C9.3 Marine Generator Set Engines Caterpillar


Electrical System

Usage:

C9.3 C93

Grounding Practices


NOTICE

Improper grounding can cause uncontrolled or unreliable circuit paths and electrical noise resulting in damage to the engine bearings, and other engine components.


Proper grounding of the unit and the engine electrical systems is necessary for proper performance and reliability.

Negative Battery Connection

All return paths to the negative battery must carry any likely fault currents.

The starter should be connected directly to the negative battery post. The alternator must be connected to the negative battery, bus bar, or negative side of the starting motor.

Negative Battery Connection for Multiple Engines



Illustration 1g01635383
Isolated components

If multiple bus bars are used to connect components to the negative battery, a common reference should be provided. All bus bars must be wired together for proper engine synchronization for multiple engine installations.

Welding on a Vessel that is Equipped with an Electronic Controlled Engine

Refer to the appropriate Troubleshooting Guide for more information about welding on a vessel that is equipped with an electronic controlled engine. Also refer to the appropriate Operation and Maintenance Manual for more information about welding.

Switched Positive Battery and Unswitched Positive Battery



Illustration 2g01264533

Note: All battery connections to the ECM must be utilized in order to prolong the service life of the ECM.

The electronic control system can operate on either a 12 V electrical system or a 24 V electrical system. The switched positive battery and the unswitched positive battery connections to the ECM are made at the P61 Customer connector.

The ECM receives electrical power through the input for the switched positive battery. Protection for this circuit must be rated at 15 Amp (12 V or 24 V system).

The input for the unswitched positive battery is used to power the ECM memory that contains maintenance information and certain logged diagnostics. Protection for the unswitched positive battery circuit is specified as 20 Amp.

Powering the electronic control system through dedicated circuits with circuit breakers reduces the possibility of performance problems of the electronic control system. This also minimizes the chance of an engine shutdown due to a short in the electrical system. Additional loads should not be connected between the ECM and the circuit protection for the ECM.

Note: Do not use in-line fuses for circuit protection. Caterpillar recommends the use of circuit breakers for circuit protection. Circuit breakers should be located with other devices for circuit protection in a centrally located, dedicated panel. If circuit breakers that automatically reset are used, consideration of the environment of the location of the breaker is critical and the effect on the trip point is critical. The trip point of some circuit breakers can be reduced below the rated trip point if the circuit breaker is exposed to high temperatures. This reduction can cause intermittent shutdowns that result with needless replacement of electronic components.

Suppression of Transient Voltage

The installation of transient suppression at the source of the transient is recommended. Refer to Illustration 4. Caterpillar follows a stringent electrical environment standard that is similar to SAE recommended practices.

The use of inductive devices such as relays and solenoids can result in the generation of transient voltage in electrical circuits. Transient voltage that is not suppressed can exceed SAE specifications and lead to the degradation of the performance of the electronic control system.



Illustration 3g01264857
Use of a diode in a relay as a transient voltage suppressor

The OEM should specify relays and solenoids with built-in voltage transient suppression. Refer to Illustration 3 for ways to minimize transient voltage from relays and solenoids without built-in voltage transient suppression. Techniques include the installation of a diode or resistor of the proper size in parallel with the solenoid or the relay coil. Other techniques may also be used.

Inductive devices such as relays or solenoids should be located as far as possible from the components of the electronic control system.

Wiring harnesses that are installed by the OEM should be routed as far as possible from the wiring harness of the electronic control system in order to avoid problems that are associated with electrical noise.

Examples of devices that require suppression of transient voltages include any device that switches inductive loads on and off. The following list provides examples of such devices:

  • Solenoids (trim tab solenoids, etc)

  • DC electric motors

  • Relays that use the same power and ground as the sensor

The following list provides other examples of situations that may cause transient voltages:

  • Improperly grounded electronic components

  • Improperly grounded cable shields

  • Improperly grounded antennas

  • Signal wires that are installed too closely to power wires

All of the components that are connected to the ECM must have return wires (ground) that are connected to the engine's − Battery. The return wires (ground) should be connected as close to the battery as possible. Caterpillar recommends the use of a separate return wire for each component. Each return wire (ground) should be attached to the engine's − Battery bus bar.

Caterpillar recommends the use of a 218-4935 Arc Suppressor on all inductive devices such as relays and solenoids. The 218-4935 Arc Suppressor is not polarized. This arc suppressor can be wired into the circuit without any concern for the direction of current flow.

Table 1
Required Parts 
Part Number  Description  Quantity 
218-4935  Arc Suppressor 
155-2270  Connecting Plug Kit (2-PIN) 
186-3736  Connector Socket 
130-5300(1)  Clip 
130-5301(1)  Clip 
(1) Optional mounting clips


Illustration 4g01093137
Typical wiring for 218-4935 Arc Suppressor

Engine Electrical System

The electrical system has two separate circuits:

  • Starting circuit

  • Low amperage circuit

Some of the electrical system components are used in more than one circuit. The following components are used in each of the three circuits:

  • Battery

  • Circuit breaker

  • Ammeter

  • Battery cables

The charging circuit is in operation when the engine is running. A voltage regulator in the circuit controls the electrical output in order to keep the battery at full charge.


NOTICE

The disconnect switch, if equipped, must be in the ON position in order to let the electrical system function. There will be damage to some of the charging circuit components if the engine is running with the disconnect switch in the OFF position.


If the engine has a disconnect switch, the starting circuit can operate only after the disconnect switch is put in the ON position.

The starting circuit is in operation only when the start switch is activated.

Both the low amperage circuit and the charging circuit are connected to the same side of the ammeter. The starting circuit is connected to the opposite side of the ammeter.

Starting System Components

Starting Solenoid

A solenoid is a magnetic switch that does two basic operations:

  • The solenoid closes the high current starting motor circuit with a low current start switch circuit.

  • The solenoid engages the electric starting motor pinion with the ring gear.


Illustration 5g00285112
Solenoid

The solenoid has windings (one set or two sets) around a hollow cylinder. The plunger can move forward and backward. When the start switch is closed and electricity is sent through the windings, a magnetic field is created. The magnetic field pulls the plunger forward in the cylinder. Pulling the plunger forward moves the shift lever in order to engage the pinion drive gear with the ring gear. The front end of the plunger then makes contact across the battery and the motor terminals of the solenoid. After the contact is made, the starting motor begins to turn the flywheel of the engine.

When the start switch is opened, current no longer flows through the windings. The spring now pushes the plunger back to the original position. At the same time, the spring moves the pinion gear away from the flywheel.

When two sets of solenoid windings are used, the windings are called the hold-in winding and the pull-in winding. Both sets of windings have the same number of turns around the cylinder, but the pull-in winding uses a wire with a larger diameter. The wire with a larger diameter produces a greater magnetic field. When the start switch is closed, part of the current flows from the battery through the hold-in windings. The rest of the current flows through the pull-in windings to the motor terminal. The current then flows through the motor to ground. The solenoid is fully activated when the connection across the battery and the motor terminal is complete. When the solenoid is fully activated, the current is shut off through the pull-in windings. Only the smaller hold-in windings are in operation. The hold-in windings operate for the duration of time that is required in order to start the engine. The solenoid will now draw less current from the battery, and the heat generated by the solenoid will be kept at an acceptable level.

Starting Motor



Illustration 6g01363366
Electric starting motor components
(1) Brush assembly
(2) Field windings
(3) Solenoid
(4) Clutch
(5) Pinion
(6) Armature

The starting motor is used to turn the engine flywheel at a rate that will allow the engine to start running.

Note: Some starting motors have ground straps that connect the starting motor to the frame. But, many of these starting motors are not grounded to the engine. These starting motors have electrical insulation systems. For this reason, the ground strap that connects the starting motor to the frame may not be an acceptable engine ground. Starting motors that were installed as original equipment are grounded to the engine. These starting motors have a ground wire from the starting motor to the negative terminal of the battery. When a starting motor must be changed, consult an authorized dealer for the proper grounding practices for that starting motor.

The starting motor has a solenoid. When the ignition switch is turned to the START position, the starting motor solenoid will be activated electrically. The solenoid plunger will now move a mechanical linkage. The mechanical linkage will push the pinion in order to engage with the flywheel ring gear. The pinion will engage with the ring gear before the electric contacts in the solenoid close the circuit between the battery and the starting motor. When the circuit between the battery and the starting motor is complete, the pinion will turn the engine flywheel. A clutch gives protection for the starting motor so that the engine cannot turn the starting motor too fast.

When the ignition switch is released from the START position, the starting motor solenoid is deactivated. The starting motor solenoid is deactivated when current no longer flows through the windings. The spring now pushes the plunger back to the original position of the plunger. At the same time, the spring moves the pinion gear away from the flywheel ring gear.

Caterpillar Information System:

794 AC Off-Highway Truck Field Assembly Muffler - Install
C9.3 Marine Generator Set Engines Basic Engine
Welding The 3600/C280 Caterpillar Engine And Two Bearing Generator To The Base{1152, 1152} Welding The 3600/C280 Caterpillar Engine And Two Bearing Generator To The Base{1152, 1152}
C9.3 Marine Generator Set Engines Cooling System
C9.3 Marine Generator Set Engines Lubrication System
C27 and C32 Tier 4 Final Engines for MD6250 Drill and MD6310 Drill Fuel Priming Pump
C27 and C32 Engines for Caterpillar Built Machines Fuel Filter Base
C15 and C18 Engines for Caterpillar Built Machines Fan Drive
C15 and C18 Tier 4 Final Engines Diesel Particulate Filter - Clean
C9.3 Marine Generator Set Engines Air Inlet and Exhaust System
Guide Springs and Valve Lifter Assemblies are Breaking in Certain C9 and C9.3 Engines{1108, 1209} Guide Springs and Valve Lifter Assemblies are Breaking in Certain C9 and C9.3 Engines{1108, 1209}
C32 Petroleum Class 1 / Division 2 Certified Hazardous Location Generator Set Maintenance Interval Schedule
C9.3 Marine Generator Set Engines Fuel System - Inspect
794 AC Off-Highway Truck Field Assembly Support Link (Platform) - Install
C9.3 Marine Generator Set Engines Finding Top Center Position for No. 1 Piston
C9.3 Marine Engine Fuel Filter Base - Remove and Install - Right-Hand Simplex
G3408 and G3412 Engines Coolant (NGEC) - Change
794 AC Off-Highway Truck Field Assembly Battery Box - Install
G3408 and G3412 Engines Maintenance Interval Schedule - Naturally Aspirated
G3408 and G3412 Engines Maintenance Interval Schedule - Turbocharged Aftercooled
G3408 and G3412 Engines Maintenance Interval Schedule - Standby
C9.3 Marine Engine Fuel Filter Base - Remove and Install - Right-Hand Duplex
G3500H 60Hz Generator Sets Additional Messages
PM620 and PM622 Cold Planer Air Compressor - Inspect
Back to top
The names Caterpillar, John Deere, JD, JCB, Hyundai or any other original equipment manufacturers are registered trademarks of the respective original equipment manufacturers. All names, descriptions, numbers and symbols are used for reference purposes only.
CH-Part.com is in no way associated with any of the manufacturers we have listed. All manufacturer's names and descriptions are for reference only.