Digital Voltage Regulator Caterpillar


Electrical

Usage:

SR4B 1BN

Table 1
Specifications 
Regulation  0.25% from no load to full load 
Regulator temperature drift  Less than 0.5% for any 40 °C (72 °F) change over the ambient operating temperature range. 
Configurable Volts/Hz characteristic  Two slope ranges adjustable from 1 to 10 V/Hz. See the Regulation Characteristic Illustration. 
Regulator response time  Maximum of 10 milliseconds. 
Regulator sensing  True RMS 3-phase sensing is standard. Single phase sensing is available. Variable sense range: 90 to 600 volts. 
Regulator stability  The regulator responds to the fundamental component of the sensed voltage and remains stable for total harmonic distortion of the generator output voltage waveform, up to 20%. 
Telephone influence factor (TIF)  Less than 50. Complies with MIL STD 461C Part 9 and VDE 0875 level N. 
Fine voltage adjust range  ± 10% of regulator sensing voltage. 
Regulator voltage gain (Line loss compensation)  Adjustable from 0 to 10%. 
Fault detection and identification  Diagnostics identify operation outside of programmed limits. Specific fault information is available even after the unit has been powered down. 
Regulator start-up voltage  Meets ISO8325-3 class G2 specifications. 
Harmonic tolerance  The digital voltage regulator maintains precise control of the generator output with up to 20% harmonic distortion in the generator output voltage. 
Reactive droop adjustment  Adjustable from 0 to 10%. 
Overexcitation protection  Shuts off generator output when excitation current exceeds normal operating currents for 15 seconds or instantaneous shutoff if output is shorted. 
Ambient operating temperature  −40 °C (−40 °F) to +70 °C (+ 158 °F)
Storage temperature range  −40 °C (−40 °F) to +85 °C (+ 185 °F)
Power dissipation  5 watts at idle, 55 watts at rated output. 
Shock  Withstands up to 20 g's. 
Vibration  Withstands 4.5 g's at frequencies between 18 and 2000 Hz in three mutually perpendicular planes. 
Salt spray  Meets MIL-STD-810C, method 509.1. 
Sealing  Withstands up to 35 kPa (5.08 psi)
Weight  5 kg (11 lb)
Electromagnetic compatibility  Meets 89/336/EEC Electromagnetic Compatibility Directive. 
Power supply  24 ± 6 volt DC power supply required (0.5 amp). 


Illustration 1g00538141
Regulation Characteristic Illustration

Table 2
Summary of Operating Parameters
For the 120 Volt PM and SE Generators 
Power Input  70-120
3 Ø 
 
Freq. Hz 50-240 
VA 1500 
Output Rating  Max. Continuous  48 
A 12 
Min. Forcing 84 
A 21 
Sensing  79 to 124   
Max. VA
Burden per Ø
Reactive Droop Input  Max. Voltage 
Max. VA
Burden
Exciter Field Resistance  Min. Ohms 
Max. Ohms 10 

Table 3
Summary of Operating Parameters
For the 240 Volt PM and SE Generators 
Power Input  70-120
3 Ø 
 
Freq. Hz 50-240 
VA 1500 
Output Rating  Max. Continuous  48 
A 12 
Min. Forcing 84 
A 21 
Sensing  125 to 249   
Max. VA
Burden per Ø
Reactive Droop Input  Max. Voltage 
Max. VA
Burden
Exciter Field Resistance  Min. Ohms 
Max. Ohms 10 

Table 4
Summary of Operating Parameters
For the 480 Volt PM and SE Generators 
Power Input  70-120
3 Ø 
 
Freq. Hz 50 to 240 
VA 1500 
Output Rating  Max. Continuous  48 
A 12 
Min. Forcing 84 
A 21 
Sensing  250 to 600   
Max. VA
Burden per Ø
Reactive Droop Input  Max. Voltage 
Max. VA
Burden
Exciter Field Resistance  Min. Ohms 
Max. Ohms 10 

Note: Permanent Magnet (PM) Generator

Note: Self-Excited (SE) Generator

Caterpillar Information System:

Digital Voltage Regulator Display and Keypad
Digital Voltage Regulator Dimensions
325B Excavator Machine Systems Main Control Valve - Remove
Digital Voltage Regulator Customer Options
5230 Excavator Hydraulic System Cooler (Pump Drive Lubrication)
320B Excavator Hydraulic System Pilot Hydraulic System
5110B Excavator, 24H Motor Grader, 69D, 769D, 773D, 773E, 776D and 777D Off-Highway Truck/Tractors, 771D, 775D and 775E Quarry Trucks and AD40 Series II, AD45 and AE40 II Underground Articulated Trucks Caterpillar Monitoring System Quad Gauge Module
3046 Engine For Caterpillar Built Machines Crankshaft Main Bearings - Remove
CR3 Crusher and S3 Shear General Information
320B Excavator Hydraulic System Main Control Valve
325B Excavator Machine Systems Relief Valve (Pilot) - Remove and Install
315B L, 317B L and 317B LN Excavators Attachment Hydraulic System Combined Function Hydraulic Operation - Pilot Lines
Digital Voltage Regulator Fault Classifications
Digital Voltage Regulator Fault Codes
Digital Voltage Regulator Fault Handling for Earlier Digital Voltage Regulators
Digital Voltage Regulator Fault Handling
Digital Voltage Regulator General Information
Digital Voltage Regulator General Information
Digital Voltage Regulator Loading and Stopping Profile
Digital Voltage Regulator Parameter Viewing and Configuring Procedure
Digital Voltage Regulator Parameters
Digital Voltage Regulator Remote Communication
Cat® Digital Voltage Regulator Service Tools
Cat® Digital Voltage Regulator Startup Procedure
Back to top
The names Caterpillar, John Deere, JD, JCB, Hyundai or any other original equipment manufacturers are registered trademarks of the respective original equipment manufacturers. All names, descriptions, numbers and symbols are used for reference purposes only.
CH-Part.com is in no way associated with any of the manufacturers we have listed. All manufacturer's names and descriptions are for reference only.