Digital Voltage Regulator Caterpillar


Display and Keypad

Usage:

SR4B 1BN


Illustration 1g00538863
Display And Keypad
(1) Display
(2) Keypad
(3) Function key
(4) Scroll down key
(5) Scroll up key

Note: For a list of parameter codes and the corresponding range of values, see System Operation, "Parameters".

Display (1) and keypad (2) are used to select and manipulate parameter values that control the operation of the digital voltage regulator. Display (1) of the digital voltage regulator has four digits. A colon in the display indicates that the number showing is a parameter code. If a colon is not present, then the number showing is a parameter value. A decimal point in the display is used to indicate the precision of the parameter value.

Keypad (2) has three keys. The keys are listed below.

  • Function key (3)

  • Scroll down key (4)

  • Scroll up key (5)

Display (1) has two modes, parameter code mode and parameter value mode. Function key (3) is used to toggle back and forth between the two modes. Scroll down key (4) and scroll up key (5) are used to decrease and increase the parameter number or value number that is showing on display (1).

Table 1
Parameter Code  Parameter Value 
:01  0480 
0481
0482
0483
:02  0001 
0002
0003
0004
:03  0004 
0003
0002
:04  0100 
0099
0100
0101

The operation of display (1) and keypad (2) can be described as a table. Pressing function key (3) toggles the display back and forth between the two columns of the table (parameter code and parameter value). If a colon is present, the display is in parameter code mode. If a colon is not present, the display is in parameter value mode.

Pressing a scroll up key (5) or scroll down key (4) will increase or decrease the display to the next number within a column. Use of the scroll keys cannot cause the display to change columns of the table.

In order to configure a parameter code (change the value), follow the procedure below.

  1. Select the desired parameter code by pressing scroll key (4) or (5).

  2. Access the parameter value by pressing function key (3).

  3. Select the desired parameter value by pressing scroll key (4) or (5).

  4. Enter the chosen value into the memory of the digital voltage regulator by pressing function key (3).

Example



Illustration 2g00538864
Example Illustration - Display Shows Parameter Code Of :01
(1) Display
(2) Keypad
(3) Function key
(4) Scroll down key
(5) Scroll up key

This example is a demonstration of scrolling and selection of parameter codes. Also the scrolling and configuration of values is demonstrated.

After the digital voltage regulator is powered up (battery voltage applied) parameter code ":01" is shown on the display. The engine does not have to be running for the digital voltage regulator to show parameter codes. The colon indicates that a parameter code is being shown.

The user has the option of pressing function key (3), scroll down key (4), or scroll up key (5).

If scroll up key (5) is pressed, the display moves (scrolls) up to the next parameter code, ":02". Again, the colon is on. This is the entry point for parameter code :02.

Then, if scroll down key (4) is pressed, the display moves (scrolls) down to the preceding parameter code, ":01" again.

If scroll down key (4) is pressed again, the display moves (scrolls) to the highest parameter code, ":96".

Note: When scroll key (4) or (5) is held down for more than five seconds, the display will scroll rapidly. Otherwise, the display changes at the rate of one parameter per second.



Illustration 3g00538865
Example Illustration - Display Shows Value Of "0480"

Note: The value of some parameter codes is only for viewing by the user. Such parameters cannot be configured. See System Operation, "Parameters". View the value. Then, press function key (3) in order to return the display to showing parameter codes.

If function key (3) is pressed, the display changes to show the value "0480" of parameter code :01. Notice that the colon is off. The value of parameter code :01 can now be changed (configured).

If scroll up key (5) is pressed, the display moves (scrolls) up to the next value, "0481". The colon remains off.

Then if scroll down key (4) is pressed, the display moves (scrolls) down to the preceding value, "0480" again.

To enter (configure) a new value for a parameter code, scroll the display until the desired new value is showing, then press function key (3). Now, the new value is entered into the memory of the digital voltage regulator. The display returns to showing the parameter codes.

Caterpillar Information System:

Digital Voltage Regulator Dimensions
325B Excavator Machine Systems Main Control Valve - Remove
Digital Voltage Regulator Customer Options
5230 Excavator Hydraulic System Cooler (Pump Drive Lubrication)
320B Excavator Hydraulic System Pilot Hydraulic System
5110B Excavator, 24H Motor Grader, 69D, 769D, 773D, 773E, 776D and 777D Off-Highway Truck/Tractors, 771D, 775D and 775E Quarry Trucks and AD40 Series II, AD45 and AE40 II Underground Articulated Trucks Caterpillar Monitoring System Quad Gauge Module
3046 Engine For Caterpillar Built Machines Crankshaft Main Bearings - Remove
CR3 Crusher and S3 Shear General Information
320B Excavator Hydraulic System Main Control Valve
325B Excavator Machine Systems Relief Valve (Pilot) - Remove and Install
315B L, 317B L and 317B LN Excavators Attachment Hydraulic System Combined Function Hydraulic Operation - Pilot Lines
3304B and 3306B Engines for Caterpillar Built Machines Exhaust Manifold - Remove and Install
Digital Voltage Regulator Electrical
Digital Voltage Regulator Fault Classifications
Digital Voltage Regulator Fault Codes
Digital Voltage Regulator Fault Handling for Earlier Digital Voltage Regulators
Digital Voltage Regulator Fault Handling
Digital Voltage Regulator General Information
Digital Voltage Regulator General Information
Digital Voltage Regulator Loading and Stopping Profile
Digital Voltage Regulator Parameter Viewing and Configuring Procedure