Generator Set Start Module Caterpillar


Specifications

Usage:

UPS 250 APZ

Table 1
Electrical Specifications    
Nominal Voltage (Voltage Regulation)     24 DCV (+10%/-40%) at 0 - 1000 amperes DC    
Current Rating     1000 amperes    
Input Voltage     Up to 720 ACV (line to line)    
Output Fusing     1000 amperes    
Rated number of start attempts     5 cycles of 10 seconds each    

Table 2
Physical Dimensions    
Height     914.40 mm (36.0 inch)    
Depth    
309.88 mm (12.2 inch)    
Width    
609.6 mm (24 inch)    
Weight    
181.44 kg (400 lb)    
Distance from UPS     <
152.4 m (500 ft)    
Distance from engine starter     <
7.62 m (25 ft)    
3-phase AC line from UPS (not provided)     #6 AWG, 4 wire    
DC cables (not provided)     Use 3/0 cable minimum for 1% maximum loss at 1000 amperes    
Indoor installation     NEMA 1 construction    
Operating temperature    
-20 °C (-4.0 °F) to
50 °C (122.0 °F)    
Storage temperature    
-25 °C (-13.0 °F) to
70 °C (158.0 °F)    
Humidity     5% to 95% (non condensing)    

Table 3
Fuses    
Location     Quantity    
Generator Set Start Module, Bus Inductor Fuse "F9"     1    
Generator Set Start Module, Generator Set Start Filter (1)     2    
( 1 ) Used only on UPS 250 model.
Back to top