During each key on event of at least two seconds, the Electronic Control Module (ECM) evaluates the signal voltage from each pressure sensor. The ECM compares each signal voltage to a reference voltage. The reference voltage that is used depends on the sensor.
If a signal voltage is close to the reference voltage, the ECM will internally adjust the signal voltage. The internal adjustment causes the pressure value for the sensor to be correct. This process is called automatic sensor calibration.
If a signal voltage is not close to the reference voltage, the ECM will not internally adjust the signal voltage. The ECM will set a fault code that indicates there is a problem with the signal voltage.
Table 1 indicates the maximum error that is permitted for each sensor, and the reference for that sensor. Refer to the troubleshooting procedure to determine the root cause of the incorrect signal voltage.
Diagnostic Trouble Codes | ||
J1939 Code | Code Description
(code descriptions may vary) |
Comments |
101-13 | Engine Crankcase Pressure : Out of Calibration | During key on, the signal voltage from the crankcase air pressure sensor indicated a crankcase air pressure greater than +/- There is not a reference sensor for this sensor |
411-13 | Engine Exhaust Gas Recirculation Differential Pressure : Out of Calibration | During key on, the signal voltage from the EGR differential pressure sensor indicated a differential pressure greater than +/- There is not a reference sensor for this sensor |
3251-13 | Aftertreatment #1 DPF Differential Pressure : Out of Calibration | During key on, the signal voltage from the diesel particulate filter #1 differential pressure sensor indicated a dpf differential pressure greater than +/- The 3251-13 will not activate for several hours if the ambient temperature is below There is not a reference sensor for this sensor |
3358-13 | Engine Exhaust Gas Recirculation Inlet Pressure : Out of Calibration | During key on, the signal voltage from the EGR intake pressure sensor indicated an EGR intake pressure greater than +/- Reference sensor : Atmospheric Pressure Sensor |
3563-13 | Engine Intake Manifold #1 Absolute Pressure : Out of Calibration | During key on, the signal voltage from the Intake Manifold pressure sensor indicated an Intake Manifold pressure greater than +/- Reference sensor : Atmospheric Pressure Sensor |
3609-13 | DPF #1 Intake Pressure : Out of Calibration | During key on, the signal voltage from the diesel particulate filter #1 intake pressure sensor indicated a dpf intake pressure greater than +/- Reference sensor : Atmospheric Pressure Sensor |
Troubleshooting Test Steps | Values | Results |
---|---|---|
1. Check for Diagnostic Trouble Codes The engine coolant temperature must be greater than A. Establish communication between Caterpillar Electronic Technician (ET) and the Electronic Control Module (ECM) . Refer to Troubleshooting, "Electronic Service Tools", if necessary. B. Download the "Warranty Report" from the engine ECM before performing any troubleshooting or clearing diagnostic trouble codes. C. Wait at least 30 seconds in order for the diagnostic codes to become active. Look for an active -13 code or for a logged -13 code. |
Diagnostic Trouble Codes |
Result: There is an active or there is a logged -13 code. Proceed to Test Step 2. |
2. Check for Debris A. Turn the keyswitch to the OFF position. B. Check the suspect sensor for debris. C. If applicable, check the reference sensor for debris. D. Check the sensor measurement port for blockage by debris. E. If debris is found, clear the debris from the measurement port and replace the suspect sensor. F. Turn the keyswitch to the ON position. G. Check for -13 codes. Wait at least 30 seconds in order for the diagnostic codes to become active. The 3251-13 will not activate for several hours if the ambient temperature is below |
Debris |
Result: The sensor measurement port is not blocked by debris. Proceed to Test Step 3. Result: A -13 code is not present, return the unit to service. Result: A -13 code is present, replace the suspect sensor. Verify that the problem is resolved. Result: If more than one -13 code is present and the codes have a reference sensor, replace the reference sensor. Verify that the problem is resolved. |
3. Inspect the Suspect Sensor Connector A. Turn the keyswitch to the OFF position. Inspect the suspect sensor connector for moisture and/or corrosion. |
Moisture |
Result: The suspect sensor connector has moisture and/or corrosion. Proceed to Test Step 4. Result: The suspect sensor connector does not have moisture and/or corrosion. Proceed to Test Step 5. |
4. Remove any moisture and/or corrosion A. Disconnect the suspect sensor connector. B. Remove any moisture and/or corrosion from the outside of the connector. Check for moisture and corrosion inside the connector. Verify that the seals for the wires are sealing correctly. Refer to Troubleshooting, "Electrical Connectors - Inspect", if necessary. C. If necessary, repair the connector or replace the connector. D. Reconnect the connector. Verify that the connection is secure. E. Turn the keyswitch to the ON position. F. Monitor the diagnostic codes on Cat ET. Check for -13 codes. Wait at least 30 seconds in order for the diagnostic codes to become active. The 3251-13 will not activate for several hours if the ambient temperature is below |
Moisture |
Result: A -13 code is not present, return the unit to service. Result: A -13 code is present, replace the suspect sensor. Verify that the problem is resolved. Result: If more than one -13 code is present and the codes have a reference sensor, replace the reference sensor. Verify that the problem is resolved. |
5. Check for Moisture and/or Corrosion in the Circuit A. Check all of the connectors in the circuit for moisture and/or corrosion. B. Check for corrosion inside the connector. Verify that the seals for the wires are sealing correctly. Refer to Troubleshooting, "Electrical Connectors - Inspect", if necessary. C. If necessary, repair the connector or replace the connector. D. Reconnect the connector. Verify that the connection is secure. E. Turn the keyswitch to the ON position. F. Monitor the diagnostic codes on Cat ET. Check for -13 codes. Wait at least 30 seconds in order for the diagnostic codes to become active. The 3251-13 will not activate for several hours if the ambient temperature is below |
Moisture |
Result: A -13 code is not present, return the unit to service. Result: A -13 code is present, replace the suspect sensor. Verify that the problem is resolved. Result: If more than one -13 code is present and the codes have a reference sensor, replace the reference sensor. Verify that the problem is resolved. |
Complete the procedure in the order in which the steps are listed.