Ethernet - Configure
Note: Each MMU requires the following procedures.
Show/hide table
Illustration 1 | g01273567 |
PC Settings and Connection settings |
- Place the system into BYPASS mode by turning the keyswitch to the BYPASS position.
- Click "PC Settings/Connection Settings" on the toolbar.
- Connect to a computer that is equipped with "UPSView". Connect to the RS 232 port in the system cabinet.
- Select the appropriate MMU. Select the MMU with the Selector Switch on the Parallel Cabinet Interface (PCI).
Show/hide table
Illustration 2 g01273569 "UPSView" Connection Settings - Click "Connect" on the "Connection Menu".
Show/hide table
Illustration 3 g01273571 Connect to "UPSView" - Click "Enter Password" on the Main Tool Bar.
- Enter the User name and the password in the "Enter Password Screen".
Show/hide table
Illustration 4 g01273572 User Name and Password Entry Screen - Click "OK".
Note: To change the "Network Enable" parameter, a special password must be obtained from Active Power.
- Click "OP. Params \ OP Group 5 Internal CAN Enable \ Network Enable" on the Main Toolbar.
- Change the default 0 to 1.
- Click "Send".
- Press "Y" in order to confirm the reset of the processor.
Enabling of the Ethernet Options is now complete.
Note: Wait for reboot before attempting to continue.
- Click "UPSView Settings".
- Click "Remote Notification Settings" from the "UPSView Settings" Menu.
Show/hide table
Illustration 5 g01273593 Enable the Network Drop-Down Menus. Show/hide tableIllustration 6 g01273594 Enable Network Screen. Show/hide tableIllustration 7 g01273595 Settings Drop-Down Menus. - Click "Network Configuration" from the Remote Notifications Menu.
Show/hide table
Illustration 8 g01273596 Network Configuration Screen. - Enter Network Information in the Network Configuration Screen. See your system administrator for Network Information.
- Click "Send" Button. Text will appear on the Text Box Window Stating "Accept / Decline".
- Click "Receive" in order to verify the Network Settings.
- Close the screen.
- Press "CTRL-R" in order to Reset the processor.
- Press "Y" in order to acknowledge the Reset of the Processor.
Note: Default Gateway: Revision E SNMP must be enabled to use this feature.
Caterpillar Information System:
2006/06/01 Do Not Reuse the Hold Down Bolts for the Fuel Injector {1290}
2014/08/14 Do Not Reuse the Hold Down Bolts for the Fuel Injectors On All Products that Contain C9 Through C32 Engines {1290}
2006/05/29 Do Not Reuse the Hold Down Bolts for the Fuel Injector {1290}
C4.4 Industrial Engine Air Inlet and Exhaust System - Inspect
Filtration Procedure for Transmission Oil on Motor Graders Without Ecology Drain {0680, 0768, 3030} Filtration Procedure for Transmission Oil on Motor Graders Without Ecology Drain {0680, 0768, 3030}
UPS 1000S/ UPS 1200S Uninterruptible Power Supplys Maintenance Bypass Controller PWA
UPS 120, UPS 150, UPS 250, UPS 300, UPS 301, UPS 500, UPS 600, UPS 750 and UPS 900 Uninterruptible Power Supplies Modbus Network - Setup
UPS 120, UPS 150, UPS 250, UPS 300, UPS 301, UPS 500, UPS 600, UPS 750 and UPS 900 Uninterruptible Power Supplies Rotor Position Sensor - Calibrate
UPS 120, UPS 150, UPS 250, UPS 300, UPS 301, UPS 500, UPS 600, UPS 750 and UPS 900 Uninterruptible Power Supplies Zig Zag Thyristor (MMS System Cabinet)
UPS 120, UPS 150, UPS 250, UPS 300, UPS 301, UPS 500, UPS 600, UPS 750 and UPS 900 Uninterruptible Power Supplies Zig Zag Overload Relay (MMS System Cabinet)
UPS 120, UPS 150, UPS 250, UPS 300, UPS 301, UPS 500, UPS 600, UPS 750 and UPS 900 Uninterruptible Power Supplies Zig Zag Circuit Breaker (MMS System Cabinet)
UPS 120, UPS 150, UPS 250, UPS 300, UPS 301, UPS 500, UPS 600, UPS 750 and UPS 900 Uninterruptible Power Supplies Zig Zag Controller PWA (MMS System Cabinet)
C7 and C9 On-Highway Engines Engine Monitoring Parameters
UPS 1000S/ UPS 1200S Uninterruptible Power Supplys Maintenance Power Supply PWA
2006/05/29 Radiator pedestal on 1104C-TAG engines: Smaller engine mounting holes for improved accuracy of the fan position in the radiator cowl. {1353}
UPS 120, UPS 150, UPS 250, UPS 300, UPS 301, UPS 500, UPS 600, UPS 750 and UPS 900 Uninterruptible Power Supplies Remote Input/Output Dry Contact - Setup
2006/06/01 New Connecting Rod and Main Bearings {1203, 1218, 1230}
UPS 1000S/ UPS 1200S Uninterruptible Power Supplys Time Delay Relay
UPS 1000S/ UPS 1200S Uninterruptible Power Supplys Transformer (Maintenance Bypass Cabinet)
TA19-M2WD and TA19-M4WD Agricultural Transmissions Transmission Oil Sample - Obtain
UPS 1000S/ UPS 1200S Uninterruptible Power Supplys Cable Landing (Maintenance Bypass Cabinet)
C9 Engine for Caterpillar Built Machines Camshaft - Remove
UPS 120, UPS 150, UPS 250, UPS 300, UPS 301, UPS 500, UPS 600, UPS 750 and UPS 900 Uninterruptible Power Supplies Emergency Power Off - Reset
UPS 120, UPS 150, UPS 250, UPS 300, UPS 301, UPS 500, UPS 600, UPS 750 and UPS 900 Uninterruptible Power Supplies Remote Notification - Setup