio Control (Oxygen Feedback) System Overview
G3516B Engines MID 036 - CID 0416 - FMI 06 Ignition Transformer Secondary #16 short to ground
G3516B Engines MID 036 - CID 0415 - FMI 06 Ignition Transformer Secondary #15 short to ground
325D and 329D Excavators and 325D Material Handler Machine System Specifications Relief Valve (Negative Flow Control) - Auxiliary, Combined Function
3412C Engine Electronic Control System Components
Electronic Modular Control Panel II (EMCP II) GSC CID 0442 - FMI 12
SPS342 Skid Mounted Pumper Gauges and Indicators
SPS342 Skid Mounted Pumper Emergency Stopping
SPS342 Skid Mounted Pumper Universal Remote Control Console
SPS342 Skid Mounted Pumper Junction Box
Electronic Modular Control Panel II (EMCP II) GSC CID 0443 - FMI 12
3034 Marine Engine Engine Crankcase Breather - Clean/Replace
2003/12/29 New Process for Reporting Incidents {0337}
G3600 Engines Valve Mechanism
SPS342 Skid Mounted Pumper Manual Stop Procedure
Back to top
The names Caterpillar, John Deere, JD, JCB, Hyundai or any other original equipment manufacturers are registered trademarks of the respective original equipment manufacturers. All names, descriptions, numbers and symbols are used for reference purposes only.
CH-Part.com is in no way associated with any of the manufacturers we have listed. All manufacturer's names and descriptions are for reference only.