UPS 1000S/ UPS 1200S Uninterruptible Power Supplys Caterpillar


Bypass Pushbutton

Usage:

ES12F CZE
The pushbuttons that activate Maintenance Bypass Mode have the following functions and features:

  • return the load to the UPS

  • backlit by green bulbs that are replaceable




Illustration 1g01273093

Bypass Switch Location

(1) Transfer to Maintenance Bypass Pushbutton SW3

(2) Top Safety Panel

(3) Transfer from Maintenance Bypass Pushbutton SW4

(4) Bottom Safety Panel

The pushbuttons are located on the front of the bottom safety panel, behind the door of the Maintenance Bypass (MBP) cabinet. Refer to Illustration 1.




Illustration 2g01273094

Bypass Buttons

Pushbutton 3 (SW3), on the left, marked "Transfer To Maintenance Bypass" transfers the system to maintenance bypass. Refer to Illustration 2.

Pushbutton 4 (SW4) on the right, marked "Transfer From Maintenance Bypass" transfers the load back to the UPS. Refer to Illustration 2.

In each case, the pushbuttons are illuminated green only when the required set of conditions for transfer are met. Then, pressing and holding the appropriate button initiates the transfer. System status is displayed on the user interface panel on the Controls Cabinet. Refer to Systems Operation, Testing and Adjusting, RENR7654, "Front Panel Display".

Bulb Replacement




    Illustration 3g01273095

    Bypass Switch, Side View

    (5) Shield

    (6) Wire Assembly

    (7) Button, Rear Assembly

    (8) Button, Front Assembly

  1. Locate the pushbuttons and wire assembly.

    Refer to Illustration 1 and Illustration 7.




    Illustration 4g01273098

    Pushbutton Assembly, Front View

  1. Unlock the lever on the bottom of the wire assembly in order to disconnect the wire assembly from the button assembly.

    Refer to Illustration 4.




    Illustration 5g01273096

    Bulb and Wire Assembly

    (6) Wire Assembly

    (9) Bulb

  1. Detach the wire assembly from the rear button assembly and expose the bulb by pulling back on the wire assembly.

    Refer to Illustration 5.

  1. Remove the bulb by pressing the bulb in and turning the bulb counter-clockwise.



    Illustration 6g01273097

    230VAC Bulb

  1. Insert new 230VAC bulb in wire assembly by pressing the bulb in and turning the bulb clockwise.

  1. Attach the wire assembly to the rear button assembly and lock the assembly in place by moving the locking switch to the right.

    Refer to Illustration 4.

Pushbutton Removal

  1. Refer to the information in the Systems Operation, Testing and Adjusting, "Internal Component Preremoval Steps (Maintenance Bypass Cabinet)"in order to de-energize the system and gain access to internal components.

  1. Open the cabinet door. Locate the two green buttons.

  1. Remove the top metal safety panel in order to gain access to the rear of the buttons.



    Illustration 7g01273095

    Bypass Switch, Side View

    (5) Shield

    (6) Wire Assembly

    (7) Button, Rear Assembly

    (8) Button, Front Assembly

  1. Locate the wire assembly.

    Refer to Illustration 7.




    Illustration 8g01273098

    Pushbutton Assembly, Front View

  1. Unlock the lever on the bottom of the wire assembly in order to disconnect the wire assembly from the button assembly.

    Refer to Illustration 8.

  1. Pull back on the wire assembly in order to remove the wire assembly.

  1. Disconnect all six wires from the wiring assembly with the use of a screwdriver.

  1. Remove the rear button assembly from the safety panel by loosening the assembly. Pull back on the assembly.

  1. Squeeze the two small white tabs on the sides of the remaining button assembly. Slide the button out through the front of safety panel.

Pushbutton Installation

  1. Install the front button assembly into the safety panel by sliding the front button assembly through the front of the panel.

  1. Seat the rear portion of the button assembly to the front assembly. Tighten the rear portion of the button assembly down in order to hold the button to the door.



    Illustration 9g01273099

    Pushbutton Assembly, Rear View

  1. Attach all six wires to the wire assembly.

    The location is marked on each wire.

    Refer to Illustration 9.




    Illustration 10g01273098

    Pushbutton Assembly, Front View

  1. Attach the wire assembly to the rear button assembly. Lock the assembly in place by moving the locking switch to the right.

    Refer to Illustration 10.

Caterpillar Information System:

UPS 1000S/ UPS 1200S Uninterruptible Power Supplys System Fuse (Maintenance Bypass Cabinet)
UPS 1000S/ UPS 1200S Uninterruptible Power Supplys Internal Component Preremoval Steps (Maintenance Bypass Cabinet)
3408E and 3412E Industrial Engines Piston and Rings
3408E and 3412E Industrial Engines Piston and Rings
C7 and C9 On-highway Engines Engine Oil Level Gauge - Calibrate
UPS 120, UPS 150, UPS 250, UPS 300, UPS 301, UPS 500, UPS 600, UPS 750 and UPS 900 Uninterruptible Power Supplies Flywheel Telemetry - Calibrate
TA22-4WD Agricultural Transmission Breather (Transmission) - Clean
UPS 120, UPS 150, UPS 250, UPS 300, UPS 301, UPS 500, UPS 600, UPS 750 and UPS 900 Uninterruptible Power Supplies Flywheel Field Coil Current - Calibrate
2006/05/29 New Cylinder Head Groups are Used {1100}
C7 and C9 On-highway Engines Engine Oil and Filter - Change
UPS 1000S/ UPS 1200S Uninterruptible Power Supplys General Information (Maintenance Bypass Cabinet)
2006/05/22 Wiring for the Coolant Level Switches and the Coolant Level Sensors {7422}
C4.4 Industrial Engine Gear Group - Inspect
UPS Firmware Enhancement for Monitoring Bearing Serviceability{4480, 7551, 7620} UPS Firmware Enhancement for Monitoring Bearing Serviceability{4480, 7551, 7620}
C4.4 Industrial Engine Flywheel - Inspect
C13 and C15 On-highway Engines Data Link - Test
C4.4 Industrial Engine Flywheel Housing - Inspect
TA22-4WD Agricultural Transmission Lifting and Tying Down the Transmission
UPS 120, UPS 150, UPS 250, UPS 300, UPS 301, UPS 500, UPS 600, UPS 750 and UPS 900 Uninterruptible Power Supplies Rotor Position Sensor - Adjust
C15 and C18 Petroleum Generator Sets Fuel System Primary Filter (Water Separator) Element - Replace
UPS 120, UPS 150, UPS 250, UPS 300, UPS 301, UPS 500, UPS 600, UPS 750 and UPS 900 Uninterruptible Power Supplies System I/O PWA (MMS System Cabinet)
UPS 120, UPS 150, UPS 250, UPS 300, UPS 301, UPS 500, UPS 600, UPS 750 and UPS 900 Uninterruptible Power Supplies System I/O Daughter PWA (MMS System Cabinet)
UPS 120, UPS 150, UPS 250, UPS 300, UPS 301, UPS 500, UPS 600, UPS 750 and UPS 900 Uninterruptible Power Supplies Transformer (T1 to T3)
UPS 120, UPS 150, UPS 250, UPS 300, UPS 301, UPS 500, UPS 600, UPS 750 and UPS 900 Uninterruptible Power Supplies 24V Power Supply (MMS System Cabinet)
Back to top
The names Caterpillar, John Deere, JD, JCB, Hyundai or any other original equipment manufacturers are registered trademarks of the respective original equipment manufacturers. All names, descriptions, numbers and symbols are used for reference purposes only.
CH-Part.com is in no way associated with any of the manufacturers we have listed. All manufacturer's names and descriptions are for reference only.