Illustration 1 | g01269268 |
Connections of the blade sideshift right solenoid |
This diagnostic code is associated with the blade sideshift right solenoid. The FMI 06 means that the Implement ECM has determined that the current of the solenoid circuit is above normal.
The Implement ECM provides a PWM signal to the solenoid in order to provide proportional control of the solenoid. The ECM will vary the electrical current of the PWM signal, based on the input command that is received from the position sensor for the blade sideshift. The sensor is located in the assembly of the right joystick.
Some possible causes of this diagnostic code are listed:
- The energize circuit of the solenoid is shorted to ground.
- The solenoid has failed.
- The ECM has failed. This is unlikely.
Before performing this procedure, inspect the harness connectors that are involved in the circuit. Poor connections can often be the cause of a problem in an electrical circuit. Inspect the connections for the following:
- Connections are clean.
- Connections are secure.
- Connections are in good condition.
If a problem with a connection is found, correct the problem and verify that this diagnostic code is active before performing this procedure.
Note: The following test procedure may create other diagnostic codes. Ignore these created diagnostic codes and clear these diagnostic codes when the original diagnostic code has been corrected.
Note: The resistance of the solenoid coil should be 8.7 ± .4 ohms at 25 °C (77.0 °F).
Test Step 1. CHECK THE SOLENOID
- Turn the disconnect switch and the key start switch to the ON position. Do not start the engine.
- Observe the status of the diagnostic code.
- Disconnect the solenoid with the active diagnostic code from the machine harness.
Expected Result:
The active CID 2166 FMI 06 diagnostic code changes to a CID 2166 FMI 05 diagnostic code when the solenoid is disconnected.
Results:
- YES - The active CID 2166 FMI 06 diagnostic code changes to a CID 2166 FMI 05 diagnostic code when the solenoid is disconnected. The circuit is correct.
Repair: The solenoid has failed. Repeat this test "CHECK THE SOLENOID" in order to verify the solenoid failure. Replace the solenoid.
STOP
- NO - The CID 2166 FMI 06 remains active when the solenoid is disconnected. The solenoid is not causing the problem. Proceed to Test Step 2.
Test Step 2. CHECK THE ENERGIZE CIRCUIT OF THE SOLENOID FOR A SHORT TO GROUND
- Turn the key start switch and the disconnect switch to the OFF position.
- The solenoid remains disconnected from the machine harness.
- Disconnect the ECM connectors J1 and J2 from the ECM.
- At the ECM connectors of the machine harness, measure the resistance from the signal contact J1-66 (wire U749-BR) to frame ground. Measure the resistance from the signal contact J1-66 (wire U749-BR) to all of the other J1 and J2 contacts that are used in the ECM connectors.
Expected Result:
Each resistance measurement is greater than 5000 ohms.
Results:
- OK - Each resistance measurement is greater than 5000 ohms. The machine harness is correct. Proceed to Test Step 3.
- NOT OK - One or more of the resistance measurements is less than 5000 ohms. There is a short in the machine harness. The short is between wire U749-BR and the circuit with the low resistance measurement.
Repair: Repair the machine harness or replace the machine harness.
STOP
Test Step 3. CHECK THE STATUS OF THE DIAGNOSTIC CODE
- Perform the following:
- Visually inspect the harness connectors.
- Clean the contacts of the harness connectors.
- Visually inspect the insulation of the wires for damage that is caused by excessive heat, battery acid, or chafing.
- Visually inspect the harness connectors.
- Perform a 45 N (10 lb) pull test on each of the wires that are associated with the sensor circuit.
- Reconnect all harness connectors. Verify the following:
- The connectors are fully seated.
- The clips for each connector are completely fastened.
- The connectors are fully seated.
- Turn the disconnect switch and the key start switch to the ON position.
- Operate the machine.
- Check the status of the CID 2166 FMI 06 diagnostic code.
Expected Result:
The CID 2166 FMI 06 diagnostic code is still active.
Results:
- YES - The CID 2166 FMI 06diagnostic code is still active. The diagnostic code has not been corrected.
Repair: Check the circuit again. Perform a Wiggle Test on the machine wiring harness with the Caterpillar Electronic Technician (Cat ET) service tool. The Wiggle Test can detect the following in the machine wiring harness:
- Momentary shorts
- Intermittent shorts
- Opens
STOP
- Momentary shorts
- NO - The CID 2166 FMI 06 is not active. The diagnostic code does not exist at this time.
Repair: The initial diagnostic code was probably caused by a poor electrical connection or a short at one of the harness connectors that was disconnected and reconnected. Resume normal machine operation.
STOP