Winding Data for 141-5534 Generator through 142-9900 Generator
141-5534 Generator
Show/hide table
MAIN STATOR AND ROTOR WINDING DATA     | |||||||
---|---|---|---|---|---|---|---|
ITEM     | STATOR     | ROTOR     | |||||
Stack Height     | 254.0 mm (10.0 inch)     |
254.0 mm (10.0 inch)     |
|||||
Slots     | 48     | -     | |||||
Coil Throw     | 1 - 10     | -     | |||||
Turns/Coil     | 3.5 (3-4-3-4)     | -     | |||||
Turns/Pole     | -     | 130     | |||||
No. & Wire Size     | 8 - #13     | #8 SQ     | |||||
Mean Length Turn     | 1165.9 mm (45.9 inch)     |
-     | |||||
Copper Weight     | 36.1 kg (79.5 lb)     |
43.5 kg (95.8 lb)     |
|||||
Inside Connection (1)     | 2 Parallel Star     | 4 in Series     | |||||
Line Leads (No. & Size)     | 24 - #4     | -     | |||||
Terminal bolt size     | 3/8 inch     | -     | |||||
Low Voltage connected line resistance at 25 ° C (77 ° F)     | 0.00827 ohms     | -     | |||||
Field lead resistance at 25 ° C (77 ° F)     | -     | 0.909 ohms     | |||||
EXCITER WINDING DATA     | |||||||
Exciter Frequency (Hz)     | 90 Hz     | Permanent Magnet Frequency     | - Hz     | ||||
Exciter Poles     | 6     | ||||||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | Permanent Magnet Stator     | ||||
Stack Length     | 88.9 mm (3.5 inch)     |
88.9 mm (3.5 inch)     |
-     | ||||
Coils/Group     | 6     | 2     | -     | ||||
Slots (Coils)     | 6     | 36     | -     | ||||
Turns (Coils)     | 150     | 8     | -     | ||||
No. & Size Wire     | 1 - #16     | 2 - #16     | -     | ||||
Coil Throw     | 1 - 2     | 1 - 6     | -     | ||||
Mean Length Turn (Calc.)     | 388.6 mm (15.3 inch)     |
350.5 mm (13.8 inch)     |
-     | ||||
Copper Weight     | 4.1 kg (9.1 lb)     |
2.2 kg (4.8 lb)     |
-     | ||||
Insulation     | Heavy Polyester Polyamide Imide     | ||||||
Connection (2)     | Series     | 2 Parallel Star     | -     | ||||
Line Leads     | 2 - #14     | 3 - #10     | -     |
Show/hide table
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 03 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram D |
141-5535 Generator
Show/hide table
MAIN STATOR AND ROTOR WINDING DATA     | |||||||
---|---|---|---|---|---|---|---|
ITEM     | STATOR     | ROTOR     | |||||
Stack Height     | 254.0 mm (10.0 inch)     |
254.0 mm (10.0 inch)     |
|||||
Slots     | 48     | -     | |||||
Coil Throw     | 1 - 11     | -     | |||||
Turns/Coil     | 3     | -     | |||||
Turns/Pole     | -     | 130     | |||||
No. & Wire Size     | 11 - #14     | #8 SQ     | |||||
Mean Length Turn     | 1198.9 mm (47.2 inch)     |
-     | |||||
Copper Weight     | 35.8 kg (79.0 lb)     |
43.5 kg (95.8 lb)     |
|||||
Inside Connection (1)     | 4/2 Parallel Star     | 4 in Series     | |||||
Line Leads (No. & Size)     | 12 - #000     | -     | |||||
Terminal bolt size     | 3/8 inch     | -     | |||||
Low Voltage connected line resistance at 25 ° C (77 ° F)     | 0.00645 ohms     | -     | |||||
Field lead resistance at 25 ° C (77 ° F)     | -     | 0.909 ohms     | |||||
EXCITER WINDING DATA     | |||||||
Exciter Frequency (Hz)     | 90 Hz     | Permanent Magnet Frequency     | - Hz     | ||||
Exciter Poles     | 6     | ||||||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | Permanent Magnet Stator     | ||||
Stack Length     | 88.9 mm (3.5 inch)     |
88.9 mm (3.5 inch)     |
-     | ||||
Coils/Group     | 6     | 2     | -     | ||||
Slots (Coils)     | 6     | 36     | -     | ||||
Turns (Coils)     | 150     | 8     | -     | ||||
No. & Size Wire     | 1 - #16     | 2 - #16     | -     | ||||
Coil Throw     | 1 - 2     | 1 - 6     | -     | ||||
Mean Length Turn (Calc.)     | 388.6 mm (15.3 inch)     |
350.5 mm (13.8 inch)     |
-     | ||||
Copper Weight     | 4.1 kg (9.1 lb)     |
2.2 kg (4.8 lb)     |
-     | ||||
Insulation     | Heavy Polyester Polyamide Imide     | ||||||
Connection (2)     | Series     | 2 Parallel Star     | -     | ||||
Line Leads     | 2 - #14     | 3 - #10     | -     |
Show/hide table
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 04 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram E |
141-5536 Generator
Show/hide table
MAIN STATOR AND ROTOR WINDING DATA     | |||||||
---|---|---|---|---|---|---|---|
ITEM     | STATOR     | ROTOR     | |||||
Stack Height     | 276.9 mm (10.9 inch)     |
276.9 mm (10.9 inch)     |
|||||
Slots     | 48     | -     | |||||
Coil Throw     | 1 - 10     | -     | |||||
Turns/Coil     | 3.25 (3-3-3-4)     | -     | |||||
Turns/Pole     | -     | 130     | |||||
No. & Wire Size     | 9 - #14     | #8 SQ     | |||||
Mean Length Turn     | 1231.9 mm (48.5 inch)     |
-     | |||||
Copper Weight     | 31.4 kg (69.3 lb)     |
45.6 kg (100.6 lb)     |
|||||
Inside Connection (1)     | 2 Parallel Star     | 4 in Series     | |||||
Line Leads (No. & Size)     | 24 - #4     | -     | |||||
Terminal bolt size     | 3/8 inch     | -     | |||||
Low Voltage connected line resistance at 25 ° C (77 ° F)     | 0.00895 ohms     | -     | |||||
Field lead resistance at 25 ° C (77 ° F)     | -     | 0.961 ohms     | |||||
EXCITER WINDING DATA     | |||||||
Exciter Frequency (Hz)     | 90 Hz     | Permanent Magnet Frequency     | - Hz     | ||||
Exciter Poles     | 6     | ||||||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | Permanent Magnet Stator     | ||||
Stack Length     | 88.9 mm (3.5 inch)     |
88.9 mm (3.5 inch)     |
-     | ||||
Coils/Group     | 6     | 2     | -     | ||||
Slots (Coils)     | 6     | 36     | -     | ||||
Turns (Coils)     | 150     | 8     | -     | ||||
No. & Size Wire     | 1 - #16     | 2 - #16     | -     | ||||
Coil Throw     | 1 - 2     | 1 - 6     | -     | ||||
Mean Length Turn (Calc.)     | 388.6 mm (15.3 inch)     |
350.5 mm (13.8 inch)     |
-     | ||||
Copper Weight     | 4.1 kg (9.1 lb)     |
2.2 kg (4.8 lb)     |
-     | ||||
Insulation     | Heavy Polyester Polyamide Imide     | ||||||
Connection (2)     | Series     | 2 Parallel Star     | -     | ||||
Line Leads     | 2 - #14     | 3 - #10     | -     |
Show/hide table
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 03 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram D |
141-5537 Generator
Show/hide table
MAIN STATOR AND ROTOR WINDING DATA     | |||||||
---|---|---|---|---|---|---|---|
ITEM     | STATOR     | ROTOR     | |||||
Stack Height     | 276.9 mm (10.9 inch)     |
276.9 mm (10.9 inch)     |
|||||
Slots     | 48     | -     | |||||
Coil Throw     | 1 - 11     | -     | |||||
Turns/Coil     | 2.75 (2-3-3-3)     | -     | |||||
Turns/Pole     | -     | 130     | |||||
No. & Wire Size     | 12 - #14     | #8 SQ     | |||||
Mean Length Turn     | 1244.6 mm (49.0 inch)     |
-     | |||||
Copper Weight     | 37.2 kg (82.0 lb)     |
45.6 kg (100.6 lb)     |
|||||
Inside Connection (1)     | 4/2 Parallel Star     | 4 in Series     | |||||
Line Leads (No. & Size)     | 12 - #0000     | -     | |||||
Terminal bolt size     | 3/8 inch     | -     | |||||
Low Voltage connected line resistance at 25 ° C (77 ° F)     | 0.00493 ohms     | -     | |||||
Field lead resistance at 25 ° C (77 ° F)     | -     | 0.961 ohms     | |||||
EXCITER WINDING DATA     | |||||||
Exciter Frequency (Hz)     | 90 Hz     | Permanent Magnet Frequency     | - Hz     | ||||
Exciter Poles     | 6     | ||||||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | Permanent Magnet Stator     | ||||
Stack Length     | 88.9 mm (3.5 inch)     |
88.9 mm (3.5 inch)     |
-     | ||||
Coils/Group     | 6     | 2     | -     | ||||
Slots (Coils)     | 6     | 36     | -     | ||||
Turns (Coils)     | 150     | 8     | -     | ||||
No. & Size Wire     | 1 - #16     | 2 - #16     | -     | ||||
Coil Throw     | 1 - 2     | 1 - 6     | -     | ||||
Mean Length Turn (Calc.)     | 388.6 mm (15.3 inch)     |
350.5 mm (13.8 inch)     |
-     | ||||
Copper Weight     | 4.1 kg (9.1 lb)     |
2.2 kg (4.8 lb)     |
-     | ||||
Insulation     | Heavy Polyester Polyamide Imide     | ||||||
Connection (2)     | Series     | 2 Parallel Star     | -     | ||||
Line Leads     | 2 - #14     | 3 - #10     | -     |
Show/hide table
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 04 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram E |
141-5538 Generator
Show/hide table
MAIN STATOR AND ROTOR WINDING DATA     | |||||||
---|---|---|---|---|---|---|---|
ITEM     | STATOR     | ROTOR     | |||||
Stack Height     | 304.8 mm (12.0 inch)     |
304.8 mm (12.0 inch)     |
|||||
Slots     | 48     | -     | |||||
Coil Throw     | 1 - 10     | -     | |||||
Turns/Coil     | 3     | -     | |||||
Turns/Pole     | -     | 130     | |||||
No. & Wire Size     | 10 - #14     | #8 SQ     | |||||
Mean Length Turn     | 1242.1 mm (48.9 inch)     |
-     | |||||
Copper Weight     | 33.7 kg (74.4 lb)     |
48.3 kg (106.5 lb)     |
|||||
Inside Connection (1)     | 4/2 Parallel Star     | 4 in Series     | |||||
Line Leads (No. & Size)     | 12 - #000     | -     | |||||
Terminal bolt size     | 3/8 inch     | -     | |||||
Low Voltage connected line resistance at 25 ° C (77 ° F)     | 0.00712 ohms     | -     | |||||
Field lead resistance at 25 ° C (77 ° F)     | -     | 1.015 ohms     | |||||
EXCITER WINDING DATA     | |||||||
Exciter Frequency (Hz)     | 90 Hz     | Permanent Magnet Frequency     | - Hz     | ||||
Exciter Poles     | 6     | ||||||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | Permanent Magnet Stator     | ||||
Stack Length     | 88.9 mm (3.5 inch)     |
88.9 mm (3.5 inch)     |
-     | ||||
Coils/Group     | 6     | 2     | -     | ||||
Slots (Coils)     | 6     | 36     | -     | ||||
Turns (Coils)     | 150     | 8     | -     | ||||
No. & Size Wire     | 1 - #16     | 2 - #16     | -     | ||||
Coil Throw     | 1 - 2     | 1 - 6     | -     | ||||
Mean Length Turn (Calc.)     | 388.6 mm (15.3 inch)     |
350.5 mm (13.8 inch)     |
-     | ||||
Copper Weight     | 4.1 kg (9.1 lb)     |
2.2 kg (4.8 lb)     |
-     | ||||
Insulation     | Heavy Polyester Polyamide Imide     | ||||||
Connection (2)     | Series     | 2 Parallel Star     | -     | ||||
Line Leads     | 2 - #14     | 3 - #10     | -     |
Show/hide table
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 04 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram E |
141-5539 Generator
Show/hide table
MAIN STATOR AND ROTOR WINDING DATA     | |||||||
---|---|---|---|---|---|---|---|
ITEM     | STATOR     | ROTOR     | |||||
Stack Height     | 304.8 mm (12.0 inch)     |
304.8 mm (12.0 inch)     |
|||||
Slots     | 48     | -     | |||||
Coil Throw     | 1 - 10     | -     | |||||
Turns/Coil     | 2.5 (2-3-2-3)     | -     | |||||
Turns/Pole     | -     | 130     | |||||
No. & Wire Size     | 12 - #14     | #8 SQ     | |||||
Mean Length Turn     | 1244.6 mm (49.0 inch)     |
-     | |||||
Copper Weight     | 33.6 kg (74.0 lb)     |
48.3 kg (106.5 lb)     |
|||||
Inside Connection (1)     | 4/2 Parallel Star     | 4 in Series     | |||||
Line Leads (No. & Size)     | 12 - #0000     | -     | |||||
Terminal bolt size     | 3/8 inch     | -     | |||||
Low Voltage connected line resistance at 25 ° C (77 ° F)     | 0.00448 ohms     | -     | |||||
Field lead resistance at 25 ° C (77 ° F)     | -     | 1.015 ohms     | |||||
EXCITER WINDING DATA     | |||||||
Exciter Frequency (Hz)     | 90 Hz     | Permanent Magnet Frequency     | - Hz     | ||||
Exciter Poles     | 6     | ||||||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | Permanent Magnet Stator     | ||||
Stack Length     | 88.9 mm (3.5 inch)     |
88.9 mm (3.5 inch)     |
-     | ||||
Coils/Group     | 6     | 2     | -     | ||||
Slots (Coils)     | 6     | 36     | -     | ||||
Turns (Coils)     | 150     | 8     | -     | ||||
No. & Size Wire     | 1 - #16     | 2 - #16     | -     | ||||
Coil Throw     | 1 - 2     | 1 - 6     | -     | ||||
Mean Length Turn (Calc.)     | 388.6 mm (15.3 inch)     |
350.5 mm (13.8 inch)     |
-     | ||||
Copper Weight     | 4.1 kg (9.1 lb)     |
2.2 kg (4.8 lb)     |
-     | ||||
Insulation     | Heavy Polyester Polyamide Imide     | ||||||
Connection (2)     | Series     | 2 Parallel Star     | -     | ||||
Line Leads     | 2 - #14     | 3 - #10     | -     |
Show/hide table
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 04 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram E |
141-5540 Generator
Show/hide table
MAIN STATOR AND ROTOR WINDING DATA     | |||||||
---|---|---|---|---|---|---|---|
ITEM     | STATOR     | ROTOR     | |||||
Stack Height     | 360.7 mm (14.2 inch)     |
360.7 mm (14.2 inch)     |
|||||
Slots     | 48     | -     | |||||
Coil Throw     | 1 - 10     | -     | |||||
Turns/Coil     | 2.5 (2-3-2-3)     | -     | |||||
Turns/Pole     | -     | 130     | |||||
No. & Wire Size     | 12 - #14     | #8 SQ     | |||||
Mean Length Turn     | 1353.8 mm (53.3 inch)     |
-     | |||||
Copper Weight     | 40.1 kg (88.5 lb)     |
53.6 kg (118.2 lb)     |
|||||
Inside Connection (1)     | 4/2 Parallel Star     | 4 in Series     | |||||
Line Leads (No. & Size)     | 12 - #000     | -     | |||||
Terminal bolt size     | 3/8 inch     | -     | |||||
Low Voltage connected line resistance at 25 ° C (77 ° F)     | 0.00574 ohms     | -     | |||||
Field lead resistance at 25 ° C (77 ° F)     | -     | 1.115 ohms     | |||||
EXCITER WINDING DATA     | |||||||
Exciter Frequency (Hz)     | 90 Hz     | Permanent Magnet Frequency     | - Hz     | ||||
Exciter Poles     | 6     | ||||||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | Permanent Magnet Stator     | ||||
Stack Length     | 88.9 mm (3.5 inch)     |
88.9 mm (3.5 inch)     |
-     | ||||
Coils/Group     | 6     | 2     | -     | ||||
Slots (Coils)     | 6     | 36     | -     | ||||
Turns (Coils)     | 150     | 8     | -     | ||||
No. & Size Wire     | 1 - #16     | 2 - #16     | -     | ||||
Coil Throw     | 1 - 2     | 1 - 6     | -     | ||||
Mean Length Turn (Calc.)     | 388.6 mm (15.3 inch)     |
350.5 mm (13.8 inch)     |
-     | ||||
Copper Weight     | 4.1 kg (9.1 lb)     |
2.2 kg (4.8 lb)     |
-     | ||||
Insulation     | Heavy Polyester Polyamide Imide     | ||||||
Connection (2)     | Series     | 2 Parallel Star     | -     | ||||
Line Leads     | 2 - #14     | 3 - #10     | -     |
Show/hide table
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 04 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram E |
141-5541 Generator
Show/hide table
MAIN STATOR AND ROTOR WINDING DATA     | |||||||
---|---|---|---|---|---|---|---|
ITEM     | STATOR     | ROTOR     | |||||
Stack Height     | 360.7 mm (14.2 inch)     |
360.7 mm (14.2 inch)     |
|||||
Slots     | 48     | -     | |||||
Coil Throw     | 1 - 11     | -     | |||||
Turns/Coil     | 2     | -     | |||||
Turns/Pole     | -     | 130     | |||||
No. & Wire Size     | 16 - #14     | #8 SQ     | |||||
Mean Length Turn     | 1422.4 mm (56.0 inch)     |
-     | |||||
Copper Weight     | 40.8 kg (90.0 lb)     |
53.6 kg (118.2 lb)     |
|||||
Inside Connection (1)     | 4/2 Parallel Star     | 4 in Series     | |||||
Line Leads (No. & Size)     | 24 - #1     | -     | |||||
Terminal bolt size     | 3/8 inch     | -     | |||||
Low Voltage connected line resistance at 25 ° C (77 ° F)     | 0.00305 ohms     | -     | |||||
Field lead resistance at 25 ° C (77 ° F)     | -     | 1.115 ohms     | |||||
EXCITER WINDING DATA     | |||||||
Exciter Frequency (Hz)     | 90 Hz     | Permanent Magnet Frequency     | - Hz     | ||||
Exciter Poles     | 6     | ||||||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | Permanent Magnet Stator     | ||||
Stack Length     | 88.9 mm (3.5 inch)     |
88.9 mm (3.5 inch)     |
-     | ||||
Coils/Group     | 6     | 2     | -     | ||||
Slots (Coils)     | 6     | 36     | -     | ||||
Turns (Coils)     | 150     | 8     | -     | ||||
No. & Size Wire     | 1 - #16     | 2 - #16     | -     | ||||
Coil Throw     | 1 - 2     | 1 - 6     | -     | ||||
Mean Length Turn (Calc.)     | 388.6 mm (15.3 inch)     |
350.5 mm (13.8 inch)     |
-     | ||||
Copper Weight     | 4.1 kg (9.1 lb)     |
2.2 kg (4.8 lb)     |
-     | ||||
Insulation     | Heavy Polyester Polyamide Imide     | ||||||
Connection (2)     | Series     | 2 Parallel Star     | -     | ||||
Line Leads     | 2 - #14     | 3 - #10     | -     |
Show/hide table
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 47 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram D |
141-5542 Generator
Show/hide table
MAIN STATOR AND ROTOR WINDING DATA     | |||||||
---|---|---|---|---|---|---|---|
ITEM     | STATOR     | ROTOR     | |||||
Stack Height     | 419.1 mm (16.5 inch)     |
419.1 mm (16.5 inch)     |
|||||
Slots     | 48     | -     | |||||
Coil Throw     | 1 - 10     | -     | |||||
Turns/Coil     | 2.25 (2-2-2-3)     | -     | |||||
Turns/Pole     | -     | 130     | |||||
No. & Wire Size     | 7 - #14 and 7 - #13.5     | #8 SQ     | |||||
Mean Length Turn     | 1473.2 mm (58.0 inch)     |
-     | |||||
Copper Weight     | 44.5 kg (98.0 lb)     |
59.1 kg (130.4 lb)     |
|||||
Inside Connection (1)     | 4/2 Parallel Star     | 4 in Series     | |||||
Line Leads (No. & Size)     | 24 - #1     | -     | |||||
Terminal bolt size     | 3/8 inch     | -     | |||||
Low Voltage connected line resistance at 25 ° C (77 ° F)     | 0.00386 ohms     | -     | |||||
Field lead resistance at 25 ° C (77 ° F)     | -     | 1.225 ohms     | |||||
EXCITER WINDING DATA     | |||||||
Exciter Frequency (Hz)     | 90 Hz     | Permanent Magnet Frequency     | - Hz     | ||||
Exciter Poles     | 6     | ||||||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | Permanent Magnet Stator     | ||||
Stack Length     | 88.9 mm (3.5 inch)     |
88.9 mm (3.5 inch)     |
-     | ||||
Coils/Group     | 6     | 2     | -     | ||||
Slots (Coils)     | 6     | 36     | -     | ||||
Turns (Coils)     | 150     | 8     | -     | ||||
No. & Size Wire     | 1 - #16     | 2 - #16     | -     | ||||
Coil Throw     | 1 - 2     | 1 - 6     | -     | ||||
Mean Length Turn (Calc.)     | 388.6 mm (15.3 inch)     |
350.5 mm (13.8 inch)     |
-     | ||||
Copper Weight     | 4.1 kg (9.1 lb)     |
2.2 kg (4.8 lb)     |
-     | ||||
Insulation     | Heavy Polyester Polyamide Imide     | ||||||
Connection (2)     | Series     | 2 Parallel Star     | -     | ||||
Line Leads     | 2 - #14     | 3 - #10     | -     |
Show/hide table
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 47 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram D |
141-5543 Generator
Show/hide table
MAIN STATOR AND ROTOR WINDING DATA     | |||||||
---|---|---|---|---|---|---|---|
ITEM     | STATOR     | ROTOR     | |||||
Stack Height     | 419.1 mm (16.5 inch)     |
419.1 mm (16.5 inch)     |
|||||
Slots     | 48     | -     | |||||
Coil Throw     | 1 - 11     | -     | |||||
Turns/Coil     | 1.75 (1-2-2-2)     | -     | |||||
Turns/Pole     | -     | 130     | |||||
No. & Wire Size     | 18 - #14     | #8 SQ     | |||||
Mean Length Turn     | 1524.0 mm (60.0 inch)     |
-     | |||||
Copper Weight     | 43.5 kg (96.0 lb)     |
59.1 kg (130.4 lb)     |
|||||
Inside Connection (1)     | 4/2 Parallel Star     | 4 in Series     | |||||
Line Leads (No. & Size)     | 24 - #0     | -     | |||||
Terminal bolt size     | 3/8 inch     | -     | |||||
Low Voltage connected line resistance at 25 ° C (77 ° F)     | 0.00257 ohms     | -     | |||||
Field lead resistance at 25 ° C (77 ° F)     | -     | 1.225 ohms     | |||||
EXCITER WINDING DATA     | |||||||
Exciter Frequency (Hz)     | 90 Hz     | Permanent Magnet Frequency     | - Hz     | ||||
Exciter Poles     | 6     | ||||||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | Permanent Magnet Stator     | ||||
Stack Length     | 88.9 mm (3.5 inch)     |
88.9 mm (3.5 inch)     |
-     | ||||
Coils/Group     | 6     | 2     | -     | ||||
Slots (Coils)     | 6     | 36     | -     | ||||
Turns (Coils)     | 150     | 8     | -     | ||||
No. & Size Wire     | 1 - #16     | 2 - #16     | -     | ||||
Coil Throw     | 1 - 2     | 1 - 6     | -     | ||||
Mean Length Turn (Calc.)     | 388.6 mm (15.3 inch)     |
350.5 mm (13.8 inch)     |
-     | ||||
Copper Weight     | 4.1 kg (9.1 lb)     |
2.2 kg (4.8 lb)     |
-     | ||||
Insulation     | Heavy Polyester Polyamide Imide     | ||||||
Connection (2)     | Series     | 2 Parallel Star     | -     | ||||
Line Leads     | 2 - #14     | 3 - #10     | -     |
Show/hide table
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 47 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram D |
141-5544 Generator
Show/hide table
MAIN STATOR AND ROTOR WINDING DATA     | |||||||
---|---|---|---|---|---|---|---|
ITEM     | STATOR     | ROTOR     | |||||
Stack Height     | 495.3 mm (19.5 inch)     |
495.3 mm (19.5 inch)     |
|||||
Slots     | 48     | -     | |||||
Coil Throw     | 1 - 10     | -     | |||||
Turns/Coil     | 2     | -     | |||||
Turns/Pole     | -     | 130     | |||||
No. & Wire Size     | 14 - #14 and 4 - #13.5     | #8 SQ     | |||||
Mean Length Turn     | 1783.1 mm (70.2 inch)     |
-     | |||||
Copper Weight     | 54.4 kg (120.0 lb)     |
66.4 kg (146.4 lb)     |
|||||
Inside Connection (1)     | 4/2 Parallel Star     | 4 in Series     | |||||
Line Leads (No. & Size)     | 24 - #0     | -     | |||||
Terminal bolt size     | 3/8 inch     | -     | |||||
Low Voltage connected line resistance at 25 ° C (77 ° F)     | 0.00304 ohms     | -     | |||||
Field lead resistance at 25 ° C (77 ° F)     | -     | 1.40 ohms     | |||||
EXCITER WINDING DATA     | |||||||
Exciter Frequency (Hz)     | 90 Hz     | Permanent Magnet Frequency     | - Hz     | ||||
Exciter Poles     | 6     | ||||||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | Permanent Magnet Stator     | ||||
Stack Length     | 88.9 mm (3.5 inch)     |
88.9 mm (3.5 inch)     |
-     | ||||
Coils/Group     | 6     | 2     | -     | ||||
Slots (Coils)     | 6     | 36     | -     | ||||
Turns (Coils)     | 150     | 8     | -     | ||||
No. & Size Wire     | 1 - #16     | 2 - #16     | -     | ||||
Coil Throw     | 1 - 2     | 1 - 6     | -     | ||||
Mean Length Turn (Calc.)     | 388.6 mm (15.3 inch)     |
350.5 mm (13.8 inch)     |
-     | ||||
Copper Weight     | 4.1 kg (9.1 lb)     |
2.2 kg (4.8 lb)     |
-     | ||||
Insulation     | Heavy Polyester Polyamide Imide     | ||||||
Connection (2)     | Series     | 2 Parallel Star     | -     | ||||
Line Leads     | 2 - #14     | 3 - #10     | -     |
Show/hide table
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 47 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram D |
141-5545 Generator
Show/hide table
MAIN STATOR AND ROTOR WINDING DATA     | |||||||
---|---|---|---|---|---|---|---|
ITEM     | STATOR     | ROTOR     | |||||
Stack Height     | 495.3 mm (19.5 inch)     |
495.3 mm (19.5 inch)     |
|||||
Slots     | 48     | -     | |||||
Coil Throw     | 1 - 10     | -     | |||||
Turns/Coil     | 1.75 (1-2-2-2)     | -     | |||||
Turns/Pole     | -     | 130     | |||||
No. & Wire Size     | 14 - #14 and 4 - #13.5     | #8 SQ     | |||||
Mean Length Turn     | 1625.6 mm (64.0 inch)     |
-     | |||||
Copper Weight     | 47.2 kg (104.0 lb)     |
66.4 kg (146.4 lb)     |
|||||
Inside Connection (1)     | 2 Parallel Star     | 4 in Series     | |||||
Line Leads (No. & Size)     | 24 - #00     | -     | |||||
Terminal bolt size     | 3/8 inch     | -     | |||||
Low Voltage connected line resistance at 25 ° C (77 ° F)     | 0.00265 ohms     | -     | |||||
Field lead resistance at 25 ° C (77 ° F)     | -     | 1.40 ohms     | |||||
EXCITER WINDING DATA     | |||||||
Exciter Frequency (Hz)     | 90 Hz     | Permanent Magnet Frequency     | - Hz     | ||||
Exciter Poles     | 6     | ||||||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | Permanent Magnet Stator     | ||||
Stack Length     | 88.9 mm (3.5 inch)     |
88.9 mm (3.5 inch)     |
-     | ||||
Coils/Group     | 6     | 2     | -     | ||||
Slots (Coils)     | 6     | 36     | -     | ||||
Turns (Coils)     | 150     | 8     | -     | ||||
No. & Size Wire     | 1 - #16     | 2 - #16     | -     | ||||
Coil Throw     | 1 - 2     | 1 - 6     | -     | ||||
Mean Length Turn (Calc.)     | 388.6 mm (15.3 inch)     |
350.5 mm (13.8 inch)     |
-     | ||||
Copper Weight     | 4.1 kg (9.1 lb)     |
2.2 kg (4.8 lb)     |
-     | ||||
Insulation     | Heavy Polyester Polyamide Imide     | ||||||
Connection (2)     | Series     | 2 Parallel Star     | -     | ||||
Line Leads     | 2 - #14     | 3 - #10     | -     |
Show/hide table
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 50 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram D |
141-5546 Generator
Show/hide table
MAIN STATOR AND ROTOR WINDING DATA     | |||||||
---|---|---|---|---|---|---|---|
ITEM     | STATOR     | ROTOR     | |||||
Stack Height     | 360.7 mm (14.2 inch)     |
360.7 mm (14.2 inch)     |
|||||
Slots     | 48     | -     | |||||
Coil Throw     | 1 - 10     | -     | |||||
Turns/Coil     | 2.5 (2-3-2-3)     | -     | |||||
Turns/Pole     | -     | 130     | |||||
No. & Wire Size     | 12 - #14     | #8 SQ     | |||||
Mean Length Turn     | 1353.8 mm (53.3 inch)     |
-     | |||||
Copper Weight     | 40.1 kg (88.5 lb)     |
53.6 kg (118.2 lb)     |
|||||
Inside Connection (1)     | 4/2 Parallel Star     | 4 in Series     | |||||
Line Leads (No. & Size)     | 12 - #000     | -     | |||||
Terminal bolt size     | 3/8 inch     | -     | |||||
Low Voltage connected line resistance at 25 ° C (77 ° F)     | 0.00574 ohms     | -     | |||||
Field lead resistance at 25 ° C (77 ° F)     | -     | 1.115 ohms     | |||||
EXCITER WINDING DATA     | |||||||
Exciter Frequency (Hz)     | 90 Hz     | Permanent Magnet Frequency     | - Hz     | ||||
Exciter Poles     | 6     | ||||||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | Permanent Magnet Stator     | ||||
Stack Length     | 88.9 mm (3.5 inch)     |
88.9 mm (3.5 inch)     |
-     | ||||
Coils/Group     | 6     | 2     | -     | ||||
Slots (Coils)     | 6     | 36     | -     | ||||
Turns (Coils)     | 150     | 8     | -     | ||||
No. & Size Wire     | 1 - #16     | 2 - #16     | -     | ||||
Coil Throw     | 1 - 2     | 1 - 6     | -     | ||||
Mean Length Turn (Calc.)     | 388.6 mm (15.3 inch)     |
350.5 mm (13.8 inch)     |
-     | ||||
Copper Weight     | 4.1 kg (9.1 lb)     |
2.2 kg (4.8 lb)     |
-     | ||||
Insulation     | Heavy Polyester Polyamide Imide     | ||||||
Connection (2)     | Series     | 2 Parallel Star     | -     | ||||
Line Leads     | 2 - #14     | 3 - #10     | -     |
Show/hide table
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 04 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram E |
141-5547 Generator
Show/hide table
MAIN STATOR AND ROTOR WINDING DATA     | |||||||
---|---|---|---|---|---|---|---|
ITEM     | STATOR     | ROTOR     | |||||
Stack Height     | 360.7 mm (14.2 inch)     |
360.7 mm (14.2 inch)     |
|||||
Slots     | 48     | -     | |||||
Coil Throw     | 1 - 11     | -     | |||||
Turns/Coil     | 2     | -     | |||||
Turns/Pole     | -     | 130     | |||||
No. & Wire Size     | 16 - #14     | #8 SQ     | |||||
Mean Length Turn     | 1422.4 mm (56.0 inch)     |
-     | |||||
Copper Weight     | 40.8 kg (90.0 lb)     |
53.6 kg (118.2 lb)     |
|||||
Inside Connection (1)     | 4/2 Parallel Star     | 4 in Series     | |||||
Line Leads (No. & Size)     | 24 - #1     | -     | |||||
Terminal bolt size     | 3/8 inch     | -     | |||||
Low Voltage connected line resistance at 25 ° C (77 ° F)     | 0.00305 ohms     | -     | |||||
Field lead resistance at 25 ° C (77 ° F)     | -     | 1.115 ohms     | |||||
EXCITER WINDING DATA     | |||||||
Exciter Frequency (Hz)     | 90 Hz     | Permanent Magnet Frequency     | - Hz     | ||||
Exciter Poles     | 6     | ||||||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | Permanent Magnet Stator     | ||||
Stack Length     | 88.9 mm (3.5 inch)     |
88.9 mm (3.5 inch)     |
-     | ||||
Coils/Group     | 6     | 2     | -     | ||||
Slots (Coils)     | 6     | 36     | -     | ||||
Turns (Coils)     | 150     | 8     | -     | ||||
No. & Size Wire     | 1 - #16     | 2 - #16     | -     | ||||
Coil Throw     | 1 - 2     | 1 - 6     | -     | ||||
Mean Length Turn (Calc.)     | 388.6 mm (15.3 inch)     |
350.5 mm (13.8 inch)     |
-     | ||||
Copper Weight     | 4.1 kg (9.1 lb)     |
2.2 kg (4.8 lb)     |
-     | ||||
Insulation     | Heavy Polyester Polyamide Imide     | ||||||
Connection (2)     | Series     | 2 Parallel Star     | -     | ||||
Line Leads     | 2 - #14     | 3 - #10     | -     |
Show/hide table
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 47 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram D |
142-4935 Generator
Show/hide table
MAIN STATOR AND ROTOR WINDING DATA     | |||||||
---|---|---|---|---|---|---|---|
ITEM     | STATOR     | ROTOR     | |||||
Stack Height     | 495.3 mm (19.5 inch)     |
495.3 mm (19.5 inch)     |
|||||
Slots     | 48     | -     | |||||
Coil Throw     | 1 - 10     | -     | |||||
Turns/Coil     | 2     | -     | |||||
Turns/Pole     | -     | 130     | |||||
No. & Wire Size     | 18 - #14     | #8 SQ     | |||||
Mean Length Turn     | 1623.1 mm (63.9 inch)     |
-     | |||||
Copper Weight     | 52.9 kg (116.7 lb)     |
66.4 kg (146.4 lb)     |
|||||
Inside Connection (1)     | 4/2 Parallel Star     | 4 in Series     | |||||
Line Leads (No. & Size)     | 24 - #0     | -     | |||||
Terminal bolt size     | 3/8 inch     | -     | |||||
Low Voltage connected line resistance at 25 ° C (77 ° F)     | 0.00377 ohms     | -     | |||||
Field lead resistance at 25 ° C (77 ° F)     | -     | 1.40 ohms     | |||||
EXCITER WINDING DATA     | |||||||
Exciter Frequency (Hz)     | 90 Hz     | Permanent Magnet Frequency     | 120 Hz     | ||||
Exciter Poles     | 6     | 8     | |||||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | Permanent Magnet Stator     | ||||
Stack Length     | 88.9 mm (3.5 inch)     |
88.9 mm (3.5 inch)     |
31.8 mm (1.25 inch)     |
||||
Coils/Group     | 6     | 2     | 1     | ||||
Slots (Coils)     | 6     | 36     | 24     | ||||
Turns (Coils)     | 150     | 8     | 12     | ||||
No. & Size Wire     | 1 - #16     | 2 - #16     | 2 - #18     | ||||
Coil Throw     | 1 - 2     | 1 - 6     | 1 - 4     | ||||
Mean Length Turn (Calc.)     | 388.6 mm (15.3 inch)     |
350.5 mm (13.8 inch)     |
330.2 mm (13.0 inch)     |
||||
Copper Weight     | 4.1 kg (9.1 lb)     |
2.2 kg (4.8 lb)     |
0.5 kg (1.0 lb)     |
||||
Insulation     | Heavy Polyester Polyamide Imide     | ||||||
Connection (2)     | Series     | 2 Parallel Star     | Star     | ||||
Line Leads     | 2 - #14     | 3 - #10     | 3 - #14     |
Show/hide table
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 47 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram D |
142-9900 Generator Ar
Show/hide table
MAIN STATOR AND ROTOR WINDING DATA     | |||||||
---|---|---|---|---|---|---|---|
ITEM     | STATOR     | ROTOR     | |||||
Stack Height     | 914.4 mm (36 inch)     |
927.10 mm (36.5 inch)     |
|||||
Slots     | 90     | 4     | |||||
Coil Throw     | 1-12     | 1 - 2     | |||||
Turns/Coil     | 1     | -     | |||||
Turns/Pole     | -     | 163.5 (3)     | |||||
No. & Wire Size     | 3 - 5.1816 mm (0.204 inch) x 8.2550 mm (0.325 inch) 3 High x 1 Wide     |
1 of 3.6576 mm (0.144 inch) X 7.3152 mm (0.288 inch)     |
|||||
Mean Length Turn     | 2712.72 mm (106.8 inch)     |
2311.4 mm (91 inch)     |
|||||
Copper Weight     | 276.6 kg (610 lb)     |
549.7 kg (1212 lb)     |
|||||
Inside Connection     | 3 Parallel Wye     | Series     | |||||
Line Leads (No. & Size)     | 6 - 6 of # 2/0     | 2 of #6 Ld     | |||||
Low Voltage connected line resistance at 25° C (77.0° F)     |
0.00305 ohms     | -     | |||||
Field lead resistance at 25° C (77.0° F)     |
-     | 1.522     | |||||
EXCITER WINDING DATA     | |||||||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | Permanent Magnet Stator     | ||||
Exciter Frequency (Hz)     | 80 Hz     | 80 Hz     |     | ||||
Exciter Poles     | 8     | 8     |     | ||||
Stack Length     | 88.90 mm (3.5 inch)     |
88.90 mm (3.5 inch)     |
    | ||||
Coils/Group     | 1     | 1     |     | ||||
Turns (Coils)     | 320     | 16     |     | ||||
No. & Size Wire     | 2 # 18.5     | 3 of #16     |     | ||||
Coil Throw     | 1 - 2     | 1 - 6     |     | ||||
Mean Length Turn     | 355.6 mm (14 inch)     |
419.10 mm (16.5 inch)     |
    | ||||
Resistance at 25° C (77.0° F)     |
3.2 ohms     | 0.122 ohms     |     | ||||
Copper Weight     | 14.01 kg (30.9 lb)     |
6.3 kg (14 lb)     |
    | ||||
Connection     | 2Gr Ser/Par     | 2 Parallel Wye     |     | ||||
Line Leads     | #14     | 3 - #10     |     |
Show/hide table
( 3 ) | Winding table: wind 4-layers of 15 turns, 2-layers of 14 turns, 1-layer of 13 turns, 1-layer of 12 turns, 1-layer of 11turns, 1-layer of 10 turns, 1-layer of 9 turns, 1-layer of 8-turns, 1-layer of 6.5 turns, 1-layer of 6 turns = 163.5 turns. |
Caterpillar Information System:
SR4 and SR4B Electric Power Generation Rewind Data Winding Data for 136-6580 Generator through 136-6609 Generator
SR4 and SR4B Electric Power Generation Rewind Data Winding Data for 126-8022 Generator through 128-7424 Generator
C1.7, C1.8 and C2.4 Tier 4 Interim and EU Stage 3A Engines for Caterpillar Built Machines Engine Oil Pressure Switch
CX31 and CX31 HT On-Highway Transmissions (Cat Truck) Transmission Hydraulic Control
2013/09/20 A Rework Procedure for the Power Access Stairway (PAS) On Certain Off-Highway Trucks is Now Available {7253}
2013/09/27 New Software Is Now Available for All Cat® Products With The Product Link 522 System {7606}
Rework Procedure for the PAS (Powered Access Stairway) on Certain Off-Highway Trucks{0679, 7253, 7254, 7255} Rework Procedure for the PAS (Powered Access Stairway) on Certain Off-Highway Trucks{0679, 7253, 7254, 7255}
LC5000, LC6100, and LC7000 Electric Power Generation Exciter Armature - Remove and Install
C280-16 Engine Priority Valve - Install
3512C Petroleum Engines with Dynamic Gas Blending Data Link - Test
C280-16 Engine Auxiliary Water Pump - Install
C280-16 Engine Auxiliary Water Pump - Remove
312D2 and 313D2 Excavators System Pressure Release
3512C Petroleum Engines with Dynamic Gas Blending Engine Shutdown Occurrence
SR4 and SR4B Electric Power Generation Rewind Data Winding Data for 144-1666 Generator through 144-1766 Generator
SR4 and SR4B Electric Power Generation Rewind Data Winding Data for 136-6610 Generator through 136-6641 Generator
SR4 and SR4B Electric Power Generation Rewind Data Winding Data for 144-1964 Generator through 144-2088 Generator
SR4 and SR4B Electric Power Generation Rewind Data Winding Data for 149-2447 Generator through 150-9152 Generator
SR4 and SR4B Electric Power Generation Rewind Data Winding Data for 158-6410 Generator through 163-8546 Generator
SR4 and SR4B Electric Power Generation Rewind Data Winding Data for 164-0975 Generator through 164-4946 Generator
SR4 and SR4B Electric Power Generation Rewind Data Winding Data for 173-7078 Generator through 194-6563 Generator
SR4 and SR4B Electric Power Generation Rewind Data Winding Data for 203-5749 Generator through 324-5120 Generator
SR4 and SR4B Electric Power Generation Rewind Data Winding Data for 6I-0053 Generator through 6I-4860 Generator
2013/11/11 An Improved ARD Combustion Head is Now Used on the Tier 4 Engines of Certain Machines {108B, 108E, 108M}