VR3F VOLTAGE GENERATOR PERMANENT MAGNET EXCITED SR4 GENERATO Caterpillar


Problem 3 - High AC Voltage

Usage:

Procedure A - Check Engine RPM (Frequency)

Procedure B - Adjust Voltage Level

The voltage level adjustment range must be within +10 to -25% of rated voltage.

* If the voltage level cannot be adjusted as described:

a. Check accuracy of voltmeter.

b. Go to Procedure C.

Procedure C - Check Fuses Located On Regulator

* If fuse(s) have failed:

Look for possible short circuits that could cause fuse failure such as shorted exciter stator L1, etc.

* If fuse(s) are okay:

Go to Procedure D.

Procedure D - Check Connections To Regulator

* If connections are correct:

Go to Procedure E.

Procedure E - Isolate Attachments

Disconnect attachments such as manual voltage control, etc. Operate at rated rpm.

NOTE: If remote mounted voltage adjustment is disconnected, connect jumper across terminals 4 and 7.

* If generator output voltage is normal:

Check attachments.

* If voltage cannot be adjusted to rated voltage at rated frequency:

a. Replace regulator.

b. Bench test the regulator; see Bench Test.

Caterpillar Information System:

VR3F VOLTAGE GENERATOR PERMANENT MAGNET EXCITED SR4 GENERATO Problem 2 - Low AC Voltage
VR3F VOLTAGE GENERATOR PERMANENT MAGNET EXCITED SR4 GENERATO Problem 1 - No AC Voltage
VR3F VOLTAGE GENERATOR PERMANENT MAGNET EXCITED SR4 GENERATO Problem List
VR3F VOLTAGE GENERATOR PERMANENT MAGNET EXCITED SR4 GENERATO Introduction
VR3F VOLTAGE GENERATOR PERMANENT MAGNET EXCITED SR4 GENERATO Testing And Adjusting
VR3F VOLTAGE GENERATOR PERMANENT MAGNET EXCITED SR4 GENERATO Systems Operation
3176B, C-10, C-12 & 3406E TRUCK ENGINES Glossary Of Terms
3176B, C-10, C-12 & 3406E TRUCK ENGINES Troubleshooting With a Diagnostic Code
3176B, C-10, C-12 & 3406E TRUCK ENGINES Troubleshooting Without a Diagnostic Code
3176B, C-10, C-12 & 3406E TRUCK ENGINES Service Information Report
3176B, C-10, C-12 & 3406E TRUCK ENGINES How to use the ECM Date/Time Stamped Information
3176B, C-10, C-12 & 3406E TRUCK ENGINES ECM Snapshot
VR3F VOLTAGE GENERATOR PERMANENT MAGNET EXCITED SR4 GENERATO Problem 4 - Unstable AC Voltage
VR3F VOLTAGE GENERATOR PERMANENT MAGNET EXCITED SR4 GENERATO Bench Test
VR3F VOLTAGE GENERATOR PERMANENT MAGNET EXCITED SR4 GENERATO Remote Voltage Control
VR3F VOLTAGE GENERATOR PERMANENT MAGNET EXCITED SR4 GENERATO Manual Voltage Control
VR3F VOLTAGE GENERATOR PERMANENT MAGNET EXCITED SR4 GENERATO Voltage Droop Transformer And Adjustment Rheostat For Parallel Operation
ELECTRONIC MODULAR CONTROL PANEL II+ (EMCPII+) FOR MUI ENGIN Systems Operation
ELECTRONIC MODULAR CONTROL PANEL II+ (EMCPII+) FOR MUI ENGIN Testing And Adjusting
G3408 & G3412 ENGINES Systems Operation
G3408 & G3412 ENGINES Testing & Adjusting
3400 ELECTRONIC MARINE ENGINES 3408 and 3412 High Performance Marine Engine Electronic Control System
3400 ELECTRONIC MARINE ENGINES Throttle and Engine Synchronization System
3400 ELECTRONIC MARINE ENGINES Connecting the PORT and STBD Throttle Without Engine Synchronization
Back to top
The names Caterpillar, John Deere, JD, JCB, Hyundai or any other original equipment manufacturers are registered trademarks of the respective original equipment manufacturers. All names, descriptions, numbers and symbols are used for reference purposes only.
CH-Part.com is in no way associated with any of the manufacturers we have listed. All manufacturer's names and descriptions are for reference only.