If the Monitoring System detects a parameter that has exceeded a trip point, an internal timer will be activated. The parameter must fall to a specific value below the value of the trip point in order to reset the timer. The difference between the specific value and the value of the trip point is called the Hysteresis. If the delay time is exceeded the Monitoring System will initiate the programmed action. The Engine Monitoring System can initiate the following events: Warning, Derate and Shutdown. Not all of these events are available for each parameter. The engine monitoring system is enabled after the engine is started. When the engine is within 50 rpm of low idle, the ECM will check the parameters. The ECM checks for oil pressure after a 10 second delay. The delay is designed to eliminate false low oil pressure warnings.
If the ECM generates an event, the event will be displayed as a "Status Flag" on the "Status" screen on the Cat ET. Go to the "Information" menu on Cat ET and activate the "Status" screen in order to see the active event. The event will be displayed across the top of the screen with the name of the ECM and serial number of the product.
The Cat ET can be used to set the programmable limits of the parameters. To set the limits, go to the "Service" menu on Cat ET. Select "Monitoring System". The screen for the Monitoring System has the following four columns: Parameter description, State, Trip point and Delay time. The following list describes the four columns:
Parameter description - The function that is being monitored
State - Programmed as ON, OFF or Always ON
Trip point - Programmed limits for safe operation
Delay time - Programmed time before action is taken.
In order to change the programmed limit, highlight the action or delay time and press the "Change" button. If a password is required to change the limit the Monitoring System will ask for either a "Factory Password" or a "Customer Password". Refer to the diagnostic procedure Troubleshooting, "Factory Passwords" for information on passwords.
Note: Use care when you program the trip point and the delay times. The ECM response must be correct for the application. If the legal range is not exceeded the engine monitoring system will accept any setting. Table 1 contains the parameters and the default limits for the Monitoring System.
Engine Monitoring System | |||||||
---|---|---|---|---|---|---|---|
Parameter | ECM Response | Default Trip Point | Default Delay Time | Limits | |||
Range for Trip Point | Delay Time | Hysteresis | |||||
Low | High | ||||||
Low System Voltage(1) | Off | ||||||
Warning | 20 VDC | 10 Seconds | 20 VDC | 30 VDC | 1 to 30 seconds | 2 VDC | |
Low Oil Pressure | Off | ||||||
Warning | (2) | 4 Seconds | N/A | 1 to 15 seconds | |
||
Shutdown | (2) | 9 Seconds | N/A | 1 to 15 seconds | |
||
High Coolant Temperature | Off | ||||||
Warning | |
5 Seconds | |
|
1 to 60 Seconds | |
|
Derate(3) | |
30 Seconds | |
|
1 to 60 Seconds | |
|
Shutdown | |
5 Seconds | |
|
1 to 60 Seconds | |
|
Low Coolant Temperature(1) | Off | ||||||
Warning (4) | |
5 Seconds | |
|
1 to 60 Seconds | |
|
Engine Overspeed | Off | ||||||
Warning | 118% of Rated Speed | 0 Seconds | 1200 rpm | 2400 rpm | 0 to 5 Seconds | 100 rpm | |
Shutdown | 118% of Rated Speed | 0 Seconds | 1200 rpm | 2400 rpm | 0 to 5 Seconds | 100 rpm | |
Air Filter Restriction Pressure(1) | Off | ||||||
Warning | |
5 Seconds | |
|
1 to 60 Seconds | N/A | |
Derate(5) | |
5 Seconds | |
10 kPa
(1.45 psi) |
1 to 60 Seconds | N/A | |
High Exhaust Temperature(1) | Off | ||||||
Warning | (6) | 5 Seconds | |
800 °C
(1472 °F) |
1 to 60 Seconds | |
|
Derate(7) | (6) | 5 Seconds | 1 to 60 Seconds | |
|||
Oil Filter Differential(1) | Off | ||||||
Warning | 105 kPa
(15 psi) |
5 Seconds | |
140 kPa
(20 psi) |
1 to 60 Seconds | |
|
Fuel Filter Differential(1) | Off | ||||||
Warning | |
5 Seconds | |
140 kPa
(20 psi) |
1 to 60 Seconds | |
|
Crankcase Pressure | Off | ||||||
Warning | |
3 Seconds | 0.5 kPa
(0.1 psi) |
|
1 to 30 Seconds | |
|
Derate(8) | |
10 Seconds | 0.5 kPa
(0.1 psi) |
|
1 to 60 Seconds | |
|
Shutdown | 3.5 kPa
(0.5 psi) |
3 Seconds | 0.5 kPa
(0.1 psi) |
|
1 to 30 Seconds | |
|
Aftercooler Water Temperature | Off | ||||||
Warning | |
5 Seconds | |
|
1 to 60 Seconds | |
|
Derate(9) | |
5 Seconds | |
|
1 to 60 Seconds | |
|
Shutdown | |
5 Seconds | |
|
1 to 60 Seconds | |
(1) | Some Engine Monitoring parameters do not have the ability to perform an engine shutdown. |
(2) | Refer to the oil pressure map. |
(3) | If the trip point for the derate is exceeded the derate will reduce power linearly from 0 % to a maximum of 25 % over a period of 480 seconds. |
(4) | The engine must be operated at an average load that is greater than 20 % for ten minutes. When the average load is greater than 20% and the coolant temperature is below |
(5) | Derates power 2% per kPa to a maximum derate of 25%. This derate will not reset, if the value falls below the value of the trip point. |
(6) | Refer to the Performance and Ratings manual. |
(7) | If the trip point is exceeded, engine power will be derated 2% for each 15 second time period. The maximum derate is 20%. |
(8) | Derates power 15% over a 480 second time period. |
(9) | If the trip point for the derate is exceeded the derate will reduce power linearly from 0 % to a maximum of 25 % over a period of 480 seconds. |
Note: The derate may not have an effect when the engine is not operating at the maximum torque limit. The derate is subtracted from the maximum torque limit. The current rack limit may be below the derated rack limit. There will be no effect on engine operation until the derated rack limit falls below the current rack limit. Rack limits are added together. The maximum torque limit is
Illustration 1 | g00863970 |
Map of the engine oil pressure versus the engine rpm (X) Engine rpm (Y) Engine oil pressure in kPa (1) Hysteresis (minimum and maximum engine oil pressure) (2) Normal engine oil pressure |
Example 1
Default settings are used for high coolant temperature as the coolant temperature increases to
Illustration 2 | g00869677 |
Typical example 1 |
Parameter | Enable and/or Disable | ECM Response | Trip Point | Delay Time |
---|---|---|---|---|
High Coolant Temperature | Enabled | Warning | |
5 Seconds |
Disabled | Active Engine Derate | |
5 Seconds | |
Enabled | Shutdown | |
5 Seconds |
Example 2
Default settings are used for High Coolant Temperature as the coolant temperature fluctuates around
Illustration 3 | g00869680 |
Typical example 2 |
Parameter | Enable and/or Disable | ECM Response | Trip Point | Delay Time |
---|---|---|---|---|
High Coolant Temperature | Enabled | Warning | |
5 Seconds |
Disabled | Active Engine Derate | |
5 Seconds | |
Enabled | Shutdown | |
5 Seconds |
Example 3
Default settings are used for low engine oil pressure. The engine oil pressure is low when the engine is started. Once the system is enabled there is an automatic ten second delay. The delay compensates for the low engine oil pressure after the engine oil has been changed. After the delay, the timer starts due to the low engine oil pressure. A warning is issued after one second. A shutdown occurs after one second.
Illustration 4 | g00869678 |
Typical example |
Parameter | Enable and/or Disable | ECM Response | Delay Time |
---|---|---|---|
Engine Oil Pressure | Enabled | Warning | 1 Seconds |
Disabled | Active Engine Derate | 5 Seconds | |
Enabled | Shutdown | 1 Seconds |