Probable Causes
- Fuel quality
- Unit injectors
- Valve lash
Recommended Actions
Fuel Quality
Check the fuel quality. Remove unsatisfactory fuel from the fuel tank. Refer to Operation and Maintenance Manual, "Fuel Tank Water and Sediment - Drain". Install new fuel filters. Refer to Operation and Maintenance Manual, "Fuel System Secondary Filter - Replace". Use the proper grade of clean fuel in the fuel tank.
Unit Injectors
- Check for correct installation of the J1/P1 and J2/P2 Electronic Control Module (ECM) connectors and the unit injector connectors. Refer to Troubleshooting, "Electrical Connectors - Inspect" for additional information.
- Perform the "Injector Solenoid Test" on the Cat ET in order to determine if all of the injector solenoids are being energized by the ECM.
- Perform the "Cylinder Cutout Test" on Cat ET in order to identify any injectors that might be misfiring. Refer to Troubleshooting, "Injector Solenoid Circuit - Test" for additional information.
Valve Lash
Refer to Systems Operation/Testing and Adjusting, "Engine Valve Lash - Inspect/Adjust".