SR 4 AND SRCR GENERATORS - OPERATION & MAINTENANCE Caterpillar


Circulating Currents

Usage:

When two units are paralleled there will be circulating currents. These currents are not doing useful work, but are flowing between the generators. By determining the total generator amperage and subtracting the amperage going to the load, the amount of circulating current can be determined.

Circulating currents are caused by voltage differences between the two units.

With cold generator sets, circulating current may be as high as 25% of rated amperes, without being considered harmful. Circulating current is part of the total generator current and this total must not exceed the amperage rating.

As the generators warm, the circulating currents will decrease. The ammeter readings should decrease slightly, but the voltage meter readings should remain constant.

Caterpillar Information System:

SR 4 AND SRCR GENERATORS - OPERATION & MAINTENANCE Load Division-(Speed Droop)
SR 4 AND SRCR GENERATORS - OPERATION & MAINTENANCE Parallel Operation
SR 4 AND SRCR GENERATORS - OPERATION & MAINTENANCE Single Unit Operation
SR 4 AND SRCR GENERATORS - OPERATION & MAINTENANCE Oilfield Generator
SR 4 AND SRCR GENERATORS - OPERATION & MAINTENANCE Generator Set Control Panel (If Equipped)
SR 4 AND SRCR GENERATORS - OPERATION & MAINTENANCE Generator Set Control Panel (If Equipped)
SR 4 AND SRCR GENERATORS - OPERATION & MAINTENANCE Generator Set Control Panel (If Equipped)
SR 4 AND SRCR GENERATORS - OPERATION & MAINTENANCE Generator Performance
SR 4 AND SRCR GENERATORS - OPERATION & MAINTENANCE Voltage Connections
SR 4 AND SRCR GENERATORS - OPERATION & MAINTENANCE Neutral Connections
SR 4 AND SRCR GENERATORS - OPERATION & MAINTENANCE Generator Lead Connections
SR 4 AND SRCR GENERATORS - OPERATION & MAINTENANCE Generator Identification
SR 4 AND SRCR GENERATORS - OPERATION & MAINTENANCE Parallel Operation of Governors
SR 4 AND SRCR GENERATORS - OPERATION & MAINTENANCE Parallel Operation of Governors
SR 4 AND SRCR GENERATORS - OPERATION & MAINTENANCE Electronic (2301) Governor
SR 4 AND SRCR GENERATORS - OPERATION & MAINTENANCE Stopping
SR 4 AND SRCR GENERATORS - OPERATION & MAINTENANCE Standby Electric Sets
SR 4 AND SRCR GENERATORS - OPERATION & MAINTENANCE Generator Storage
SR 4 AND SRCR GENERATORS - OPERATION & MAINTENANCE Generator Lubrication and Maintenance
SR 4 AND SRCR GENERATORS - OPERATION & MAINTENANCE Generator Lubrication and Maintenance
SR 4 AND SRCR GENERATORS - OPERATION & MAINTENANCE Generator Lubrication and Maintenance
SUPPLEMENT TO OPERATION & MAINTENANCE INSTRUCTIONS FOR MACHINES POWERED Introduction
SUPPLEMENT TO OPERATION & MAINTENANCE INSTRUCTIONS FOR MACHINES POWERED Starting the Engine
SUPPLEMENT TO OPERATION & MAINTENANCE INSTRUCTIONS FOR MACHINES POWERED When Required
Back to top
The names Caterpillar, John Deere, JD, JCB, Hyundai or any other original equipment manufacturers are registered trademarks of the respective original equipment manufacturers. All names, descriptions, numbers and symbols are used for reference purposes only.
CH-Part.com is in no way associated with any of the manufacturers we have listed. All manufacturer's names and descriptions are for reference only.