3606, 3608, 3612 and 3616 Engines and C280-12, C280-16, C280-6 and C280-8 Marine Engines Generator Monitoring System Caterpillar


Central Processing Unit Cannot Find Active Nodes

Usage:

3616 1PD

Test Procedure

System Operation

The SLC 5/04 - 5/05 indicators are located on the front of the following components: Power Supply, CPU and I/O Modules.

The diagnostic indicators help trace the source of the fault. Faults can be found in the following components: input devices, output devices, wiring and the controller.

The green "DH+" LED is flashing. There are no active nodes on the network.

The red "DH+" LED is flashing. There are duplicate active nodes on the link with the same address.

The red "FLT" LED is flashing during operation. The processor detects a major fault. The fault is in the processor expansion chassis or the fault is in the memory.




Illustration 1g00563551

Diagram of the LED indicators




Illustration 2g00562937

Central Processing Unit for typical system

Functional Test

  1. Check the electrical connectors and check the wiring.

      ------ WARNING! ------

      Bodily contact with electrical potential can cause bodily injury or death.

      To avoid the possibility of injury or death, ensure that the main power supply has been disconnected before performing any maintenance or removing any modules.

      ----------------------

    1. Disconnect the power supply.

    1. Check the electrical connectors and check the wiring for damage or bad connections.

    1. Verify that all modules are properly seated.

    1. Verify the status of the LED on the SLC 5/04 - 5/05.

      The results of the preceding procedure are in the following list:

      • All of the components are fully installed. All of the components are free of corrosion. All of the components are free of damage. All of the modules are properly seated. Proceed to 2.

      • The components are not fully installed. The components are not free of corrosion. The components are damaged. All of the modules are not properly seated. Repair the component. Verify that the repair resolves the problem. STOP.

  1. Check the communication parameters of the customer supplied devices.

    1. Check the communication parameter of the programmer.

      The results of the preceding procedure are in the following list:

      • The programmer address and the processor address are different. Proceed to 3.

      • The programmer address and the processor address are not different. Set the addresses. Verify that the repair resolves the problem. Stop.

  1. Change the baud rate.

    1. Change the baud rate of the programmer and change the baud rate of the processor.

    1. Increase the maximum node address.

      Note: The default baud rate is 57,600. The default node address is one.

      The results of the preceding procedure are in the following list:

      • No errors are displayed on the LED indicators. Stop.

      • Errors are displayed on the LED indicators. Proceed to 4.

  1. Check line voltage.

    1. Measure the line voltage at the terminals.

    1. Verify the voltage of the power supply. The power supply voltage should be measured between 21.0 VDC and 28.0 VDC.

      The results of the preceding procedure are in the following list:

      • The line voltage is in the range. Replace the processor. Verify that the repair solves the problem. Refer to Maintenance Procedure, "Processor - Replace".

      • The line voltage is out of the range. Refer to Troubleshooting, "System Power". Stop.

Caterpillar Information System:

3606, 3608, 3612 and 3616 Engines and C280-12, C280-16, C280-6 and C280-8 Marine Engines Generator Monitoring System Low Battery Power
3606, 3608, 3612 and 3616 Engines and C280-12, C280-16, C280-6 and C280-8 Marine Engines Generator Monitoring System Central Processing Unit Major Fault
Marine Monitoring System II Central Processing Unit Communications Error
3606, 3608, 3612 and 3616 Engines and C280-12, C280-16, C280-6 and C280-8 Marine Engines Generator Monitoring System Central Processing Unit Fault
Marine Monitoring System II System Power
C-10, C-12, C-15 and C-16 Industrial Engines Battery
UPS 250, UPS 300, UPS 301, UPS 500, UPS 600, UPS 750 and UPS 900 Uninterruptible Power Supplies Acronyms
Installation Instructions for Turbochargers {1052} Installation Instructions for Turbochargers {1052}
G3516B and G3520B Generator Set Engines Flywheel Housing - Install
G3516B and G3520B Generator Set Engines Flywheel Housing - Remove
3054, 3054B and 3056 Marine Engines Installation Guide Engine Control
C7 Engines for Combat and Tactical Vehicles Cruise Control Switch Circuit - Test
3126B and 3126E On-highway Engines Rear Power Take-Off (RPTO) - Remove
Marine Monitoring System II Central Processing Unit Fatal Error
3126B and 3126E On-highway Engines Rear Power Take-Off (RPTO) - Install
3606, 3608, 3612 and 3616 Engines and C280-12, C280-16, C280-6 and C280-8 Marine Engines Generator Monitoring System System Inoperable
UPS 250, UPS 300, UPS 301, UPS 500, UPS 600, UPS 750 and UPS 900 Uninterruptible Power Supplies System Description
Marine Monitoring System II Reference Parts Information
UPS 300, UPS 301, UPS 500, UPS 600, UPS 750 and UPS 900 Uninterruptible Power Supplies Model View Illustrations
G3304 and G3306 Engines Coolant Level Sensor
2000/12/01 Engine Troubleshooting Guides Are Available For Gas Engines {1000}
3126B Industrial Engine Fuel Filter and Water Separator
3054, 3054B and 3056 Marine Engines Fuel Shutoff Solenoid - Remove and Install - Bosch and Delphi Fuel Injection Pumps
2000/12/01 A New Integral Seal Is Being Used In The Water Lines Groups {1380}
Back to top
The names Caterpillar, John Deere, JD, JCB, Hyundai or any other original equipment manufacturers are registered trademarks of the respective original equipment manufacturers. All names, descriptions, numbers and symbols are used for reference purposes only.
CH-Part.com is in no way associated with any of the manufacturers we have listed. All manufacturer's names and descriptions are for reference only.