Dimensions
Show/hide table
Illustration 1 | g00779068 |
Dimensions of the VR6 Voltage Regulator (A) (B) (C) (D) (E) |
Note: When the voltage regulator is used with a permanent magnet generator, ensure that the jumpers are removed between the following terminals: 20 - 28, 22 - 30 and 24 - 26. For regulators that were manufactured before June 2003, ensure that a jumper is installed between terminals 28 and "GND".
Show/hide table
Number of the Terminal | Description |
---|---|
GND | Ground |
2 | Auxiliary input from VAR/PF Controller |
3 | Auxiliary input from VAR/PF Controller |
4 | This terminal is used in conjunction with terminal 7 for selecting internal voltage adjustment. Place the jumper between terminals 4 and 7 for using internal voltage adjustment. Remote voltage adjustment requires a remote voltage adjust potentiometer between terminals 6A and 7. |
5 | 1 Ampere Current Transformer (CT) |
5A | 5 Ampere Current Transformer (CT) |
6 | Common for the Current Transformer |
6A | Common connection for selectable features |
7 | This terminal is used in conjunction with terminal 4 for selecting external voltage adjustment. Place the jumper between terminals 4 and 7 for using internal voltage adjustment. Remote voltage adjustment requires a remote voltage adjust potentiometer between terminals 6A and 7. |
8 | Connect terminal 8 to terminal 6A in order to select a 1 V/Hz underfrequency slope. |
9 | Connect terminal 9 to terminal 6A in order to select three-phase sensing. |
20 | Sensing input on phase C |
22 | Sensing input on phase A |
24 | Sensing input on phase B |
26 | Three-phase power input |
28 | Single-phase power input or three-phase power input |
30 | Single-phase power input or three-phase power input |
F1 | Positive field lead |
F2 | Negative field lead |
Show/hide table
NOTICE |
---|
Terminals 26, 28, and 30 are designed to be connected directly to a power source that is NOT switched. Either a permanent magnet or the generator's output is preferred so the voltage will gradually build. Connecting the terminals directly to a switched power source may cause damage to the regulator unless an inrush current reduction device is utilized. |
Show/hide table
Adjustment | Description |
---|---|
"DRP" | Adjustment of the Voltage Droop |
"FAC CAL" | This is the factory calibration of the voltage adjustment range. Adjustment by the customer is not required. |
"VLT ADJ" | Voltage Adjustment |
"UF" | Underfrequency Knee Adjustment |
"STB" | Stability Adjustment |
Caterpillar Information System:
3500B Marine Propulsion Engines Speed Sensor - Clean/Inspect
3054E and 3056E Industrial Engines and Engines for Caterpillar Built Machines CID 1684 FMI 10
VR6 Voltage Regulator Electrical
3054E and 3056E Industrial Engines and Engines for Caterpillar Built Machines CID 1684 FMI 09
3054E and 3056E Industrial Engines and Engines for Caterpillar Built Machines CID 1684 FMI 08
3054E and 3056E Industrial Engines and Engines for Caterpillar Built Machines CID 1684 FMI 07
3054E and 3056E Industrial Engines and Engines for Caterpillar Built Machines CID 1684 FMI 05
3054E and 3056E Industrial Engines and Engines for Caterpillar Built Machines CID 1684 FMI 04
3054E and 3056E Industrial Engines and Engines for Caterpillar Built Machines CID 1684 FMI 03
3054E and 3056E Industrial Engines and Engines for Caterpillar Built Machines CID 1684 FMI 02
C11 and C13 Industrial Engines Electric Starting Motor
3054E and 3056E Industrial Engines and Engines for Caterpillar Built Machines CID 1684 FMI 00
784C and 785C Off-Highway Truck/Tractors Rim - Inspect
3054E and 3056E Industrial Engines and Engines for Caterpillar Built Machines CID 1684 FMI 11
3054E and 3056E Industrial Engines and Engines for Caterpillar Built Machines CID 1684 FMI 12
3054E and 3056E Industrial Engines and Engines for Caterpillar Built Machines CID 1684 FMI 14
3054E and 3056E Industrial Engines and Engines for Caterpillar Built Machines CID 1743 FMI 02
3054E and 3056E Industrial Engines and Engines for Caterpillar Built Machines CID 1894 FMI 02
3054E and 3056E Industrial Engines and Engines for Caterpillar Built Machines CID 1895 FMI 02
3054E and 3056E Industrial Engines and Engines for Caterpillar Built Machines Event Codes
3054E and 3056E Industrial Engines and Engines for Caterpillar Built Machines E015 High Engine Coolant Temperature Derate
3054E and 3056E Industrial Engines and Engines for Caterpillar Built Machines E016 High Engine Coolant Temperature Shutdown
3054E and 3056E Industrial Engines and Engines for Caterpillar Built Machines E017 High Engine Coolant Temperature Warning
3054E and 3056E Industrial Engines and Engines for Caterpillar Built Machines E025 High Inlet Air Temperature Derate