Screen For Metering
Illustration 1 | g00854931 |
Screen for "METERING" (1) Button for "METER LOADING" (2) Button for "VOLTS" (3) Button for "AMPS" |
Note: The screen for the 480 Volt Diesel model is shown.
The screen for "METERING" displays switchgear electrical parameters. All phases of voltage and current can be displayed by the use of the button for "VOLTS" (2) or the button for "AMPS" (3). Touch these buttons in order to change to the next phase.
Illustration 2 | g00854932 |
Screen for "METER LOADING" (4) Button for "RETURN" (5) Button for "BASE LOAD SETPOINT" (6) Button for the load share module ("LSM") (7) Button for transduced watts |
Note: The screen for the 480 Volt gas model is shown in illustration 2.
The screen for "METER LOADING" will be displayed when the button for "METER LOADING" (1) is touched. The screen for "METER LOADING" illustrates the action of the controller in base load operation. The base load stability is displayed on this screen. These measurements are represented as both a numeric display and as a bar graph: transduced watts, base load setpoint and the load share module's reference voltage.
The user can navigate back to the screen for "METERING" by touching the button for "RETURN" (4) .