SR4 and SR4B Electric Power Generation Rewind Data Caterpillar


Winding Data for 141-5534 Generator through 142-9900 Generator

Usage:

SR4B 1BN

141-5534 Generator

Table 1
MAIN STATOR AND ROTOR WINDING DATA    
ITEM     STATOR     ROTOR    
Stack Height    
254.0 mm (10.0 inch)    

254.0 mm (10.0 inch)    
Slots     48     -    
Coil Throw     1 - 10     -    
Turns/Coil     3.5 (3-4-3-4)     -    
Turns/Pole     -     130    
No. & Wire Size     8 - #13     #8 SQ    
Mean Length Turn    
1165.9 mm (45.9 inch)    
-    
Copper Weight    
36.1 kg (79.5 lb)    

43.5 kg (95.8 lb)    
Inside Connection (1)     2 Parallel Star     4 in Series    
Line Leads (No. & Size)     24 - #4     -    
Terminal bolt size     3/8 inch     -    
Low Voltage connected line resistance at 25 ° C (77 ° F)     0.00827 ohms     -    
Field lead resistance at 25 ° C (77 ° F)     -     0.909 ohms    
EXCITER WINDING DATA    
Exciter Frequency (Hz)     90 Hz     Permanent Magnet Frequency     - Hz    
Exciter Poles     6    
ITEM     STATOR (FIELD)     ROTOR (ARMATURE)     Permanent Magnet Stator    
Stack Length    
88.9 mm (3.5 inch)    

88.9 mm (3.5 inch)    
-    
Coils/Group     6     2     -    
Slots (Coils)     6     36     -    
Turns (Coils)     150     8     -    
No. & Size Wire     1 - #16     2 - #16     -    
Coil Throw     1 - 2     1 - 6     -    
Mean Length Turn (Calc.)    
388.6 mm (15.3 inch)    

350.5 mm (13.8 inch)    
-    
Copper Weight    
4.1 kg (9.1 lb)    

2.2 kg (4.8 lb)    
-    
Insulation     Heavy Polyester Polyamide Imide    
Connection (2)     Series     2 Parallel Star     -    
Line Leads     2 - #14     3 - #10     -    
( 1 ) See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 03
( 2 ) See Specifications, "Connection Diagrams for Exciter" Connection Diagram D

141-5535 Generator

Table 2
MAIN STATOR AND ROTOR WINDING DATA    
ITEM     STATOR     ROTOR    
Stack Height    
254.0 mm (10.0 inch)    

254.0 mm (10.0 inch)    
Slots     48     -    
Coil Throw     1 - 11     -    
Turns/Coil     3     -    
Turns/Pole     -     130    
No. & Wire Size     11 - #14     #8 SQ    
Mean Length Turn    
1198.9 mm (47.2 inch)    
-    
Copper Weight    
35.8 kg (79.0 lb)    

43.5 kg (95.8 lb)    
Inside Connection (1)     4/2 Parallel Star     4 in Series    
Line Leads (No. & Size)     12 - #000     -    
Terminal bolt size     3/8 inch     -    
Low Voltage connected line resistance at 25 ° C (77 ° F)     0.00645 ohms     -    
Field lead resistance at 25 ° C (77 ° F)     -     0.909 ohms    
EXCITER WINDING DATA    
Exciter Frequency (Hz)     90 Hz     Permanent Magnet Frequency     - Hz    
Exciter Poles     6    
ITEM     STATOR (FIELD)     ROTOR (ARMATURE)     Permanent Magnet Stator    
Stack Length    
88.9 mm (3.5 inch)    

88.9 mm (3.5 inch)    
-    
Coils/Group     6     2     -    
Slots (Coils)     6     36     -    
Turns (Coils)     150     8     -    
No. & Size Wire     1 - #16     2 - #16     -    
Coil Throw     1 - 2     1 - 6     -    
Mean Length Turn (Calc.)    
388.6 mm (15.3 inch)    

350.5 mm (13.8 inch)    
-    
Copper Weight    
4.1 kg (9.1 lb)    

2.2 kg (4.8 lb)    
-    
Insulation     Heavy Polyester Polyamide Imide    
Connection (2)     Series     2 Parallel Star     -    
Line Leads     2 - #14     3 - #10     -    
( 1 ) See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 04
( 2 ) See Specifications, "Connection Diagrams for Exciter" Connection Diagram E

141-5536 Generator

Table 3
MAIN STATOR AND ROTOR WINDING DATA    
ITEM     STATOR     ROTOR    
Stack Height    
276.9 mm (10.9 inch)    

276.9 mm (10.9 inch)    
Slots     48     -    
Coil Throw     1 - 10     -    
Turns/Coil     3.25 (3-3-3-4)     -    
Turns/Pole     -     130    
No. & Wire Size     9 - #14     #8 SQ    
Mean Length Turn    
1231.9 mm (48.5 inch)    
-    
Copper Weight    
31.4 kg (69.3 lb)    

45.6 kg (100.6 lb)    
Inside Connection (1)     2 Parallel Star     4 in Series    
Line Leads (No. & Size)     24 - #4     -    
Terminal bolt size     3/8 inch     -    
Low Voltage connected line resistance at 25 ° C (77 ° F)     0.00895 ohms     -    
Field lead resistance at 25 ° C (77 ° F)     -     0.961 ohms    
EXCITER WINDING DATA    
Exciter Frequency (Hz)     90 Hz     Permanent Magnet Frequency     - Hz    
Exciter Poles     6    
ITEM     STATOR (FIELD)     ROTOR (ARMATURE)     Permanent Magnet Stator    
Stack Length    
88.9 mm (3.5 inch)    

88.9 mm (3.5 inch)    
-    
Coils/Group     6     2     -    
Slots (Coils)     6     36     -    
Turns (Coils)     150     8     -    
No. & Size Wire     1 - #16     2 - #16     -    
Coil Throw     1 - 2     1 - 6     -    
Mean Length Turn (Calc.)    
388.6 mm (15.3 inch)    

350.5 mm (13.8 inch)    
-    
Copper Weight    
4.1 kg (9.1 lb)    

2.2 kg (4.8 lb)    
-    
Insulation     Heavy Polyester Polyamide Imide    
Connection (2)     Series     2 Parallel Star     -    
Line Leads     2 - #14     3 - #10     -    
( 1 ) See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 03
( 2 ) See Specifications, "Connection Diagrams for Exciter" Connection Diagram D

141-5537 Generator

Table 4
MAIN STATOR AND ROTOR WINDING DATA    
ITEM     STATOR     ROTOR    
Stack Height    
276.9 mm (10.9 inch)    

276.9 mm (10.9 inch)    
Slots     48     -    
Coil Throw     1 - 11     -    
Turns/Coil     2.75 (2-3-3-3)     -    
Turns/Pole     -     130    
No. & Wire Size     12 - #14     #8 SQ    
Mean Length Turn    
1244.6 mm (49.0 inch)    
-    
Copper Weight    
37.2 kg (82.0 lb)    

45.6 kg (100.6 lb)    
Inside Connection (1)     4/2 Parallel Star     4 in Series    
Line Leads (No. & Size)     12 - #0000     -    
Terminal bolt size     3/8 inch     -    
Low Voltage connected line resistance at 25 ° C (77 ° F)     0.00493 ohms     -    
Field lead resistance at 25 ° C (77 ° F)     -     0.961 ohms    
EXCITER WINDING DATA    
Exciter Frequency (Hz)     90 Hz     Permanent Magnet Frequency     - Hz    
Exciter Poles     6    
ITEM     STATOR (FIELD)     ROTOR (ARMATURE)     Permanent Magnet Stator    
Stack Length    
88.9 mm (3.5 inch)    

88.9 mm (3.5 inch)    
-    
Coils/Group     6     2     -    
Slots (Coils)     6     36     -    
Turns (Coils)     150     8     -    
No. & Size Wire     1 - #16     2 - #16     -    
Coil Throw     1 - 2     1 - 6     -    
Mean Length Turn (Calc.)    
388.6 mm (15.3 inch)    

350.5 mm (13.8 inch)    
-    
Copper Weight    
4.1 kg (9.1 lb)    

2.2 kg (4.8 lb)    
-    
Insulation     Heavy Polyester Polyamide Imide    
Connection (2)     Series     2 Parallel Star     -    
Line Leads     2 - #14     3 - #10     -    
( 1 ) See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 04
( 2 ) See Specifications, "Connection Diagrams for Exciter" Connection Diagram E

141-5538 Generator

Table 5
MAIN STATOR AND ROTOR WINDING DATA    
ITEM     STATOR     ROTOR    
Stack Height    
304.8 mm (12.0 inch)    

304.8 mm (12.0 inch)    
Slots     48     -    
Coil Throw     1 - 10     -    
Turns/Coil     3     -    
Turns/Pole     -     130    
No. & Wire Size     10 - #14     #8 SQ    
Mean Length Turn    
1242.1 mm (48.9 inch)    
-    
Copper Weight    
33.7 kg (74.4 lb)    

48.3 kg (106.5 lb)    
Inside Connection (1)     4/2 Parallel Star     4 in Series    
Line Leads (No. & Size)     12 - #000     -    
Terminal bolt size     3/8 inch     -    
Low Voltage connected line resistance at 25 ° C (77 ° F)     0.00712 ohms     -    
Field lead resistance at 25 ° C (77 ° F)     -     1.015 ohms    
EXCITER WINDING DATA    
Exciter Frequency (Hz)     90 Hz     Permanent Magnet Frequency     - Hz    
Exciter Poles     6    
ITEM     STATOR (FIELD)     ROTOR (ARMATURE)     Permanent Magnet Stator    
Stack Length    
88.9 mm (3.5 inch)    

88.9 mm (3.5 inch)    
-    
Coils/Group     6     2     -    
Slots (Coils)     6     36     -    
Turns (Coils)     150     8     -    
No. & Size Wire     1 - #16     2 - #16     -    
Coil Throw     1 - 2     1 - 6     -    
Mean Length Turn (Calc.)    
388.6 mm (15.3 inch)    

350.5 mm (13.8 inch)    
-    
Copper Weight    
4.1 kg (9.1 lb)    

2.2 kg (4.8 lb)    
-    
Insulation     Heavy Polyester Polyamide Imide    
Connection (2)     Series     2 Parallel Star     -    
Line Leads     2 - #14     3 - #10     -    
( 1 ) See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 04
( 2 ) See Specifications, "Connection Diagrams for Exciter" Connection Diagram E

141-5539 Generator

Table 6
MAIN STATOR AND ROTOR WINDING DATA    
ITEM     STATOR     ROTOR    
Stack Height    
304.8 mm (12.0 inch)    

304.8 mm (12.0 inch)    
Slots     48     -    
Coil Throw     1 - 10     -    
Turns/Coil     2.5 (2-3-2-3)     -    
Turns/Pole     -     130    
No. & Wire Size     12 - #14     #8 SQ    
Mean Length Turn    
1244.6 mm (49.0 inch)    
-    
Copper Weight    
33.6 kg (74.0 lb)    

48.3 kg (106.5 lb)    
Inside Connection (1)     4/2 Parallel Star     4 in Series    
Line Leads (No. & Size)     12 - #0000     -    
Terminal bolt size     3/8 inch     -    
Low Voltage connected line resistance at 25 ° C (77 ° F)     0.00448 ohms     -    
Field lead resistance at 25 ° C (77 ° F)     -     1.015 ohms    
EXCITER WINDING DATA    
Exciter Frequency (Hz)     90 Hz     Permanent Magnet Frequency     - Hz    
Exciter Poles     6    
ITEM     STATOR (FIELD)     ROTOR (ARMATURE)     Permanent Magnet Stator    
Stack Length    
88.9 mm (3.5 inch)    

88.9 mm (3.5 inch)    
-    
Coils/Group     6     2     -    
Slots (Coils)     6     36     -    
Turns (Coils)     150     8     -    
No. & Size Wire     1 - #16     2 - #16     -    
Coil Throw     1 - 2     1 - 6     -    
Mean Length Turn (Calc.)    
388.6 mm (15.3 inch)    

350.5 mm (13.8 inch)    
-    
Copper Weight    
4.1 kg (9.1 lb)    

2.2 kg (4.8 lb)    
-    
Insulation     Heavy Polyester Polyamide Imide    
Connection (2)     Series     2 Parallel Star     -    
Line Leads     2 - #14     3 - #10     -    
( 1 ) See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 04
( 2 ) See Specifications, "Connection Diagrams for Exciter" Connection Diagram E

141-5540 Generator

Table 7
MAIN STATOR AND ROTOR WINDING DATA    
ITEM     STATOR     ROTOR    
Stack Height    
360.7 mm (14.2 inch)    

360.7 mm (14.2 inch)    
Slots     48     -    
Coil Throw     1 - 10     -    
Turns/Coil     2.5 (2-3-2-3)     -    
Turns/Pole     -     130    
No. & Wire Size     12 - #14     #8 SQ    
Mean Length Turn    
1353.8 mm (53.3 inch)    
-    
Copper Weight    
40.1 kg (88.5 lb)    

53.6 kg (118.2 lb)    
Inside Connection (1)     4/2 Parallel Star     4 in Series    
Line Leads (No. & Size)     12 - #000     -    
Terminal bolt size     3/8 inch     -    
Low Voltage connected line resistance at 25 ° C (77 ° F)     0.00574 ohms     -    
Field lead resistance at 25 ° C (77 ° F)     -     1.115 ohms    
EXCITER WINDING DATA    
Exciter Frequency (Hz)     90 Hz     Permanent Magnet Frequency     - Hz    
Exciter Poles     6    
ITEM     STATOR (FIELD)     ROTOR (ARMATURE)     Permanent Magnet Stator    
Stack Length    
88.9 mm (3.5 inch)    

88.9 mm (3.5 inch)    
-    
Coils/Group     6     2     -    
Slots (Coils)     6     36     -    
Turns (Coils)     150     8     -    
No. & Size Wire     1 - #16     2 - #16     -    
Coil Throw     1 - 2     1 - 6     -    
Mean Length Turn (Calc.)    
388.6 mm (15.3 inch)    

350.5 mm (13.8 inch)    
-    
Copper Weight    
4.1 kg (9.1 lb)    

2.2 kg (4.8 lb)    
-    
Insulation     Heavy Polyester Polyamide Imide    
Connection (2)     Series     2 Parallel Star     -    
Line Leads     2 - #14     3 - #10     -    
( 1 ) See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 04
( 2 ) See Specifications, "Connection Diagrams for Exciter" Connection Diagram E

141-5541 Generator

Table 8
MAIN STATOR AND ROTOR WINDING DATA    
ITEM     STATOR     ROTOR    
Stack Height    
360.7 mm (14.2 inch)    

360.7 mm (14.2 inch)    
Slots     48     -    
Coil Throw     1 - 11     -    
Turns/Coil     2     -    
Turns/Pole     -     130    
No. & Wire Size     16 - #14     #8 SQ    
Mean Length Turn    
1422.4 mm (56.0 inch)    
-    
Copper Weight    
40.8 kg (90.0 lb)    

53.6 kg (118.2 lb)    
Inside Connection (1)     4/2 Parallel Star     4 in Series    
Line Leads (No. & Size)     24 - #1     -    
Terminal bolt size     3/8 inch     -    
Low Voltage connected line resistance at 25 ° C (77 ° F)     0.00305 ohms     -    
Field lead resistance at 25 ° C (77 ° F)     -     1.115 ohms    
EXCITER WINDING DATA    
Exciter Frequency (Hz)     90 Hz     Permanent Magnet Frequency     - Hz    
Exciter Poles     6    
ITEM     STATOR (FIELD)     ROTOR (ARMATURE)     Permanent Magnet Stator    
Stack Length    
88.9 mm (3.5 inch)    

88.9 mm (3.5 inch)    
-    
Coils/Group     6     2     -    
Slots (Coils)     6     36     -    
Turns (Coils)     150     8     -    
No. & Size Wire     1 - #16     2 - #16     -    
Coil Throw     1 - 2     1 - 6     -    
Mean Length Turn (Calc.)    
388.6 mm (15.3 inch)    

350.5 mm (13.8 inch)    
-    
Copper Weight    
4.1 kg (9.1 lb)    

2.2 kg (4.8 lb)    
-    
Insulation     Heavy Polyester Polyamide Imide    
Connection (2)     Series     2 Parallel Star     -    
Line Leads     2 - #14     3 - #10     -    
( 1 ) See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 47
( 2 ) See Specifications, "Connection Diagrams for Exciter" Connection Diagram D

141-5542 Generator

Table 9
MAIN STATOR AND ROTOR WINDING DATA    
ITEM     STATOR     ROTOR    
Stack Height    
419.1 mm (16.5 inch)    

419.1 mm (16.5 inch)    
Slots     48     -    
Coil Throw     1 - 10     -    
Turns/Coil     2.25 (2-2-2-3)     -    
Turns/Pole     -     130    
No. & Wire Size     7 - #14 and 7 - #13.5     #8 SQ    
Mean Length Turn    
1473.2 mm (58.0 inch)    
-    
Copper Weight    
44.5 kg (98.0 lb)    

59.1 kg (130.4 lb)    
Inside Connection (1)     4/2 Parallel Star     4 in Series    
Line Leads (No. & Size)     24 - #1     -    
Terminal bolt size     3/8 inch     -    
Low Voltage connected line resistance at 25 ° C (77 ° F)     0.00386 ohms     -    
Field lead resistance at 25 ° C (77 ° F)     -     1.225 ohms    
EXCITER WINDING DATA    
Exciter Frequency (Hz)     90 Hz     Permanent Magnet Frequency     - Hz    
Exciter Poles     6    
ITEM     STATOR (FIELD)     ROTOR (ARMATURE)     Permanent Magnet Stator    
Stack Length    
88.9 mm (3.5 inch)    

88.9 mm (3.5 inch)    
-    
Coils/Group     6     2     -    
Slots (Coils)     6     36     -    
Turns (Coils)     150     8     -    
No. & Size Wire     1 - #16     2 - #16     -    
Coil Throw     1 - 2     1 - 6     -    
Mean Length Turn (Calc.)    
388.6 mm (15.3 inch)    

350.5 mm (13.8 inch)    
-    
Copper Weight    
4.1 kg (9.1 lb)    

2.2 kg (4.8 lb)    
-    
Insulation     Heavy Polyester Polyamide Imide    
Connection (2)     Series     2 Parallel Star     -    
Line Leads     2 - #14     3 - #10     -    
( 1 ) See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 47
( 2 ) See Specifications, "Connection Diagrams for Exciter" Connection Diagram D

141-5543 Generator

Table 10
MAIN STATOR AND ROTOR WINDING DATA    
ITEM     STATOR     ROTOR    
Stack Height    
419.1 mm (16.5 inch)    

419.1 mm (16.5 inch)    
Slots     48     -    
Coil Throw     1 - 11     -    
Turns/Coil     1.75 (1-2-2-2)     -    
Turns/Pole     -     130    
No. & Wire Size     18 - #14     #8 SQ    
Mean Length Turn    
1524.0 mm (60.0 inch)    
-    
Copper Weight    
43.5 kg (96.0 lb)    

59.1 kg (130.4 lb)    
Inside Connection (1)     4/2 Parallel Star     4 in Series    
Line Leads (No. & Size)     24 - #0     -    
Terminal bolt size     3/8 inch     -    
Low Voltage connected line resistance at 25 ° C (77 ° F)     0.00257 ohms     -    
Field lead resistance at 25 ° C (77 ° F)     -     1.225 ohms    
EXCITER WINDING DATA    
Exciter Frequency (Hz)     90 Hz     Permanent Magnet Frequency     - Hz    
Exciter Poles     6    
ITEM     STATOR (FIELD)     ROTOR (ARMATURE)     Permanent Magnet Stator    
Stack Length    
88.9 mm (3.5 inch)    

88.9 mm (3.5 inch)    
-    
Coils/Group     6     2     -    
Slots (Coils)     6     36     -    
Turns (Coils)     150     8     -    
No. & Size Wire     1 - #16     2 - #16     -    
Coil Throw     1 - 2     1 - 6     -    
Mean Length Turn (Calc.)    
388.6 mm (15.3 inch)    

350.5 mm (13.8 inch)    
-    
Copper Weight    
4.1 kg (9.1 lb)    

2.2 kg (4.8 lb)    
-    
Insulation     Heavy Polyester Polyamide Imide    
Connection (2)     Series     2 Parallel Star     -    
Line Leads     2 - #14     3 - #10     -    
( 1 ) See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 47
( 2 ) See Specifications, "Connection Diagrams for Exciter" Connection Diagram D

141-5544 Generator

Table 11
MAIN STATOR AND ROTOR WINDING DATA    
ITEM     STATOR     ROTOR    
Stack Height    
495.3 mm (19.5 inch)    

495.3 mm (19.5 inch)    
Slots     48     -    
Coil Throw     1 - 10     -    
Turns/Coil     2     -    
Turns/Pole     -     130    
No. & Wire Size     14 - #14 and 4 - #13.5     #8 SQ    
Mean Length Turn    
1783.1 mm (70.2 inch)    
-    
Copper Weight    
54.4 kg (120.0 lb)    

66.4 kg (146.4 lb)    
Inside Connection (1)     4/2 Parallel Star     4 in Series    
Line Leads (No. & Size)     24 - #0     -    
Terminal bolt size     3/8 inch     -    
Low Voltage connected line resistance at 25 ° C (77 ° F)     0.00304 ohms     -    
Field lead resistance at 25 ° C (77 ° F)     -     1.40 ohms    
EXCITER WINDING DATA    
Exciter Frequency (Hz)     90 Hz     Permanent Magnet Frequency     - Hz    
Exciter Poles     6    
ITEM     STATOR (FIELD)     ROTOR (ARMATURE)     Permanent Magnet Stator    
Stack Length    
88.9 mm (3.5 inch)    

88.9 mm (3.5 inch)    
-    
Coils/Group     6     2     -    
Slots (Coils)     6     36     -    
Turns (Coils)     150     8     -    
No. & Size Wire     1 - #16     2 - #16     -    
Coil Throw     1 - 2     1 - 6     -    
Mean Length Turn (Calc.)    
388.6 mm (15.3 inch)    

350.5 mm (13.8 inch)    
-    
Copper Weight    
4.1 kg (9.1 lb)    

2.2 kg (4.8 lb)    
-    
Insulation     Heavy Polyester Polyamide Imide    
Connection (2)     Series     2 Parallel Star     -    
Line Leads     2 - #14     3 - #10     -    
( 1 ) See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 47
( 2 ) See Specifications, "Connection Diagrams for Exciter" Connection Diagram D

141-5545 Generator

Table 12
MAIN STATOR AND ROTOR WINDING DATA    
ITEM     STATOR     ROTOR    
Stack Height    
495.3 mm (19.5 inch)    

495.3 mm (19.5 inch)    
Slots     48     -    
Coil Throw     1 - 10     -    
Turns/Coil     1.75 (1-2-2-2)     -    
Turns/Pole     -     130    
No. & Wire Size     14 - #14 and 4 - #13.5     #8 SQ    
Mean Length Turn    
1625.6 mm (64.0 inch)    
-    
Copper Weight    
47.2 kg (104.0 lb)    

66.4 kg (146.4 lb)    
Inside Connection (1)     2 Parallel Star     4 in Series    
Line Leads (No. & Size)     24 - #00     -    
Terminal bolt size     3/8 inch     -    
Low Voltage connected line resistance at 25 ° C (77 ° F)     0.00265 ohms     -    
Field lead resistance at 25 ° C (77 ° F)     -     1.40 ohms    
EXCITER WINDING DATA    
Exciter Frequency (Hz)     90 Hz     Permanent Magnet Frequency     - Hz    
Exciter Poles     6    
ITEM     STATOR (FIELD)     ROTOR (ARMATURE)     Permanent Magnet Stator    
Stack Length    
88.9 mm (3.5 inch)    

88.9 mm (3.5 inch)    
-    
Coils/Group     6     2     -    
Slots (Coils)     6     36     -    
Turns (Coils)     150     8     -    
No. & Size Wire     1 - #16     2 - #16     -    
Coil Throw     1 - 2     1 - 6     -    
Mean Length Turn (Calc.)    
388.6 mm (15.3 inch)    

350.5 mm (13.8 inch)    
-    
Copper Weight    
4.1 kg (9.1 lb)    

2.2 kg (4.8 lb)    
-    
Insulation     Heavy Polyester Polyamide Imide    
Connection (2)     Series     2 Parallel Star     -    
Line Leads     2 - #14     3 - #10     -    
( 1 ) See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 50
( 2 ) See Specifications, "Connection Diagrams for Exciter" Connection Diagram D

141-5546 Generator

Table 13
MAIN STATOR AND ROTOR WINDING DATA    
ITEM     STATOR     ROTOR    
Stack Height    
360.7 mm (14.2 inch)    

360.7 mm (14.2 inch)    
Slots     48     -    
Coil Throw     1 - 10     -    
Turns/Coil     2.5 (2-3-2-3)     -    
Turns/Pole     -     130    
No. & Wire Size     12 - #14     #8 SQ    
Mean Length Turn    
1353.8 mm (53.3 inch)    
-    
Copper Weight    
40.1 kg (88.5 lb)    

53.6 kg (118.2 lb)    
Inside Connection (1)     4/2 Parallel Star     4 in Series    
Line Leads (No. & Size)     12 - #000     -    
Terminal bolt size     3/8 inch     -    
Low Voltage connected line resistance at 25 ° C (77 ° F)     0.00574 ohms     -    
Field lead resistance at 25 ° C (77 ° F)     -     1.115 ohms    
EXCITER WINDING DATA    
Exciter Frequency (Hz)     90 Hz     Permanent Magnet Frequency     - Hz    
Exciter Poles     6    
ITEM     STATOR (FIELD)     ROTOR (ARMATURE)     Permanent Magnet Stator    
Stack Length    
88.9 mm (3.5 inch)    

88.9 mm (3.5 inch)    
-    
Coils/Group     6     2     -    
Slots (Coils)     6     36     -    
Turns (Coils)     150     8     -    
No. & Size Wire     1 - #16     2 - #16     -    
Coil Throw     1 - 2     1 - 6     -    
Mean Length Turn (Calc.)    
388.6 mm (15.3 inch)    

350.5 mm (13.8 inch)    
-    
Copper Weight    
4.1 kg (9.1 lb)    

2.2 kg (4.8 lb)    
-    
Insulation     Heavy Polyester Polyamide Imide    
Connection (2)     Series     2 Parallel Star     -    
Line Leads     2 - #14     3 - #10     -    
( 1 ) See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 04
( 2 ) See Specifications, "Connection Diagrams for Exciter" Connection Diagram E

141-5547 Generator

Table 14
MAIN STATOR AND ROTOR WINDING DATA    
ITEM     STATOR     ROTOR    
Stack Height    
360.7 mm (14.2 inch)    

360.7 mm (14.2 inch)    
Slots     48     -    
Coil Throw     1 - 11     -    
Turns/Coil     2     -    
Turns/Pole     -     130    
No. & Wire Size     16 - #14     #8 SQ    
Mean Length Turn    
1422.4 mm (56.0 inch)    
-    
Copper Weight    
40.8 kg (90.0 lb)    

53.6 kg (118.2 lb)    
Inside Connection (1)     4/2 Parallel Star     4 in Series    
Line Leads (No. & Size)     24 - #1     -    
Terminal bolt size     3/8 inch     -    
Low Voltage connected line resistance at 25 ° C (77 ° F)     0.00305 ohms     -    
Field lead resistance at 25 ° C (77 ° F)     -     1.115 ohms    
EXCITER WINDING DATA    
Exciter Frequency (Hz)     90 Hz     Permanent Magnet Frequency     - Hz    
Exciter Poles     6    
ITEM     STATOR (FIELD)     ROTOR (ARMATURE)     Permanent Magnet Stator    
Stack Length    
88.9 mm (3.5 inch)    

88.9 mm (3.5 inch)    
-    
Coils/Group     6     2     -    
Slots (Coils)     6     36     -    
Turns (Coils)     150     8     -    
No. & Size Wire     1 - #16     2 - #16     -    
Coil Throw     1 - 2     1 - 6     -    
Mean Length Turn (Calc.)    
388.6 mm (15.3 inch)    

350.5 mm (13.8 inch)    
-    
Copper Weight    
4.1 kg (9.1 lb)    

2.2 kg (4.8 lb)    
-    
Insulation     Heavy Polyester Polyamide Imide    
Connection (2)     Series     2 Parallel Star     -    
Line Leads     2 - #14     3 - #10     -    
( 1 ) See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 47
( 2 ) See Specifications, "Connection Diagrams for Exciter" Connection Diagram D

142-4935 Generator

Table 15
MAIN STATOR AND ROTOR WINDING DATA    
ITEM     STATOR     ROTOR    
Stack Height    
495.3 mm (19.5 inch)    

495.3 mm (19.5 inch)    
Slots     48     -    
Coil Throw     1 - 10     -    
Turns/Coil     2     -    
Turns/Pole     -     130    
No. & Wire Size     18 - #14     #8 SQ    
Mean Length Turn    
1623.1 mm (63.9 inch)    
-    
Copper Weight    
52.9 kg (116.7 lb)    

66.4 kg (146.4 lb)    
Inside Connection (1)     4/2 Parallel Star     4 in Series    
Line Leads (No. & Size)     24 - #0     -    
Terminal bolt size     3/8 inch     -    
Low Voltage connected line resistance at 25 ° C (77 ° F)     0.00377 ohms     -    
Field lead resistance at 25 ° C (77 ° F)     -     1.40 ohms    
EXCITER WINDING DATA    
Exciter Frequency (Hz)     90 Hz     Permanent Magnet Frequency     120 Hz    
Exciter Poles     6     8    
ITEM     STATOR (FIELD)     ROTOR (ARMATURE)     Permanent Magnet Stator    
Stack Length    
88.9 mm (3.5 inch)    

88.9 mm (3.5 inch)    

31.8 mm (1.25 inch)    
Coils/Group     6     2     1    
Slots (Coils)     6     36     24    
Turns (Coils)     150     8     12    
No. & Size Wire     1 - #16     2 - #16     2 - #18    
Coil Throw     1 - 2     1 - 6     1 - 4    
Mean Length Turn (Calc.)    
388.6 mm (15.3 inch)    

350.5 mm (13.8 inch)    

330.2 mm (13.0 inch)    
Copper Weight    
4.1 kg (9.1 lb)    

2.2 kg (4.8 lb)    

0.5 kg (1.0 lb)    
Insulation     Heavy Polyester Polyamide Imide    
Connection (2)     Series     2 Parallel Star     Star    
Line Leads     2 - #14     3 - #10     3 - #14    
( 1 ) See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 47
( 2 ) See Specifications, "Connection Diagrams for Exciter" Connection Diagram D

142-9900 Generator Ar

Table 16
MAIN STATOR AND ROTOR WINDING DATA    
ITEM     STATOR     ROTOR    
Stack Height    
914.4 mm (36 inch)    

927.10 mm (36.5 inch)    
Slots     90     4    
Coil Throw     1-12     1 - 2    
Turns/Coil     1     -    
Turns/Pole     -     163.5 (3)    
No. & Wire Size     3 -
5.1816 mm (0.204 inch) x
8.2550 mm (0.325 inch) 3 High x 1 Wide    
1 of
3.6576 mm (0.144 inch) X
7.3152 mm (0.288 inch)    
Mean Length Turn    
2712.72 mm (106.8 inch)    

2311.4 mm (91 inch)    
Copper Weight    
276.6 kg (610 lb)    

549.7 kg (1212 lb)    
Inside Connection     3 Parallel Wye     Series    
Line Leads (No. & Size)     6 - 6 of # 2/0     2 of #6 Ld    
Low Voltage connected line resistance at
25° C (77.0° F)    
0.00305 ohms     -    
Field lead resistance at
25° C (77.0° F)    
-     1.522    
EXCITER WINDING DATA    
ITEM     STATOR (FIELD)     ROTOR (ARMATURE)     Permanent Magnet Stator    
Exciter Frequency (Hz)     80 Hz     80 Hz        
Exciter Poles     8     8        
Stack Length    
88.90 mm (3.5 inch)    

88.90 mm (3.5 inch)    
   
Coils/Group     1     1        
Turns (Coils)     320     16        
No. & Size Wire     2 # 18.5     3 of #16        
Coil Throw     1 - 2     1 - 6        
Mean Length Turn    
355.6 mm (14 inch)    

419.10 mm (16.5 inch)    
   
Resistance at
25° C (77.0° F)    
3.2 ohms     0.122 ohms        
Copper Weight    
14.01 kg (30.9 lb)    

6.3 kg (14 lb)    
   
Connection     2Gr Ser/Par     2 Parallel Wye        
Line Leads     #14     3 - #10        
( 3 ) Winding table: wind 4-layers of 15 turns, 2-layers of 14 turns, 1-layer of 13 turns, 1-layer of 12 turns, 1-layer of 11turns, 1-layer of 10 turns, 1-layer of 9 turns, 1-layer of 8-turns, 1-layer of 6.5 turns, 1-layer of 6 turns = 163.5 turns.

Caterpillar Information System:

SR4 and SR4B Electric Power Generation Rewind Data Winding Data for 136-6580 Generator through 136-6609 Generator
SR4 and SR4B Electric Power Generation Rewind Data Winding Data for 126-8022 Generator through 128-7424 Generator
C1.7, C1.8 and C2.4 Tier 4 Interim and EU Stage 3A Engines for Caterpillar Built Machines Engine Oil Pressure Switch
CX31 and CX31 HT On-Highway Transmissions (Cat Truck) Transmission Hydraulic Control
2013/09/20 A Rework Procedure for the Power Access Stairway (PAS) On Certain Off-Highway Trucks is Now Available {7253}
2013/09/27 New Software Is Now Available for All Cat® Products With The Product Link 522 System {7606}
Rework Procedure for the PAS (Powered Access Stairway) on Certain Off-Highway Trucks{0679, 7253, 7254, 7255} Rework Procedure for the PAS (Powered Access Stairway) on Certain Off-Highway Trucks{0679, 7253, 7254, 7255}
LC5000, LC6100, and LC7000 Electric Power Generation Exciter Armature - Remove and Install
C280-16 Engine Priority Valve - Install
3512C Petroleum Engines with Dynamic Gas Blending Data Link - Test
C280-16 Engine Auxiliary Water Pump - Install
C280-16 Engine Auxiliary Water Pump - Remove
312D2 and 313D2 Excavators System Pressure Release
3512C Petroleum Engines with Dynamic Gas Blending Engine Shutdown Occurrence
SR4 and SR4B Electric Power Generation Rewind Data Winding Data for 144-1666 Generator through 144-1766 Generator
SR4 and SR4B Electric Power Generation Rewind Data Winding Data for 136-6610 Generator through 136-6641 Generator
SR4 and SR4B Electric Power Generation Rewind Data Winding Data for 144-1964 Generator through 144-2088 Generator
SR4 and SR4B Electric Power Generation Rewind Data Winding Data for 149-2447 Generator through 150-9152 Generator
SR4 and SR4B Electric Power Generation Rewind Data Winding Data for 158-6410 Generator through 163-8546 Generator
SR4 and SR4B Electric Power Generation Rewind Data Winding Data for 164-0975 Generator through 164-4946 Generator
SR4 and SR4B Electric Power Generation Rewind Data Winding Data for 173-7078 Generator through 194-6563 Generator
SR4 and SR4B Electric Power Generation Rewind Data Winding Data for 203-5749 Generator through 324-5120 Generator
SR4 and SR4B Electric Power Generation Rewind Data Winding Data for 6I-0053 Generator through 6I-4860 Generator
2013/11/11 An Improved ARD Combustion Head is Now Used on the Tier 4 Engines of Certain Machines {108B, 108E, 108M}
Back to top
The names Caterpillar, John Deere, JD, JCB, Hyundai or any other original equipment manufacturers are registered trademarks of the respective original equipment manufacturers. All names, descriptions, numbers and symbols are used for reference purposes only.
CH-Part.com is in no way associated with any of the manufacturers we have listed. All manufacturer's names and descriptions are for reference only.