3126B Industrial Engine Caterpillar


Monitoring System

Usage:

3126B BEJ

------ WARNING! ------

If the Shutdown mode has been selected and the warning indicator activates, engine shutdown may take as little as 20 seconds from the time the warning indicator is activated. Depending on the application, special precautions should be taken to avoid personal injury. The engine can be restarted following shutdown for emergency maneuvers, if necessary.



NOTICE

The Engine Monitoring System is not a guarantee against catastrophic failures. Programmed delays and derate schedules are designed to minimize false alarms and provide time for the operator to stop the engine.


The following parameters are monitored:

  • Coolant temperature

  • Oil pressure

  • Inlet manifold air temperature (if equipped)

  • Cooling system level (if equipped)

  • Fuel temperature

  • Fuel pressure (if equipped)

Programmable Options and Systems Operation

------ WARNING! ------

If the Warning/Derate/Shutdown mode has been selected and the warning indicator activates, bring the engine to a stop whenever possible. Depending on the application, special precautions should be taken to avoid personal injruy.


The engine can be programmed to the following modes:

  • "OFF"

  • "Warning"

  • "Warning/Derate"

  • "Warning/Derate/Shutdown"

"Warning"

The "DIAGNOSTIC" lamp and the warning signal (red lamp or buzzer) turn "ON" and the warning signal is activated continuously in order to alert the operator that one or more of the engine parameters is not within normal operating range.

"Warning/Derate"

The "DIAGNOSTIC" lamp turns "ON" and the warning signal (red lamp or buzzer) is activated. After the warning, the engine power will be derated. The warning lamp will begin to flash when the derating occurs.

When the engine is fully derated, the engine power is limited to 120 kW (160 hp). During a low oil pressure condition, the engine can be limited to 1350 rpm.

"Warning/Derate/Shutdown"

The "DIAGNOSTIC" lamp turns "ON" and the warning signal (red lamp or buzzer) is activated. After the warning, the engine power will be derated. The engine will continue to derate rpm until a shutdown of the engine occurs. The engine can be restarted after a shutdown for use in an emergency.

A shutdown of the engine may occur in as little as 20 seconds. The engine can be restarted after a shutdown for use in an emergency. However, the cause of the initial shutdown may still exist. The engine may shut down again in as little as 20 seconds.

If there is a signal for coolant loss, there will be a 10 second delay in order to verify the condition. The system will derate the engine power for 40 seconds before the engine will shut down if the engine has been programmed to shut down.

If there is a signal for low oil pressure or for coolant temperature, there will be a two second delay in order to verify the condition. The system will derate the engine power for 30 seconds before the engine will shut down if the engine has been programmed to shutdown.

For more information or assistance for repairs, consult your Caterpillar dealer.

Note: The Customer Specified Parameters may be secured by customer passwords. The engine may have all of the parameters that are programmed or any combination of the parameters that are programmed. Refer to the Operation and Maintenance Manual, "Customer Specified Parameters" for more information on the programmed parameters of the engine. Refer to the Electronic Troubleshooting for more information.

Caterpillar Information System:

3500B Marine Engines Rotation Enable Circuit
3126B Marine Engine Inlet Air Temperature Sensor
3126B Engine for Caterpillar Built Machines Coolant Temperature Sensor
3176C and 3196 Engines for Caterpillar Built Machines Fuel Temperature Sensor - If Equipped
3500B Marine Engines Digital Sensor Supply
3500B Marine Engines Analog Sensor Supply
3512B Petroleum Engines with the ADEM 2 Electronic Control Module MID 036 - CID 0827 - FMI 04 Left Exhaust Temperature short to ground
3512B Petroleum Engines with the ADEM 2 Electronic Control Module MID 036 - CID 0827 - FMI 03 Left Exhaust Temperature open/short to +batt
3500B Marine Engines MID 036 - CID 0650 - FMI 02 Harness Code Unknown
3500B and 3500B High Displacement Generator Set Engines MID 036 - CID 0542 - FMI 02 Unfiltered Engine Oil Pressure misinstalled
3500B and 3500B High Displacement Generator Set Engines MID 036 - CID 0444 - FMI 05 Start Relay open circuit
3003, 3013, 3014 and 3024 Engines for Caterpillar Built Machines Housing (Front) - Install
3500B Marine Engines CAT Data Link
3612 and 3616 Engines Engine Lifting Bracket - Remove and Install
3114, 3116 and 3126 Industrial, Marine and Generator Set Engines Fuel Shutoff Solenoid
3612 and 3616 Engines Engine Support - Remove and Install
3500B Marine Engines System Overview
C27 PET GEN SET Electric Power Generation and C27 KNOCKDOWN K Petroleum Power Train Package Fuel Conservation Practices
3500B Marine Engines Throttle Position Sensor
Electronic Modular Control Panel II (EMCP II) For MUI Engines Service Record
Electronic Modular Control Panel II (EMCP II) For PEEC Engines Engine/Generator Programming OP5
3500B Marine Engines Engine Speed/Timing Sensor
Electronic Modular Control Panel II (EMCP II) For PEEC Engines Spare Input/Output Programming OP6
Electronic Modular Control Panel II (EMCP II) For PEEC Engines Troubleshooting Diagnostic Codes
Back to top
The names Caterpillar, John Deere, JD, JCB, Hyundai or any other original equipment manufacturers are registered trademarks of the respective original equipment manufacturers. All names, descriptions, numbers and symbols are used for reference purposes only.
CH-Part.com is in no way associated with any of the manufacturers we have listed. All manufacturer's names and descriptions are for reference only.