120M Series 2, 120M2, 12M Series 2, 12M Series II, 140M Series 2 and 160M Series 2 Motor Graders Implement Electronic Control System Caterpillar


MID 082 - CID 2166 - FMI 05

Usage:

12M 2 F9B
Conditions Which Generate This Code:


Illustration 1g01269268

Connections of the blade sideshift right solenoid

This diagnostic code is associated with the blade sideshift right solenoid. The FMI 05 means that the ECM has determined that the current for the solenoid circuit is below normal.

The Implement ECM provides a PWM signal to the solenoid in order to provide proportional control of the solenoid. The ECM will vary the electrical current of the PWM signal, based on the input command that is received from the position sensor for the blade sideshift. The sensor is located in the assembly of the right joystick .

Some possible causes of this diagnostic code are listed below:

  • The energize circuit of the solenoid is open.

  • The return circuit of the solenoid is open.

  • The solenoid has failed.

  • The ECM has failed. This is unlikely.

Before performing this procedure, inspect the harness connectors that are involved in the circuit. Poor connections can often be the cause of a problem in an electrical circuit. Inspect the connections for the following:

  • Connections are clean.

  • Connections are secure.

  • Connections are in good condition.

If a problem with a connection is found, correct the problem and verify that this diagnostic code is active before performing this procedure.

Note: The following test procedure may create other diagnostic codes. Ignore these created diagnostic codes and clear these diagnostic codes when the original diagnostic code has been corrected.

Note: The resistance of the solenoid coil should be 8.7 ± .4 ohms at 25 °C (77.0 °F).

Test Step 1. CHECK THE SOLENOID

  1. Disconnect the solenoid from the machine harness.

  1. At the machine harness connector for the solenoid, place a jumper wire from contact 1 (wire U749-BR) to contact 2 (wire H862-GY).

  1. Turn the disconnect switch and the key start switch to the ON position. Do not start the engine.

  1. Observe the status of the CID 2166 FMI 05 diagnostic code.

Expected Result:

The active diagnostic code changes from an FMI 05 diagnostic code to an FMI 06 diagnostic code when the jumper wire is installed.

Results:

  • YES - The active diagnostic code changes from an FMI 05 diagnostic code to an FMI 06 diagnostic code when the jumper wire is installed. The solenoid has failed.

    Repair: The solenoid has failed. Repeat this Test Step "CHECK THE SOLENOID" in order to verify the solenoid failure. Replace the solenoid. Verify that the new solenoid corrects the problem.

    STOP

  • NO - The CID 2166 FMI 05 diagnostic code remains active. The jumper wire does not affect the status of the diagnostic code. The solenoid is not the cause of the problem. Proceed to Test Step 2.

Test Step 2. CHECK THE CIRCUIT FOR AN OPEN

  1. Turn the key start switch and the disconnect switch to the OFF position.

  1. Disconnect the ECM connector of the machine harness J1 from the ECM.

  1. The jumper wire that was installed in the previous Test Step remains in place.

  1. At the machine harness connector J1 for the ECM, measure the resistance from the return contact J1-55 (wire H862-GY) and energize contact J1-66 (wire U749-BR).

Expected Result:

The measurement of the resistance is less than 5 ohms.

Results:

  • OK - The measurement of the resistance is less than 5 ohms. The circuit is not open in the machine harness. Proceed to Test Step 3.

  • NOT OK - The measurement of the resistance is greater than 5000 ohms. The measurement of the resistance is not correct. There is an open connection in the machine harness or a bad connection in the machine harness. A resistance measurement that is much greater than 5 ohms but less than 5000 ohms could indicate that one of the connection points in the circuit is not an open connection, but the connection is poor.

    Repair: The open connection or the possible poor connection is in supply wire U749-BR or in the return wire H862-GY of the machine harness. Refer to the Electrical Schematic of the machine. Check all of the connectors that are in the solenoid circuit. Inspect the connections for the following:

    • Connections are clean.

    • Connections are secure.

    • Connections are in good condition.

    Repair the machine harness or replace the machine harness.

    STOP

Test Step 3. CHECK THE OPERATION OF THE ECM

  1. The disconnect switch and the key start switch remain in the OFF position.

  1. The machine harness connector for the solenoid and the ECM J1 connector remain disconnected.

  1. Remove the jumper wire that was installed in the last test step.

  1. At the machine harness connector J1 for the ECM, use a 151-6320 Removal Tool to remove the solenoid wire U749-BR and the socket at contact J1-66 from the harness connector.

  1. Reconnect the machine harness J2 connector to the ECM.

  1. Turn the disconnect switch and the key start switch to the ON position.

  1. Use a 7X-1710 Multimeter Probe that is not connected to a multimeter or a similar device to make contact with the ECM pin at J1-66 through the empty space in the J1 connector.

  1. Observe the status of the active CID 2166 FMI 05 diagnostic code and ground the other end of the 7X-1710 Multimeter Probe to the frame ground.

Expected Result:

The CID 2166 FMI 05 diagnostic code is no longer active. A CID 2166 FMI 06 diagnostic code becomes active when the ECM pin at J1-66 is grounded.

Results:

  • YES - The CID 2166 FMI 05 diagnostic code is no longer active. A CID 2166 FMI 06 diagnostic code has been activated after the ECM pin is grounded. The ECM has responded correctly to the grounded circuit condition in the solenoid circuit. The ECM is not most likely cause of the problem. Reconnect the solenoid wire into the correct connector in the ECM. Proceed to Test Step 4.

  • NO - The CID 2166 FMI 05 diagnostic code remains active. The status of the active diagnostic code does not change when the ECM pin for the solenoid is grounded.

    Repair: The ECM has not responded correctly to the grounded condition in the solenoid circuit. The operation of the ECM is not correct.Prior to replacing an ECM, always contact your dealership's Technical Communicator for possible consultation with Caterpillar. This consultation may greatly reduce repair time. If the ECM must be replaced, refer to Testing and Adjusting, "Electronic Control Module (ECM) - Replace".

    STOP

Test Step 4. CHECK THE STATUS OF THE DIAGNOSTIC CODE

  1. Perform the following:

    • Visually inspect the harness connectors.

    • Clean the contacts of the harness connectors.

    • Visually inspect the insulation of the wires for damage that is caused by excessive heat, battery acid, or chafing.

  1. Perform a 45 N (10 lb) pull test on each of the wires that are associated with the sensor circuit.

  1. Reconnect all harness connectors. Verify the following:

    • The connectors are fully seated.

    • The clips for each connector are completely fastened.

  1. Turn the disconnect switch and the key start switch to the ON position.

  1. Operate the machine.

  1. Check the status of the CID 2166 FMI 05 diagnostic code.

Expected Result:

The CID 2166 FMI 05 diagnostic code is active.

Results:

  • YES - The CID 2166 FMI 05 diagnostic code is active. The diagnostic code has not been corrected. The ECM may have failed.

    Repair: Check the circuit again. Perform a Wiggle Test on the machine wiring harness with the Caterpillar Electronic Technician (Cat ET) service tool. The Wiggle Test can detect the following in the machine wiring harness:

    • Momentary shorts

    • Intermittent shorts

    • Opens

    If the cause of the problem is not found in the machine harness, the ECM may have failed. This is unlikely due to the following:

    • The ECM responded correctly to the grounded condition in the previous test step.

    Verify that all possible causes of the diagnostic code have been investigated. Exit this procedure and perform this procedure again.Prior to replacing an ECM, always contact your dealership's Technical Communicator for possible consultation with Caterpillar. This consultation may greatly reduce repair time. If the cause of the active diagnostic code is not found and the ECM must be replaced, refer to Testing and Adjusting, "Electronic Control Module (ECM) - Replace".

    STOP

  • NO - The CID 2166 FMI 05 diagnostic code is not active. The diagnostic code does not exist at this time.

    Repair: The initial diagnostic code was probably caused by a poor electrical connection at one of the harness connectors that was disconnected and reconnected. Resume normal machine operation.

    STOP

Caterpillar Information System:

120M Series 2, 120M2, 12M Series 2, 12M Series II, 140M Series 2 and 160M Series 2 Motor Graders Implement Electronic Control System MID 082 - CID 2166 - FMI 03
2010/07/14 A New Accumulator Group that Complies with CSA B51-09 is Available for Certain Motor Graders {4263, 4264}
AP555E and BG555E Asphalt Pavers Roading the Machine
120M Series 2, 120M2, 12M Series 2, 12M Series II, 140M Series 2 and 160M Series 2 Motor Graders Implement Electronic Control System MID 082 - CID 2165 - FMI 13
120M Series 2, 120M2, 12M Series 2, 12M Series II, 140M Series 2 and 160M Series 2 Motor Graders Implement Electronic Control System MID 082 - CID 2165 - FMI 06
120M Series 2, 120M2, 12M Series 2, 12M Series II, 140M Series 2 and 160M Series 2 Motor Graders Implement Electronic Control System MID 082 - CID 2165 - FMI 05
2010/02/15 New Software is Now Used for Product Link On Certain Cat Products {7606, 7620}
120M Series 2, 120M2, 12M Series 2, 12M Series II, 140M Series 2 and 160M Series 2 Motor Graders Implement Electronic Control System MID 082 - CID 2165 - FMI 03
120M Series 2, 120M2, 12M Series 2, 12M Series II, 140M Series 2 and 160M Series 2 Motor Graders Implement Electronic Control System MID 082 - CID 2163 - FMI 13
120M Series 2, 120M2, 12M Series 2, 12M Series II, 140M Series 2 and 160M Series 2 Motor Graders Implement Electronic Control System MID 145 - CID 2201 - FMI 14
120M Series 2, 120M2, 12M Series 2, 12M Series II, 140M Series 2 and 160M Series 2 Motor Graders Implement Electronic Control System MID 145 - CID 2201 - FMI 13
120M Series 2, 120M2, 12M Series 2, 12M Series II, 140M Series 2 and 160M Series 2 Motor Graders Implement Electronic Control System MID 082 - CID 2163 - FMI 06
120M Series 2, 120M2, 12M Series 2, 12M Series II, 140M Series 2 and 160M Series 2 Motor Graders Implement Electronic Control System MID 082 - CID 2166 - FMI 06
120M Series 2, 120M2, 12M Series 2, 12M Series II, 140M Series 2 and 160M Series 2 Motor Graders Implement Electronic Control System MID 082 - CID 2166 - FMI 13
CP44 and CS44 Vibratory Soil Compactors Propel System Pump Control (Manual Displacement Control) Neutral - Test and Adjust - Drum
C13 Tier 4 Final Engines Fan Drive
527 Track-Type Skidder Ether Starting Aid Cylinder - Replace - If Equipped
527 Track-Type Skidder Fuses - Replace
CP44 and CS44 Vibratory Soil Compactors Machine Systems Operator Controls (Hydraulic System) - Blade
Disassembly and Assembly Procedures for Idlers with Conventional Duo-Cone Seals {4159, 4180} Disassembly and Assembly Procedures for Idlers with Conventional Duo-Cone Seals {4159, 4180}
CP44 and CS44 Vibratory Soil Compactors Machine Systems Hydraulic Cylinder (Blade)
AP555E and BG555E Asphalt Pavers Conveyor Override Control
416E, 420E and 430E Backhoe Loaders Transmission (Standard Shift) Transmission (Standard Shift)
CP44 and CS44 Vibratory Soil Compactors Machine Systems Hydraulic Schematic (Steering System)