AP600D, AP655D, BG600D and BG655D Asphalt Pavers Caterpillar


MID 157 - CID 2553 - FMI 05

Usage:

BG655D B5D
Conditions Which Generate This Code:


Illustration 1g01370815

Schematic of the Right Hopper Raise Solenoid

This diagnostic code is associated with the Right Hopper Raise Solenoid. The FMI 05 means that the RH Operator ECM has detected that the current for the solenoid circuit is below normal.

Note: The RH Operator ECM is located under the RH Operator platform.

Conditions that could causes this diagnostic code to be activated are:

  • The energize circuit of the solenoid is open.

  • The return circuit of the solenoid is open.

  • The solenoid has failed.

  • The ECM has failed. This is unlikely.

Note: Before performing this procedure, inspect the harness connectors that are involved in the circuit. Poor connections can often be the cause of a problem in an electrical circuit. Verify that all connections in the circuit are clean, secure and in good condition. If a problem with a connection is found, correct the problem and verify that this diagnostic code is active before performing this procedure.

System Response:

When this diagnostic code is active, the following occurs:

  • Right hopper raise disabled.

  • Operator station fault lamp is active.

Note: The following test procedure may create other diagnostic codes. Ignore these created diagnostic codes and clear these diagnostic codes when the original diagnostic code has been corrected.

Note: The resistance of the solenoid coil should be 27 ± 1.4 ohms at 20 °C (68.0 °F).

Test Step 1. CHECK THE SOLENOID

  1. Disconnect the machine harness from the solenoid at the Hopper Raise hydraulic valve.

  1. At the machine harness connector for the solenoid, place a jumper wire from contact 1 (wire A861-BR) to contact 2 (wire 200-BK).

  1. Turn the disconnect switch and the key start switch to the ON position. Do not start the engine.

  1. Observe the status of the CID 2553 FMI 05 diagnostic code.

Expected Result:

The CID 2553 FMI 05 diagnostic code is no longer active. A CID 2553 FMI 06 diagnostic code becomes active when the jumper wire is connected.

Results:

  • YES - The CID 2553 FMI 05 diagnostic code is no longer active. A CID 2553 FMI 06 diagnostic code becomes active when the jumper wire is connected. The solenoid has failed.

    Repair: Repeat this Test Step "CHECK THE SOLENOID" in order to verify the solenoid failure. The resistance of the solenoid coil should be 27 ± 1.4 ohms at 20 °C (68.0 °F). Replace the solenoid. Verify that the new solenoid corrects the problem.

    STOP

  • NO - The CID 2553 FMI 05 diagnostic code remains active. The jumper wire does not affect the status of the active diagnostic code. The solenoid is not causing the problem. Proceed to Test Step 2.

Test Step 2. CHECK THE CIRCUIT FOR AN OPEN

The jumper wire that was installed in the previous Test Step remains in place.

  1. Turn the disconnect switch and the key start switch to the OFF position.

  1. Disconnect the machine harness ECM connector J2 from the ECM.

  1. At the machine harness connector J2 for the ECM, measure the resistance from contact J2-3 (wire A861-BR) to contactground.

  1. While observing the multimeter resistance measurement, wiggle the machine harness connectors for the ECM and wiggle the machine harness connector for the solenoid. Gently pull on the wires and move the wires around.

Expected Result:

The resistance measurement is less than 5.0 ohms at all times during the manipulation of the harness and connectors.

Results:

  • OK - The resistance measurement is less than 5.0 ohms. The resistance measurement is not indicating an open or a bad connection in the circuit. Proceed to Test Step 3.

  • NOT OK - The resistance measurement is greater than 5.0 ohms. The resistance measurement is indicating and open circuit or a bad connection in the machine harness.

    Repair: A resistance measurement that is greater than 5000 ohms could indicate that a wire is either not connected or is open. A resistance measurement that is greater than 5.0 ohms but less than 5000 ohms could indicate that one of the connection points in the circuit is not open but is not a good connection.The open or possible bad connection is in supply wire A861-BR or in return wire 200-BK of the machine harness. Refer to the complete machine Electrical System Schematic. Check all of the connectors that are in the solenoid circuit. Ensure that all connections are clean, secure and in good condition. Repair the machine harness or replace the machine harness.

    STOP

Test Step 3. CHECK THE OPERATION OF THE ECM

The disconnect switch and the key start switch remain in the OFF position. The machine harness connector for the solenoid and the ECM J2 connector remain disconnected.

  1. Remove the jumper wire that was installed in the last test step.

  1. At the machine harness connector J2 for the ECM, use a 151-6320 Removal Tool to remove the solenoid energize wire A861-BR and socket at contact J2-3 from the harness connector.

  1. Reconnect the machine harness J2 connector to the ECM.

  1. Turn the disconnect switch switch and the key start to the ON position.

  1. Use a 7X-1710 Multimeter Probe that is not connected to a multimeter or a similar device to make contact with the ECM pin at J2-3 through the empty space in the J2 connector.

  1. While observing the status of the active CID 2553 FMI 05 diagnostic code, ground the other end of the 7X-1710 Multimeter Probe to frame ground.

Expected Result:

The CID 2553 FMI 05 diagnostic code is no longer active. A CID 2553 FMI 06 diagnostic code becomes active when the ECM pin at J2-3 is grounded.

Results:

  • YES - The CID 2553 FMI 05 diagnostic code is no longer active. A CID 2553 FMI 06 diagnostic code has been activated after the ECM pin is grounded. The ECM has responded correctly to the grounded circuit condition in the solenoid circuit. The ECM is most likely not causing the problem.

    Reinstall the disconnected solenoid energize wire back into the correct spot in the ECM connector before proceeding to the next Test Step.

    Proceed to Test Step 4.

  • NO - The CID 2553 FMI 05 diagnostic code remains active. The status of the active diagnostic code does not change when the ECM pin for the solenoid is grounded.

    Repair: The ECM has not responded correctly to the grounded condition in the solenoid circuit. The operation of the ECM is not correct.Prior to replacing an ECM, always contact your dealership's Technical Communicator for possible consultation with Caterpillar. This consultation may greatly reduce repair time. If the ECM must be replaced, refer to Testing and Adjusting, "Electronic Control Module (ECM) - Replace".

    STOP

Test Step 4. CHECK THE STATUS OF THE DIAGNOSTIC CODE

  1. Inspect the harness connectors and clean the contacts of the harness connectors and check the wires for damage to the insulation that is caused by excessive heat, corrosion, or chafing.

  1. Perform a 45 N (10 lb) pull test on each of the wires that are associated with the sensor circuit.

  1. Reconnect all harness connectors. Make sure that the connectors are fully seated and the clips for each connector are completely fastened.

  1. Turn the disconnect switch and the key start switch to the ON position.

  1. Operate the machine.

  1. Check the status of the CID 2553 FMI 05 diagnostic code.

Expected Result:

The CID 2553 FMI 05 diagnostic code is active.

Results:

  • YES - The CID 2553 FMI 05 diagnostic code is active. The diagnostic code has not been corrected.

    Repair: Check the circuit again. Use the Caterpillar Electronic Technician (ET) service tool, if available, in order to perform a "Wiggle Test" on the machine wiring harness. The wiggle test can detect momentary or intermittent shorts or opens in the machine wiring harness.If the cause of the problem is not found in the machine harness, the ECM may have failed. This is unlikely as the ECM responded correctly to the grounded condition in the previous test step.Verify that all possible causes of the diagnostic code have been investigated. Exit this procedure and perform this procedure again.Prior to replacing an ECM, always contact your dealership's Technical Communicator for possible consultation with Caterpillar. This consultation may greatly reduce repair time. If the cause of the active diagnostic code is not found and the ECM must be replaced, refer to Testing and Adjusting, "Electronic Control Module (ECM) - Replace".

    STOP

  • NO - The CID 2553 FMI 05 diagnostic code is not active. The diagnostic code does not exist at this time.

    Repair: The initial diagnostic code was probably caused by a poor electrical connection at one of the harness connectors that was disconnected and reconnected. Resume normal machine operation.

    STOP

Caterpillar Information System:

AP655D Asphalt Paver Machine Systems Gear Motor (Ventilation System) - Install
AP655D Asphalt Paver Machine Systems Gear Motor (Ventilation System) - Remove
D6K Track-Type Tractor Power Train Final Drive and Sprocket - Disassemble
AP600D, AP655D, BG600D and BG655D Asphalt Pavers MID 157 - CID 2553 - FMI 03
AP600D, AP655D, BG600D and BG655D Asphalt Pavers MID 157 - CID 2550 - FMI 06
AP600D, AP655D, BG600D and BG655D Asphalt Pavers MID 157 - CID 2550 - FMI 05
AP600D, AP655D, BG600D and BG655D Asphalt Pavers MID 157 - CID 2550 - FMI 03
AP600D, AP655D, BG600D and BG655D Asphalt Pavers MID 157 - CID 2549 - FMI 06
C9.3 Engines for Caterpillar Built Machines Cylinder Head - Install
AP600D, AP655D, BG600D and BG655D Asphalt Pavers MID 157 - CID 2549 - FMI 05
AP600D, AP655D, BG600D and BG655D Asphalt Pavers MID 157 - CID 2549 - FMI 03
AP655D Asphalt Paver Machine Systems Transverse Beam - Remove and Install
AP655D and BG655D Asphalt Pavers Propel System Parking Brake
AS3251C Asphalt Screed Plate Locations and Film Locations
AP600D, AP655D, BG600D and BG655D Asphalt Pavers MID 157 - CID 2553 - FMI 06
AP655D and BG655D Asphalt Pavers Propel System Location of Electrical Components (Propel System)
CB22, CB24, CB32 and CC24 Utility Compactors Engine Water Pump - Inspect
AS3251C Asphalt Screed Vibratory Control
AP655D and BG655D Asphalt Pavers Machine Systems Washdown Group - Ecological
AP655D and BG655D Asphalt Pavers Machine Systems Washdown Group - Diesel
C4.4 (Mech) Industrial Engine Engine Oil and Filter - Change
2007/03/26 Direct Shipping Process and New Packaging for Replacement Glass {7301, 7308, 7310, 7325}
938H Wheel Loader and IT38H Integrated Toolcarrier Machine Systems Radiator Cap
AP655D Asphalt Paver Machine Systems Pump Drive - Remove
Back to top
The names Caterpillar, John Deere, JD, JCB, Hyundai or any other original equipment manufacturers are registered trademarks of the respective original equipment manufacturers. All names, descriptions, numbers and symbols are used for reference purposes only.
CH-Part.com is in no way associated with any of the manufacturers we have listed. All manufacturer's names and descriptions are for reference only.