UPS 1000S/ UPS 1200S Uninterruptible Power Supplys Caterpillar


Flywheel Messages

Usage:

ES12F CZE

Table 1
Event Type    
Code     Type     Color    
A     Alarm     Red    
N     Notice     Yellow    
L     Log     Green    

Table 2
UPS Status    
Code     Status    
A     AVR    
B     Bypass    
D     Discharge    
NC     No Change    
S     Shutdown    
O     Online    

Note: The UPS will remain online as long as there are enough functioning flywheels to support the load. Therefore, any notice or alarm from a flywheel may not result in a UPS state change.

If the UPS status is not online or discharge, the load will not be protected during a utility outage. If the "UPS Status" is "AVR" or "Bypass", the load will be powered but not protected from a utility outage If the UPS status is "Shutdown", the load will not have power for a certain amount of time regardless o the utility source.

Table 3
!!ERROR!! DEADLINE TIMEOUT!!     A     A     The main control board has been reset from a "frozen" state.    
!!ERROR!! Memory Access Timeout!!     A     A     The main control board has detected a memory access problem.    
Low 24V Supply Detected.     N     A     The main control board has detected a loss of 24 vdc control power.    
Resetting the APC Board     L, A     A     The main control board has been reset.    
+15V APC1 PS Failure:     A     A     The main control board has detected a 15 vdc power supply failure.    
"<userName> Logged In", Engr/Mfg authorized for 30 minutes.     L     NC     A password has been accepted.    
"<userName> Logged In", "Field Service" authorized for 30 minutes.     L     NC     A service level password has been accepted.    
-15V APC1 PS Failure:     A     A     The main control board has detected a 15 vdc power supply failure.    
190V PS has failed.     A     A     The main control board has detected a loss of control power.    
Accepted service mode password, authorized for 30 minutes     L     NC     A valid password has been accepted.    
CAN Node Offline.     N     A     The indicated node on the CAN network has failed for report.    
CAN Node Online.     L     NC     The indicated node on the CAN network has returned to the network.    
cannot enter calibration, FWA at 100 RPM     L     NC     Certain calibrations cannot be performed while the flywheel is spinning.    
Code update: abort requested     L     A     A user command was entered to abort the firmware update.    
Code update: failed, device could not be programmed     A     A     Firmware has failed to be loaded, check communication connection and setpoints.    
Code update: failed, not in programming mode     N     A     Firmware not set to receive program upload.    
Code update: failed, timed-out waiting for data     N
   
A     Firmware has failed to be loaded, check communication connection and setpoints.    
Code update: receiving data     L     A     The firmware is being transferred to the controller (APC)    
Code update: successful     L     A     The firmware was successfully loaded into the controller and flash memory.    
Code update: updating flash     L     A     The firmware is being transferred to the flash memory.    
Connected on HV Service Port     L     A     A UPS View connection (laptop) has been made to the service port.    
CSHV Power Up     L     B, S     Control power has been restored to the UPS.    
CSNet Master Changed, Previous: X, Now: Y     L     O, A     The master of the CSNet (internal network) has changed.    
CTI Datalock Lost.     A     A
   
The CTI PWA is not communicating with the main control board.    
Datalock returned: Pri. CS HV #1-4     L     NC     The primary CSNet datalock has returned. Communication has been re-established.    
Datalock returned: Red. CS HV #1-4     L     NC     The redundant CSNet datalock has returned. Communication has been re-established.    
DC BUS Current at _, Max Overload Exceeded     N, A     B, S     A DC bus current overload terminated the discharge.    
DC Bus Current Overload at _ Amps DC     A     B, S     A DC bus current overload occurred during the discharge.    
DC Bus Fuse Failure     A     A     A DC bus fuse has failed.    
DC Bus Fuse Status error (indicates fixed)     N     A     A DC bus fuse has failed.    
DC Bus Overvolt at _ VDC     A     A     A DC bus overvoltage has occurred.    
DC Bus Precharge Timeout, VDC = _._     A     A     The precharge circuit has failed to achieve the correct DC bus voltage.    
DC High Voltage Error: _._ Vdc, _._ Amps     A     A     The DC bus voltage has exceeded the upper limit.    
DC Low Voltage Error: _._ Vdc, _._ Amps     A     A     The DC bus voltage has fallen below the lower limit.    
DCSW Closed, DC bus=_._ V     L     NC     The manual DC switch has been closed.    
DCSW Opened, DC bus=_._ V, _._ A     L     NC     The manual DC switch has been opened.    
Discharging at _ KW, FWA: _, FWB: _ RPM.     L     D     The flywheels are discharging at the specified kW.    
Disconnected on HV Service Port     L     NC     A UPS View connection (laptop) has been disconnected from the service port.    
EMO Activated     A     A     The EMO button on the cabinet door has been pressed. The flywheel cabinet must be reset to reactivate the flywheels.    
Fan 1 has failed.     N     NC     One of the fans in the flywheel cabinet has failed.    
Fan 2 has failed.     N     NC     One of the fans in the flywheel cabinet has failed.    
Fan 3 has failed.     N     NC     One of the fans in the flywheel cabinet has failed.    
FW%c: Operating Temp is now above xx, Preheating     L     A     The cabinet (ambient) temperature has risen above the valid operating level.    
FW [A,B] At Speed, _ RPM. Recharge time = _:_     L     O     The flywheel has been motored to its standby speed.    
FW [A,B] Bot Field Coil Timeout     A     A     The controller has failed to drive current into the field coil.    
FW [A,B] Braking at _ RPM     L     A     Due to a service command, the controller has started braking the flywheels.    
FW [A,B] Continue preheat equalization for _._ minutes     L     A     The flywheel will be in rotor equalization mode for the indicated minutes. Flywheel motoring will begin after the equalization period.    
FW [A,B] Continue preheat for _._ minutes, from _._ C     L     A     The flywheel will be in rotor pre-heat mode for the indicated minutes.    
FW [A,B] Datalock Lost.     N     A     The flywheel controller has failed to communicate with the flywheel Interface circuit board. (FWI PWA)    
FW [A,B] Discharge complete, Duration: _._ sec     L     O     The flywheel discharge has been completed.    
FW [A,B] Discharge Disabled     L     A     The flywheel is not capable of discharging.    
FW [A,B] Discharge Enabled at _ RPM     L     O     The flywheel is capable of discharging.    
FW [A,B] Discharge Ended, Min. RPM reached at _ RPM     L     B, S     The flywheel discharge has ended due to the minimum RPM limit.    
FW [A,B] Discharge open     L     O     UPS View command was received that removes the 'discharge blocked' command.    
FW [A,B] Enabling RPS Advance Fine Calibration     L     A     A UPS View command was received that begins the RPS Advance Fine Calibration.    
FW [A,B] Enabling RPS Advance Rough Calibration     L     A     A UPS View command was received that begins the "RPS Advance Rough Calibration".    
FW [A,B] EOD- Max. Duration exceeded at _ RPM     L     B, S     The flywheel discharge has ended due to the maximum discharge time limit.    
FW [A,B] Finished Rough Calibration, rough setting at:_     L     B     The "RPS Advance Rough Calibration" has been completed. The Fine calibration should occur once the flywheel is at full speed.    
FW [A,B] Forcing Nonstandard Preheat     L     A     A UPS View command was received that causes a nonstandard preheat. The issuer of this command is confident that the flywheel has been in a stable temperature environment for the past 72 hours.    
FW [A,B] FWI Datalock Fault     A     A     The flywheel controller has failed to communicate with the flywheel Interface circuit board.(FWI PWA)    
FW [A,B] In Auto Testing Mode at _ RPM     L     A     General start-up message    
FW [A,B] Load cell Fault - CM     A     A     The flywheel load cell signal has a grounded or bad connection.    
FW [A,B] Load cell Fault - HI     A     A     The flywheel weight as measured by the load cell has exceeded the upper limit.    
FW [A,B] Load cell Fault - LO     A     A     The flywheel weight as measured by the load cell has fallen below the lower limit.    
FW [A,B] Load cell Integrity Error: _._ lbs     A     A     The flywheel weight as measured by the load cell is not within the startup limits    
FW [A,B] Mtr Sweep Up failed waiting     N, A     A     The controller has failed to motor the flywheel to at least 50RPM after 5 start sweep attempts or it has failed to receive a speed feedback signal.    
FW [A,B] Mtring at _ RPM         A     The flywheel is being motored to its standby speed.    
FW [A,B] Preheat complete, equalizing for _._ minutes L A     L     A     The flywheel will be in rotor equalization mode for the indicated minutes. Flywheel motoring will begin after the equalization period.    
FW [A,B] Preheat interrupted - _._ minutes left     L     A, B     The rotor preheat has been interrupted.    
FW [A,B]] Preheat rotor for _._ minutes, from _._ C     L     A     The flywheel will be in rotor pre-heat mode for the indicated minutes.    
FW [A,B] RangeFault: A: <telemName>: 1.0 <units>     A     A     The telemetry channel has exceeded the maximum readable bounds.    
FW [A,B] RPS Advance Calibrated at xx, Continuing     L     O     A portion of the "RPS Advance Fine Calibration" has been completed but it is not finished.    
FW [A,B] RPS Calibration Done, Position: 1     L     O     The "RPS Advance Fine Calibration" has finished.    
FW [A,B] RPS Error     N     NC     A speed sensor error has occurred.    
FW [A,B] ShutDn at _ RPM     A     A     The flywheel has been placed in shutdown mode (no motoring, no unloading, no discharging) either due to an error or a service command.    
FW [A,B] Skiip 1,2,3] Error     N     A     One of the flywheel "Skiips" (IGBT) has generated an error.    
FW [A,B] Skip current Offset Error.     N, A     A     There is a problem with one of the Skiip (IGBT) current feedback.    
FW [A,B] Starting RPS Advance Fine Calibration         A     The flywheel has reached the appropriate speed to being the "RPS Advance Fine " calibration.    
FW [A,B] Starting RPS Advance Rough Calibration         A     The flywheel has reached the appropriate speed to being the "RPS Advance Rough" calibration.    
FW [A,B] Top Field Coil Timeout     A     A     The controller has failed to drive current into the field coil.    
FW [A,B] Unloading Time-out     A     A     The controller has failed to unload (lift) the rotor from the bottom bearing within a certain amount of time.    
FW [A,B]: Motoring Timeout at xx RPM - Please perform RPS Calibration     N     A     The controller has failed to increase the flywheels speed beyond 50 rpm.    
FW [A,B]: Preheat Not Allowed: Temp is below xx C (yy C)     N     A     The cabinet (ambient) temperature is below the valid operating level.    
Loaded Default Operating Parameters     L     NC     The UPS View command to load the default operating parameters has been issued.    
Loaded Restricted Operating Parameters     L     NC     The UPS View command to load the default restricted operating parameters has been issued.    
Local Event Log Erased     L     NC     The event log memory has been erased.    
Logged In, Service mode authorized for 30 minutes     L     NC     A valid password has been accepted.    
Logged Out     L     NC     The password that was entered via CSView has timed out.    
Login Failed     L     NC     An invalid password was entered via CSView    
Lost data lock: GPI Dlock     A     A     The controller (APC2) has lost communication with one of the other PWAs on the Multidrop network.    
Lost Datalock: Pri. CS HV #x     N     A     The flywheel cabinet has lost communication with the primary CSNET.    
Lost Datalock:Red. CS HV #x     N     A     The flywheel cabinet has lost communication with the secondary CSNET    
Op Param chg: op_param_name, from _ -> _     L     NC     An operating parameter has changed.    
Op Params Defaulted     L     NC     The operating parameters have been reset to their default values.    
Operating Temp is below Operational Limit of xx C (yy C)     N     B     The cabinet (ambient) temperature has fallen 20 degrees below the flywheel cabinets operating temperature specification.    
Operating Temp is below xx C (yy C)     N     NC     The cabinet (ambient) temperature has fallen below the flywheel cabinets operating temperature specification.    
Operator Keyswitched Online     L     A, O     The indicated flywheel cabinet has been key-switched Online.    
Operator Keyswitched to Reset             The indicated flywheel cabinet has been key-switched to reset.    
Operator Keyswitched to Spin down     L     A     The indicated flywheel cabinet has been key-switched to Spin down.    
Password has Expired.     L     NC     The password that was entered via UPS View has timed-out.    
Possible Sensor Fault: "<channelName>".xx C     N     NC     There is a possible loose connection on the indicated sensor.    
Possible Sensor Fault: FWA: Armature Temp _._ C     N     NC     There is a possible loose connection on the indicated sensor.    
PS 1 has failed.     N, A     NC     Power Supply 1 (24 vdc) in the flywheel cabinet has a problem.    
Received: GPI Dlock     N     NC     The controller is communicating with the general-purpose interface circuit board. (GPI PWA)    
Restricted Op Params Defaulted     L     NC     The restricted operating parameters have been set to their default value via a command from UPSView.    
Reverse DC Bus Polarity.     A     B     The DC bus voltage has been detected to be the wrong polarity. Check the DC wiring.    
Spinning Down FWA/FWB from _ RPM     L     A     The flywheel is in the spin down state. The field coil currents are still providing unloaded but the flywheel will not discharge from this state.    
System Shutdown     A     A     The UPS has transitioned to Shutdown Mode either due to an internal fault or an EMO.    
Vacuum Disable timed out, enabling vacuum checking     L     NC     The flywheel vacuum checking has been enabled.    
Vacuum signal lost, check connections, and sender     N, A     A     There is a connection or transducer problem with the vacuum sensor.    
Verifying FWA/FWB signals and status     L     A     General startup message    
Warning cleared Vacuum Gauge at _._ mTorr     L     A     The flywheel (vacuum) pressure has decreased below the warning level.    
Warning Vacuum Gauge at _._ mTorr     L     A     The flywheel (vacuum) pressure has increased above the warning level.    

Caterpillar Information System:

UPS 1000S/ UPS 1200S Uninterruptible Power Supplys Graphical User Interface Messages
UPS 1000S/ UPS 1200S Uninterruptible Power Supplys UPS Messages
UPS 1000S/ UPS 1200S Uninterruptible Power Supplys Flywheel Operating Parameters
C9 Engine for Caterpillar Built Machines Vibration Damper and Pulley - Remove and Install
UPS 1000S/ UPS 1200S Uninterruptible Power Supplys Current Transformers (Primary, Secondary)
UPS 120, UPS 150, UPS 250, UPS 300, UPS 301, UPS 500, UPS 600, UPS 750 and UPS 900 Uninterruptible Power Supplies System Voltage - Calibrate
C9 Engine for Caterpillar Built Machines Flywheel Housing - Remove and Install
C11 and C13 Engines for Caterpillar Built Machines Inlet Manifold - Remove
C11 and C13 Engines for Caterpillar Built Machines Inlet Manifold - Install
UPS 1000S/ UPS 1200S Uninterruptible Power Supplys Transformer (T12 to T16 )
UPS 120, UPS 150, UPS 250, UPS 300, UPS 301, UPS 500, UPS 600, UPS 750 and UPS 900 Uninterruptible Power Supplies Controller Board Battery - Replace
SPF343 and SPF343C Trailer Mounted Pumpers Air Shutoff - Replace
UPS 1000S/ UPS 1200S Uninterruptible Power Supplys UPS View Commands and Hot Keys
UPS 1000S/ UPS 1200S Uninterruptible Power Supplys Fan (4 Wire Transformer Cabinet)
UPS 1000S/ UPS 1200S Uninterruptible Power Supplys External Source Sync PWA (4 Wire Transformer Cabinet)
TA19-M2WD and TA19-M4WD Agricultural Transmissions Transmission - Assemble
UPS 120, UPS 150, UPS 250, UPS 300, UPS 301, UPS 500, UPS 600, UPS 750 and UPS 900 Uninterruptible Power Supplies General Information (Cabinet Hardware)
UPS 120, UPS 150, UPS 250, UPS 300, UPS 301, UPS 500, UPS 600, UPS 750 and UPS 900 Uninterruptible Power Supplies Door
C280 Marine Auxiliary Engines System Overview
UPS 120, UPS 150, UPS 250, UPS 300, UPS 301, UPS 500, UPS 600, UPS 750 and UPS 900 Uninterruptible Power Supplies Door Pull and Retaining Ring
UPS 120, UPS 150, UPS 250, UPS 300, UPS 301, UPS 500, UPS 600, UPS 750 and UPS 900 Uninterruptible Power Supplies Door Latch
UPS 120, UPS 150, UPS 250, UPS 300, UPS 301, UPS 500, UPS 600, UPS 750 and UPS 900 Uninterruptible Power Supplies System Output Current - Calibrate
2006/05/22 Wiring for the Coolant Level Switches and the Coolant Level Sensors {7422}
UPS 1000S/ UPS 1200S Uninterruptible Power Supplys General Information (Maintenance Bypass Cabinet)