Generator Set Control Panel for Switchgear Conversion Caterpillar


Indicator for Spare Fault - Troubleshoot

Usage:

3412C 4BZ
The control board provides one spare fault input (Contact 12). Devices from the factory or a device that is provided from the customer can be connected to the spare fault input. Some of the optional factory devices that can be connected to the spare fault input are listed below.

  • Engine Coolant Loss Sensor

  • Over/Under Voltage Relay

  • Ground Fault Relay

  • Low Fuel Level Switch

  • High Fuel Level Switch

A battery negative signal ("B-") at the spare fault input causes the control board to respond in a preselected manner (alarm or shutdown). The spare fault input is found at Contact 12 of the control board. For the spare fault, the Fault Protection Timer (FPT) is selectable. For more information, see Systems Operation, "Fault Management".

In order to troubleshoot the spare fault indicator, use a process that is similar to the preceding procedures for fault indicators.

  1. Check for obvious causes that are related to the responsible device.

  1. Check the function of the responsible device. Reset the fault by opening the Remote Start Switch and verify that the fault still exists.

  1. Disconnect the responsible device from the wiring of the generator set. Verify whether the fault still exists.

  1. Check for an unwanted short to the battery negative terminal at Contact 12 of the control board.

Caterpillar Information System:

Generator Set Control Panel for Switchgear Conversion Indicator for Low Coolant Level - Troubleshoot
Generator Set Control Panel for Switchgear Conversion Indicator for Emergency Stop - Troubleshoot
Generator Set Control Panel for Switchgear Conversion Indicator for Engine Overspeed - Troubleshoot
Generator Set Control Panel for Switchgear Conversion Indicator for Low Oil Pressure - Troubleshoot
3054 and 3056 Industrial and Generator Set Engines Piston Cooling Jet
Generator Set Control Panel for Switchgear Conversion Indicator for High Water Temperature - Troubleshoot
3054 and 3056 Industrial and Generator Set Engines Cylinder Block
SR4 HV and SR4B HV Generators Rotating Rectifier - Test
3054 Engine for Caterpillar Built Machines Crankshaft Main Bearings - Install
Control Console For CPS361 Pumper, Cement Instrument Panel
3054 and 3056 Industrial and Generator Set Engines Piston and Rings
Control Console For CPS361 Pumper, Cement Control Console
Generator Set Control Panel for Switchgear Conversion Troubleshooting Undiagnosed Problems
3406C (PEEC III) Truck Engines Air Inlet And Exhaust System
Generator Set Control Panel for Switchgear Conversion Engaged Starting Motor - Troubleshoot
3608 Engine Cooling System Coolant Analysis (ELC) (Level II) - Obtain
3408E and 3412E Engines for Caterpillar Built Machines Housing (Front) - Remove
Generator Set Control Panel for Switchgear Conversion No Engine Shutdown - Troubleshoot
3408E and 3412E Engines for Caterpillar Built Machines Housing (Front) - Install
3054 and 3056 Industrial and Generator Set Engines Exhaust Manifold
Generator Set Control Panel for Switchgear Conversion Electrical Connector - Inspect
Generator Set Control Panel for Switchgear Conversion Speed Sensor (Engine) - Adjust
Generator Set Control Panel for Switchgear Conversion Fault Protection Timer - Adjust
3054 and 3056 Industrial and Generator Set Engines Inlet Manifold
Back to top
The names Caterpillar, John Deere, JD, JCB, Hyundai or any other original equipment manufacturers are registered trademarks of the respective original equipment manufacturers. All names, descriptions, numbers and symbols are used for reference purposes only.
CH-Part.com is in no way associated with any of the manufacturers we have listed. All manufacturer's names and descriptions are for reference only.