Electronic Modular Control Panel II+ Paralleling (EMCP II+P) Caterpillar


Shutdown Mode

Usage:

C32 SXC
Shutdown mode prevents damage to the generator set when a shutdown fault is occurring. A shutdown fault is critical. When a shutdown fault occurs, the GSC+P automatically activates shutdown mode until the shutdown fault is corrected. The GSC+P shuts down the engine when the GSC+P is in shutdown mode. The GSC+P prevents starting of the engine and the GSC+P alerts the operator.

The GSC+P alerts the operator and the GSC+P identifies the shutdown fault by FLASHING the corresponding shutdown indicator. The name of the shutdown indicator identifies the shutdown fault.

Shutdown Indicators

  • Low oil pressure

  • Emergency stop

  • High water temperature

  • Engine overspeed

  • Engine overcrank

  • Fault shutdown

  • Spare 1, Spare 2, Spare 3 (that are accompanied by the fault shutdown indicator)

If the fault shutdown indicator is the only indicator FLASHING, additional information is available. A fault code is shown on the upper display which more precisely identifies the cause of the shutdown fault. Refer to System Operation, "Fault Description" for more information.

Shutdown Mode Sequence

  1. A shutdown fault occurs and the GSC+P detects the shutdown fault.

  1. On EUI engines, in order to shut off the fuel, the GSC+P deactivates the Electronic Governor Relay (EGR).

  1. In order to prevent the engine from starting, the GSC+P deactivates the Run Relay (RR), and the GSC+P deactivates the Starting Motor Relay (SMR).

  1. In order to remove the generator load, the GSC+P activates the Genset Fault Relay (GFR). This activates the optional circuit breaker shunt trip coil.

    Note: The spare output may also be programmed to activate when a shutdown occurs. This output can drive a relay in order to open the circuit breaker, or the output can open a transfer switch. Refer to System Operation, "Spare Input/Output Programming OP6".

  1. When engine speed reaches 0 rpm, the GSC+P deactivates the Crank Termination Relay (CTR). The Electronic Governor Relay (EGR) is deactivated when the engine oil pressure reaches the setpoint P014 for low oil pressure shutdown at idle speed 70 kPa (10 psi).

  1. The GSC+P FLASHES the corresponding shutdown indicator. If the fault shutdown indicator is FLASHING, a fault code is shown on the upper display. Refer to Systems Operation, "Fault Description".

  1. If the fault shutdown indicator is the only indicator FLASHING, additional information is available. A fault code is shown on the upper display that better identifies the cause of the shutdown fault. Refer to the Systems Operation, "Fault Description".

  1. The lower display continues to show the engine data.

  1. The relay status indicators show.

    • K2 (GFR)

    • K6 (ASR) will show for 15 seconds for an emergency stop fault, engine overspeed fault, or an speed sensor fault. K6 (ASR) will also show if engine speed does not decrease at least 100 rpm.

    • K7 (FCR) - (ETS fuel systems) for 70 seconds after engine speed decreases to 40 rpm and oil pressure decreases to 80 kPa (12 psi). (K7 is not shown for ETR fuel systems.)

Engine Start Sequence (After Shutdown)

  1. Correct the shutdown fault. Refer to the System Operation, "Fault Identification".

  1. Turning the Engine Control Switch (ECS) to the OFF/RESET position resets the GSC+P. If no shutdown fault is active, the GSC+P returns to normal mode and the engine is able to start.

Caterpillar Information System:

3516C Generator Set Engine Cat Data Link - Test
C175-16 Locomotive Engine Connecting Rod and Main Bearing Journals - Type 1
Electronic Modular Control Panel II+ Paralleling (EMCP II+P) Alarm Mode
Electronic Modular Control Panel II+ Paralleling (EMCP II+P) Modes Of Operation
C7 Petroleum Engine Diagnostic Flash Code Retrieval
G3600 Engines Speed/Timing - Test
Problem with Monitoring of the Turbocharger Inlet Temperature for some G3500 A3 Engines{1052, 1408, 7610, 7620} Problem with Monitoring of the Turbocharger Inlet Temperature for some G3500 A3 Engines{1052, 1408, 7610, 7620}
3516C Generator Set Engine CAN Data Link - Test
C9 Petroleum Engines Aftercooler - Install
Electronic Modular Control Panel II+ Paralleling (EMCP II+P) Sensors
14L Motor Grader Machine Systems Wheel Mounting - AWD
Troubleshooting Acceleration Issues on Caterpillar On-highway Truck Engines That Are Equipped with Automatic Transmissions {1000, 3030} Troubleshooting Acceleration Issues on Caterpillar On-highway Truck Engines That Are Equipped with Automatic Transmissions {1000, 3030}
Electronic Modular Control Panel II+ Paralleling (EMCP II+P) Paralleling Mode
3516C Generator Set Engine Coolant Level - Test
Electronic Modular Control Panel II+ Paralleling (EMCP II+P) Service Mode
C9 Petroleum Engines Turbocharger - Remove
Electronic Modular Control Panel II+ Paralleling (EMCP II+P) Fault Log Viewing OP1
3500B Engines for Caterpillar Built Power Modules with the ADEM 3 Electronic Control Module Direct Fuel Control Mode - Test
Electronic Modular Control Panel II+ Paralleling (EMCP II+P) Engine/Generator Setpoint Viewing OP2-0
Electronic Modular Control Panel II+ Paralleling (EMCP II+P) Protective Relaying Setpoint Viewing OP2-1
Electronic Modular Control Panel II+ Paralleling (EMCP II+P) AC Factory Calibration Setpoint Viewing OP2-2
3516C Generator Set Engine Electrical Power Supply - Test
Electronic Modular Control Panel II+ Paralleling (EMCP II+P) Password Entry OP3
Electronic Modular Control Panel II+ Paralleling (EMCP II+P) Fault Log Clearing OP4
Back to top
The names Caterpillar, John Deere, JD, JCB, Hyundai or any other original equipment manufacturers are registered trademarks of the respective original equipment manufacturers. All names, descriptions, numbers and symbols are used for reference purposes only.
CH-Part.com is in no way associated with any of the manufacturers we have listed. All manufacturer's names and descriptions are for reference only.