Note: If the parameters that are protected with the factory passwords are changed, the Caterpillar warranty may be voided.
Engine Serial Number
The engine serial number should be programmed to match the engine information plate. The serial number is not programmed on a new ECM.
ECM and Personality Module Interlock
Each personality module has a designated interlock code. On a new ECM, the personality module interlock is automatically programmed into the ECM. If a personality module with a different interlock code is installed, injection duration will be disabled and the engine will not start. If the customer has purchased a new personality module, the ECM interlock can be reset with the service tool. If the ECM is installed on a different application, the ECM interlock can be reset with the service tool. A factory password is required to change this parameter.
Equipment ID
This parameter allows the owner to identify the generator set.
Rated Fuel Position
This parameter is used to set engine power. A Factory Password is required to change this setting.
Minimum     | Default     | Maximum     |
Minimum Rack     | Engine Dependent     | Engine Dependent     |
Crank Duration
The crank duration determines when the starting motors will be energized. The crank duration determines when the starting motors will be disengaged. Programming this parameter to 0 will prevent the ECM from engaging the starting motors.
Minimum     | Default     | Maximum     |
0 seconds     | 10 seconds     | 120 seconds     |
Cranking Cycles
This parameter is the total number of crank cycles that can be performed.
Minimum     | Default     | Maximum     |
0     | 5     | 10     |
Crank Terminate Speed
This parameter determines when the starting motor will disengage.
Minimum     | Default     | Maximum     |
100 rpm     | 400 rpm     | 500 rpm     |
Fuel Correction Factor
The amount of fuel that is consumed by the engine is based on a map of the engine speed and the amount of rack. This parameter can be changed by the customer.
Total Hours
The total amount of engine hours can be programmed by the customer. A factory password is required to change this parameter.
Total Fuel
The ECM total fuel consumption can be programmed. A factory password is required to change this parameter.