Default Settings for Cat Digital Voltage Regulator
Cat DVR Default Settings
Show/hide table
Parameter     | XQ1000     | XQ2000     | XQ1250G     | ||||
---|---|---|---|---|---|---|---|
208V, 60Hz | 240V, 60Hz     | 400V, 50Hz     | 480V, 60Hz     | 400V, 50Hz     | 480V, 60Hz     | 480V, 50Hz     | |
Configure     | |||||||
Rated Generator Voltage     | 208 V     | 240 V     | 400 V     | 480 V     | 400 V     | 480 V     | 480 V     |
Rated Generator Current     | 3001 A     | 3007 A     | 1804 A     | 1503 A     | 2598 A     | 3007 A     | 1880 A     |
Rated Generator Frequency     | 60 Hz     | 60 Hz     | 50 Hz     | 60 Hz     | 50 Hz     | 60 Hz     | 60 Hz     |
Generator PT Primary Voltage Rating     | 208 V     | 240 V     | 400 V     | 480 V     | 400 V     | 480 V     | 480 V     |
Generator PT Secondary Voltage Rating     | 208 V     | 240 V     | 400 V     | 480 V     | 400 V     | 480 V     | 480 V     |
Generator CT Primary Current Rating     | 3000 A     | 3000 A     | 3000 A (1)     | 3000 A (1)     | 3000 A     | 3000 A     | 3000 A     |
Power Input Frequency     | 240 Hz     | 240 Hz     | 200 Hz     | 240 Hz     | 200 Hz     | 240 Hz     | 240 Hz     |
Sensing Mode     | Three Phase     | Three Phase     | Three Phase     | Three Phase     | Three Phase     | Three Phase     | Three Phase     |
Show/hide table
( 1 ) | XQ1000 without a link board will have 1600:5 CTs |
Show/hide table
Parameter     | XQ1000     | XQ2000     | XQ1250G     | ||||
---|---|---|---|---|---|---|---|
208V, 60Hz | 240V, 60Hz     | 400V, 50Hz     | 480V, 60Hz     | 400V, 50Hz     | 480V, 60Hz     | 480V, 50Hz     | |
Set Points     | |||||||
AVR Voltage (V)     | 208 V     | 240 V     | 400 V     | 480 V     | 400 V     | 480 V     | 480 V     |
VAR (% of Rated)     | 5 %     | 5 %     | 5 %     | 5 %     | 5 %     | 5 %     | 5 %     |
Power Factor     | .95     | .95     | .95     | .95     | .95     | .95     | .95     |
AVR Voltage Control Desired Input Configuration (0 is CAN Input, 1 is Switch)     |
1     | 1     | 1     | 1     | 1     | 1     | 1     |
VAR/PF Control Desired Input Configuration (0 is CAN Input, 1 is Switch)     |
1     | 1     | 1     | 1     | 1     | 1     | 1     |
Load Compensation Mode (0=Off, 1=Droop, 2=Line Drop)     |
0     | 0     | 0     | 0     | 0     | 0     | 0     |
Load Compensation Mode Set point (%) Droop Percentage     |
3%     | 3%     | 3%     | 3%     | 3%     | 3%     | 3%     |
Voltage Adjustment Band Limit (% of rated)     |
15%     | 15%     | 15%     | 15%     | 15%     | 15%     | 15%     |
Show/hide table
Parameter     | XQ1000     | XQ2000     | XQ1250G     | ||||
---|---|---|---|---|---|---|---|
208V, 60Hz | 240V, 60Hz     | 400V, 50Hz     | 480V, 60Hz     | 400V, 50Hz     | 480V, 60Hz     | 480V, 50Hz     | |
Start Up     | |||||||
Soft Start Bias     | 10.00%     | 10.00%     | 10.00%     | 10.00%     | 10.00%     | 10.00%     | 10.00%     |
Soft Start Time     | 5.00 s     | 5.00 s     | 5.00 s     | 5.00 s     | 5.00 s     | 5.00 s     | 5.00 s     |
Knee Frequency     | 59.80 Hz     | 59.80 Hz     | 49.80 Hz     | 59.80 Hz     | 49.80 Hz     | 59.80 Hz     | 59.80 Hz     |
Decreasing Slope 1     | 2.00 V/Hz     | 2.00 V/Hz     | 2.00 V/Hz     | 2.00 V/Hz     | 2.00 V/Hz     | 2.00 V/Hz     | 2.00 V/Hz     |
Decreasing Slope 2     | 2.00 V/Hz     | 2.00 V/Hz     | 2.00 V/Hz     | 2.00 V/Hz     | 2.00 V/Hz     | 2.00 V/Hz     | 2.00 V/Hz     |
Minimum Voltage     | 50.00%     | 50.00%     | 50.00%     | 50.00%     | 50.00%     | 50.00%     | 50.00%     |
Minimum Frequency     | 33.00 Hz     | 33.00 Hz     | 33.00 Hz     | 33.00 Hz     | 33.00 Hz     | 33.00 Hz     | 33.00 Hz     |
Show/hide table
Parameter     | XQ1000     | XQ2000     | XQ1250G     | ||||
---|---|---|---|---|---|---|---|
208V, 60Hz | 240V, 60Hz     | 400V, 50Hz     | 480V, 60Hz     | 400V, 50Hz     | 480V, 60Hz     | 480V, 50Hz     | |
Gain     | |||||||
Pre-defined PID Gains (1-20 or Custom)     |
21     | 21     | 21     | 21     | 21     | 21     | 21     |
AVR Proportional Gain Kp     | 200     | 200     | 200     | 200     | 200     | 200     | 200     |
AVR Integral Gain Ki     | 600     | 600     | 600     | 600     | 600     | 600     | 600     |
AVR Derivative Gain Kd     | 30     | 30     | 30     | 30     | 30     | 30     | 30     |
Noise Filter Time Constant Td     | 0     | 0     | 0     | 0     | 0     | 0     | 0     |
Loop Gain Kg     | 15     | 15     | 15     | 15     | 15     | 15     | 15     |
VAR Integral Gain Ki     | 5     | 5     | 5     | 5     | 5     | 5     | 5     |
VAR Loop Gain Kg     | 2.5     | 2.5     | 2.5     | 2.5     | 2.5     | 2.5     | 2.5     |
PF Integral Gain Ki     | 5     | 5     | 5     | 5     | 5     | 5     | 5     |
PF Loop Gain Kg     | 3     | 3     | 3     | 3     | 3     | 3     | 3     |
Show/hide table
Parameter     | XQ1000     | XQ2000     | XQ1250G     | ||||
---|---|---|---|---|---|---|---|
208V, 60Hz | 240V, 60Hz     | 400V, 50Hz     | 480V, 60Hz     | 400V, 50Hz     | 480V, 60Hz     | 480V, 50Hz     | |
Protection     | |||||||
Shutdown Override Flag (0 is Disabled, 1 is Enabled)     |
0     | 0     | 0     | 0     | 0     | 0     | 0     |
Generator Overvoltage (0 is Disabled, 1 is Enabled)     |
1     | 1     | 1     | 1     | 1     | 1     | 1     |
Generator Overvoltage Fault Type (0 is Alarm, 1 is Shutdown)     |
0     | 0     | 0     | 0     | 0     | 0     | 0     |
Generator Overvoltage Trip Value     | 135%     | 135%     | 135%     | 135%     | 135%     | 135%     | 135%     |
Generator Overvoltage Time Delay     | 2.0 s     | 2.0 s     | 2.0 s     | 2.0 s     | 2.0 s     | 2.0 s     | 2.0 s     |
Reverse VAR (0 is Disabled, 1 is Enabled)     |
1     | 1     | 1     | 1     | 1     | 1     | 1     |
Reverse VAR Fault Type (0 is Alarm, 1is Shutdown)     |
1     | 1     | 1     | 1     | 1     | 1     | 1     |
Reverse VAR Trip Value (% of rated)     |
10%     | 10%     | 10%     | 10%     | 10%     | 10%     | 40%     |
Reverse VAR Time Delay     | 3 s     | 3 s     | 3 s     | 3 s     | 3 s     | 3 s     | 3 s     |
Generator Undervoltage (0 is Disabled, 1 is Enabled)     |
1     | 1     | 1     | 1     | 1     | 1     | 1     |
Generator Undervoltage Fault Type (0 is Alarm, 1 is Shutdown)     |
0     | 0     | 0     | 0     | 0     | 0     | 0     |
Generator Undervoltage Trip Value     | 60%     | 60%     | 60%     | 60%     | 60%     | 60%     | 60%     |
Generator Undervoltage Time Delay     | 30.0 s     | 30.0 s     | 30.0 s     | 30.0 s     | 30.0 s     | 30.0 s     | 30.0 s     |
Fault Reset Too Long (0 is Disabled, 1 is Enabled)     |
1     | 1     | 1     | 1     | 1     | 1     | 1     |
Fault Reset Too Long Fault Type (0 is Alarm, 1 is Shutdown)     |
0     | 0     | 0     | 0     | 0     | 0     | 0     |
Overexcitation Type (0 is Threshold, 1 is Inverse Time)     |
0     | 0     | 0     | 0     | 0     | 0     | 0     |
Overexcitation Trip Value     | 12.0 A     | 12.0 A     | 12.0 A     | 12.0 A     | 12.0 A     | 12.0 A     | 12.0 A     |
Overexcitation Time Setting     | 10     | 10     | 10     | 10     | 10     | 10     | 10     |
Exciter Diode Monitor Trip Value     | 2.0 A     | 2.0 A     | 2.0 A     | 2.0 A     | 2.0 A     | 2.0 A     | 2.0 A     |
Loss of Sensing Time Delay     | 2.0 s     | 2.0 s     | 2.0 s     | 2.0 s     | 2.0 s     | 2.0 s     | 2.0 s     |
Caterpillar Information System:
XQ Auto Paralleling Receiving Inspection
XQ Auto Paralleling Default Settings for Discrete Input/Output Module
XQ Auto Paralleling Storage
XQ Auto Paralleling Default Settings for Electronic Modular Control Panel
XQ Auto Paralleling Default Settings for Engine Electronic Control Module
XQ Auto Paralleling Default Settings for Generator Paralleling Control
XQ Auto Paralleling Default Settings for Mode of Operation
XQ Auto Paralleling Generator Load Connections
XQ Auto Paralleling Handling
XQ Auto Paralleling Installation
XQ Auto Paralleling Initial Startup Procedure
3516C Locomotive Engines Selective Catalytic Reduction Module - Disassemble
XQ Auto Paralleling Advanced Control Jumpers
XQ Auto Paralleling Power Module Controls - Check
G3306B Gas Engines Fuel Filter
C7.1 Industrial Engine Diagnostic Flash Code Retrieval
2010/09/01 Changes to the Usage and Cleaning of the Contamination Monitor Group {0645, 0680, 1280, 1348, 3080, 429F, 5095}
3500B and 3500C Marine Propulsion Engines E048 Backup ECM Took Control
C27 and C32 Engines for Caterpillar Built Machines Exhaust Cooler (NRS) - Remove and Install
2010/08/26 Service Tips for the Hydraulic Electronic Unit Injector HEUI Pump {1714}
C15 and C18 Engines Overhaul Considerations
C9.3 Industrial Engine and CX31-P600-C9I Petroleum Power Train Package Fuel System - Prime
2011/03/16 A New Cylinder Head Gasket and Spacer Plate Are Used for 3500 Machine Engines {1100, 1201, 7555}
C15 and C18 Engines Product Lifting