UPS1000Z, UPS1200Z, UPS500G and UPS600G Uninterruptible Power Supplies Caterpillar


Power Distribution PWA (MMS System Cabinet)

Usage:

UPS 600G DLD

Description



Illustration 1g01273151
(1) Power distribution board

The power distribution board (PWD) (1) provides power for the system. The board (1) contains the fuses for power that is used throughout the system. The PWD provides power for the following:

  • 24 VDC power supply

  • 230 VAC for the input

  • 230 VAC for the output

Removal Procedure

Refer to Systems Operation, Testing and Adjusting, UENR3954, "Internal Component Preremoval Steps (MMS System Cabinet)" in order to shut down the system and gain access to internal components.



    Illustration 2g01273166
    Diagram for the power distribution board

  1. Disconnect all connectors. Refer to Illustration 2. Verify each labeling on the connector with the location of the wire. Verify each label on each connector.

  2. Disconnect the nine white plastic standoffs that connect the board (1) to the left panel.

    Note: The board (1) must be removed from the standoffs without bending the board (1).

Installation Procedure

  1. Position the board (1) in the cabinet over the nine white standoffs that are connected to the left panel.

  2. Push the board (1) onto all the standoffs simultaneously. Verify that all standoffs are locked in place.

  3. Connect the wire connectors into the correct connectors on the board (1). Check the labels on each connector for proper placement. Refer to Illustration 2.

Table 1
Fuse  Type 
PWD-F1  250 VAC, 3 A 
PWD-F2  250 VAC, 1 A 
PWD-F3  250 VAC, 2 A 
PWD-F4  250 VAC, 3 A 
PWD-F5  250 VAC, 3 A 
PWD-F6  250 VAC, 1 A 
PWD-F7  250 VAC, 2 A 
PWD-F8  250 VAC, 1 A 
PWD-F9  250 VAC, 1 A 
PWD-F10  250 VAC, 1 A 
PWD-F11  250 VAC, 3 A 
PWD-F12  250 VAC, 3 A 

Caterpillar Information System:

UPS1000Z, UPS1200Z, UPS500G and UPS600G Uninterruptible Power Supplies Parallel Cabinet Interface PWA
UPS1000Z, UPS1200Z, UPS500G and UPS600G Uninterruptible Power Supplies Parallel Cabinet Controller PWA
UPS1000Z, UPS1200Z, UPS500G and UPS600G Uninterruptible Power Supplies Fan Monitor PWA (MMS System Cabinet)
2013/03/22 A New Turbo Kit is Available for Certain 3500B Engines {1052, 1053}
UPS1000Z, UPS1200Z, UPS500G and UPS600G Uninterruptible Power Supplies EPO Reset Switch (MMS System Cabinet)
UPS1000Z, UPS1200Z, UPS500G and UPS600G Uninterruptible Power Supplies General Purpose Interface PWA (MMS System Cabinet)
UPS1000Z, UPS1200Z, UPS500G and UPS600G Uninterruptible Power Supplies Front Panel Display (MMS System Cabinet)
C7.1 Engines Rocker Shaft and Pushrod - Install
UPS1000Z, UPS1200Z, UPS500G and UPS600G Uninterruptible Power Supplies System Fuses (MMS System Cabinet)
C7.1 Engines Rocker Shaft - Disassemble
UPS1000Z, UPS1200Z, UPS500G and UPS600G Uninterruptible Power Supplies Internal Component Preremoval Steps (MMS System Cabinet)
C7.1 Engines Rocker Shaft - Assemble
UPS1000Z, UPS1200Z, UPS500G and UPS600G Uninterruptible Power Supplies AC Interface PWA (MMS System Cabinet)
C7.1 Engines Rocker Shaft and Pushrod - Remove
C7.1 Engines Turbocharger - Install - Turbocharger for Side Mounted Engines
C7.1 Engines Turbocharger - Remove - Turbocharger for Side Mounted Engines
C7.1 Engines Turbocharger - Install - Turbocharger for Top Mounted Engines
C7.1 Engines Turbocharger - Remove - Turbocharger for Top Mounted Engines
C7.1 Engines Valve Mechanism Cover - Remove and Install
C7.1 Engines Valve Mechanism Cover Base - Remove and Install
C7.1 Engines Vibration Damper and Pulley - Install
C7.1 Engines Vibration Damper and Pulley - Remove
C7.1 Engines Wastegate Solenoid - Remove and Install
C7.1 Engines Water Pump - Install
Back to top
The names Caterpillar, John Deere, JD, JCB, Hyundai or any other original equipment manufacturers are registered trademarks of the respective original equipment manufacturers. All names, descriptions, numbers and symbols are used for reference purposes only.
CH-Part.com is in no way associated with any of the manufacturers we have listed. All manufacturer's names and descriptions are for reference only.