Digital Voltage Regulator Caterpillar


Fault Handling for Earlier Digital Voltage Regulators

Usage:

SR4B 1BN
The chart lists the serial number break between the earlier fault parameters and current fault parameters. All digital voltage regulator part numbers starting with 116 (116-XXXX) and some of the regulator part numbers starting with 130 (130-XXXX) use the earlier alarm/fault handling procedures. The current fault parameters/procedure is implemented on all versions of the digital voltage regulator built after March 1996. Another method to determine if a digital voltage regulator uses the current alarm/fault handling procedures is to check the PROM ID (parameter :91). A value of 1.03 or greater indicates use of the current alarm/fault parameters/procedures.

Table 1
Earlier Fault Parameter
Serial Number Break 
Regulator
Part Number 
Earlier Fault Parameter
Serial Number 
130-3471  LBNBA0001-0123 
130-3472  LBNBB0001-0301 
130-3473  LBNBC0001-0176 
130-3474  LBNBD0001-0190 
130-3475  LBNBE0001-0392 
130-3476  LBNBF0001-0238 
116-XXXX  All 

Fault Identification (For Earlier Digital Voltage Regulator)

  1. Check the excitation.

    1. Use a multimeter across the exciter field outputs F1 and F2. A multimeter should be set for VDC. Another way to verify that the regulator is providing excitation to the generator is by looking at parameter :55. Parameter :55 describes excitation current.

      Expected Result: The digital voltage regulator is providing the excitation to the generator.

      Results:

      • OK: Go to Step 2.

      • NOT OK: Go to Step 4.

  2. Check the status of the alarm.

    1. Check the display on the digital voltage regulator.

    2. Check the status of the alarm output.

      Expected Result: The display on the regulator is flashing or the alarm output is off (open circuit). When alarm output is off, an alarm is active.

      Results:

      • OK: Go to Testing And Adjusting, "Fault Handling For Earlier Digital Voltage Regulator", section Alarm Clearing (For Earlier Digital Voltage Regulator).

      • NOT OK: Go to Step 3.

  3. Check the alarm fault log.

    1. Check the status of the alarm fault log. The alarm fault log is described by parameter :95.

      Expected Result: The alarm fault log shows "0000".

      Results:

      • OK: The alarm fault log shows "0000". No new alarm has occurred. STOP.

      • NOT OK: Go to Testing And Adjusting, "Fault Handling For Earlier Digital Voltage Regulator", section Alarm Clearing (For Earlier Digital Voltage Regulator).

  4. Check the status of the fault.

    1. Check the display on the digital voltage regulator.

    2. Check the status of the fault output.

      Expected Result: The display on the regulator is flashing or the fault output is off (open circuit). When fault output is off, a fault is active.

      Results:

      • OK: A shutdown fault has occurred and is active. No new faults will be detected until active shutdown fault is reset. Go to Step 5.

      • NOT OK: Go to Testing And Adjusting, "Troubleshooting".

  5. Check the shutdown fault log.

    1. Check the number logged in the shutdown fault log. The shutdown fault log is described by parameter :92. Check the flashing number on the display.

      Expected Result: The number starts with a 7 (7xx).

      Results:

      • OK: The number starts with a 7 (7xx). A resettable fault has occurred. It can be reset without removing power by activating either shutdown fault reset, parameter :96 or the external fault reset switch. The fault can also be reset by cycling the power to 24 VDC power inputs ("B+"/"B-"). Note, that if the engine is running when the fault is reset the digital voltage regulator will provide excitation to the generator when the fault is reset. Go to Step 6.

      • NOT OK: Go to Step 7.

  6. Check the status of the shutdown fault reset.

    1. Select parameter :96 which describes shutdown fault reset. Depress the function key in order to reset the fault.

      Expected Result: Shutdown fault reset has been activated.

      Results:

      • OK: Shutdown fault reset has been activated. The fault output driver is reset and the unit is operational. The display continues to flash and the fault is still logged in the shutdown fault log, parameter :92. A flashing display indicates a fault in the shutdown fault log, parameter :92. New faults may be detected again. Go to Testing And Adjusting, "Fault Handling For Earlier Digital Voltage Regulator", section Fault Clearing (For Earlier Digital Voltage Regulator).

      • NOT OK: Shutdown fault reset has not been activated. Go to Step 5.

  7. Check the shutdown fault log.

    1. Check the number logged in the shutdown fault log. The shutdown fault log is described by parameter :92. Check the flashing number on the display.

      Expected Result: The number starts with an 8 (8xx).

      Results:

      • OK: The number starts with an 8 (8xx). A non-resettable fault has occurred. This fault is resettable only after removing all power to the digital voltage regulator, troubleshooting and correcting the problem, and reapplying the power. Go to Testing And Adjusting, "Fault Handling For Earlier Digital Voltage Regulator", section Fault Clearing (For Earlier Digital Voltage Regulator).

      • NOT OK: The number logged in the shutdown fault log, parameter :92 or flashing on the display starts with a 9 (9xx). A severe fault has occurred. The unit must be replaced. STOP.

Alarm Clearing (For Earlier Digital Voltage Regulator)

An alarm has occurred but the digital voltage regulator is still operational. No new alarms will be recorded until the present alarm is cleared. A 6xx number is flashing on the display and logged in the alarm fault log, parameter :95. Troubleshoot per the specific alarm description in service manual.

Note: If power is removed with an active fault, upon power-up the display will stop flashing. However, the fault will remain in the alarm fault log, parameter :95.

If you want to reset and clear the alarm, clear the alarm/fault by selecting parameter :94 on the display and pressing the function key. The digital voltage regulator screen should blank briefly, stop flashing and return to parameter :94. The Alarm Fault Log in parameter :95 should be cleared to "0000" and the alarm driver output should be reset. This also affects the values in parameters :92 and :93.

Fault Clearing (For Earlier Digital Voltage Regulator)

A shutdown fault has occurred. A 7xx or 8xx number is flashing on the display. A 7xx or 8xx number is logged in the shutdown fault log, parameter :92. Troubleshoot per the specific fault description.

Note: If power is removed with an active fault, upon power-up the display will stop flashing. However, the fault will remain in the shutdown fault log, parameter :92.

Reset a 7xx fault by selecting parameter :96 and depress the function key to reset the fault. Reset an 8xx fault by removing all power to the digital voltage regulator, troubleshooting and correcting the problem, and reapplying the power.

After the fault has been reset, clear the alarm/fault by selecting parameter code :94 on the display and pressing the function key. The digital voltage regulator screen should blank briefly, stop flashing and return to parameter :94.

The alarm/fault log in parameter :95 should be cleared to "0000". The fault value in parameter :92 is moved to parameter :93 and parameter :92 is cleared to "0000".

Note: In order to clear previous fault (parameter :93), select parameter :94 on the display and press the function key. Parameter :93 is cleared to "0000". Alarm log parameter :95 is also cleared to "0000" again.

Caterpillar Information System:

Digital Voltage Regulator Fault Codes
Digital Voltage Regulator Fault Classifications
Digital Voltage Regulator Electrical
Digital Voltage Regulator Display and Keypad
Digital Voltage Regulator Dimensions
834G Wheel Dozer and 836G Landfill Compactor Electrohydraulic System Hydraulic Tank
Digital Voltage Regulator Customer Options
69D and 769D Off-Highway Truck and 771D Quarry Truck Suspension Cylinder Suspension Cylinder (Rear) - Type 1
5110B Excavator, 24H Motor Grader, 69D, 769D, 773D, 773E, 776D and 777D Off-Highway Truck/Tractors, 771D, 775D and 775E Quarry Trucks and AD40 Series II, AD45 and AE40 II Underground Articulated Trucks Caterpillar Monitoring System Quad Gauge Module
824G Wheel Tractor, 825G Soil Compactor and 826G Landfill Compactor Hydraulic System Vane Pump (Implement)
3304B and 3306B Engines for Caterpillar Built Machines Exhaust Manifold - Remove and Install
5110B Excavator, 24H Motor Grader, 69D, 769D, 773D, 773E, 776D and 777D Off-Highway Truck/Tractors, 771D, 775D and 775E Quarry Trucks and AD40 Series II, AD45 and AE40 II Underground Articulated Trucks Caterpillar Monitoring System Resettable Load Count Mode
Digital Voltage Regulator Fault Handling
Digital Voltage Regulator General Information
Digital Voltage Regulator General Information
Digital Voltage Regulator Loading and Stopping Profile
PM-465 Cold Planer General Hazard Information
Digital Voltage Regulator Parameter Viewing and Configuring Procedure
Digital Voltage Regulator Parameters
Digital Voltage Regulator Remote Communication
Cat® Digital Voltage Regulator Service Tools
Cat® Digital Voltage Regulator Startup Procedure
Digital Voltage Regulator Startup Profile Function
826G Landfill Compactor, 825G Soil Compactor and 824G Wheel Dozer Power Train Cleaner Bar - Install
Back to top
The names Caterpillar, John Deere, JD, JCB, Hyundai or any other original equipment manufacturers are registered trademarks of the respective original equipment manufacturers. All names, descriptions, numbers and symbols are used for reference purposes only.
CH-Part.com is in no way associated with any of the manufacturers we have listed. All manufacturer's names and descriptions are for reference only.