The discrete input/output (I/O) module is not required.
The discrete input/output module is a device that can read 12 discrete inputs and operating eight relay outputs. The discrete input/output module can be mounted on the generator set package or mounted remotely in another location.
The discrete input/output module has 12 inputs with four return channels. The inputs can be activated by either switching to a return or by switching to battery negative. Each of the inputs can be configured to signal one of many possible events. The Caterpillar Service Tool is used in order to configure the discrete input/output module inputs.
Inputs that generate a warning message will reset automatically whenever the input returns to a non-active state. Inputs that generate a shutdown message will continue until the input returns to a non-active state and a reset message is received by the module on the J1939 data link.
The input configuration parameters are shown in Table 1.
Configuration Parameters for Each Input | ||
---|---|---|
Setpoint Parameter | Range | Default |
Input #inn Active State Configuration | Active Low
Active High |
Active State Low |
Input #nn Time Delay | 0 to 120 seconds | 0 |
Input #nn SPN | Any SPN (see Table 2 supported by EMCP 3 | N/A |
Input #nn FMI | Any FMI supported by EMCP 3 | N/A |
Table 2 lists the "Suspect Parameter Numbers" (SPN) that the EMCP 3 supports for inputs and outputs. An SPN is an internationally recognized code that is assigned a specific meaning. For example, SPN 110 relates to the "Engine Coolant Temperature".
EMCP 3 Supported Suspect Parameter Numbers | |||
---|---|---|---|
SPN | SPN Description | Input | Output |
38 | Fuel Level-Secondary Tank | X | X |
52 | Engine After Cooler Temperature | X | |
82 | Starting Air Pressure | X | |
94 | Fuel Pressure | X | |
95 | Fuel Filter Differential Pressure | X | |
96 | Fuel Level (Primary Tank) | X | X |
98 | Engine Oil Level | X | |
99 | Oil Filter Differential Pressure | X | |
100 | Engine Oil Pressure | X | |
101 | Crankcase Pressure | X | |
107 | Air Filter Differential Pressure | X | |
110 | Engine Coolant Temperature | X | |
111 | Engine Coolant Level | X | X |
137 | Extinguisher System Pressure | X | X |
167 | Battery Charging System Voltage | X | X |
168 | Battery Voltage | X | |
171 | Ambient Air Temperature | X | |
172 | Inlet Air Temperature | X | |
173 | Exhaust Temperature | X | |
174 | Fuel Temperature | X | |
175 | Engine Oil Temperature | X | |
190 | Engine Over Speed | X | |
612 | Generator Rotating Diode Failure | X | |
628 | Voltage Regulator Failure | X | |
970 | Emergency Stop Shutdown (1) | X | |
971 | Engine Derate Overridden | X | |
1084 | Generator Over excitation | X | X |
1122 | Generator Bearing Temperature #1 | X | |
1124 | Generator Winding Temperature #1 | X | |
1125 | Generator Winding Temperature #2 | X | |
1126 | Generator Winding Temperature #3 | X | |
1237 | Emergency Shutdown Override Mode Active Warning | X | X |
1239 | Ruptured Fuel Basin-Primary Tank | X | X |
1383 | Unexpected Engine Shutdown | x | |
1664 | Engine Failure to Start Shutdown | X | |
2433 | Right Exhaust Temperature | X | |
2434 | Left Exhaust Temperature | X | |
2436 | Generator Frequency | X | |
2440 | Generator Voltage | X | |
2448 | Generator AC Current | X | |
2452 | Generator Reverse Power (kW) | X | |
2456 | Generator Reactive Power (VAR) | X | |
2648 | Service Interval Warning | X | |
4000 | Air Shutoff Damper Close | X | X |
4001 | ATS in Normal Position | X | X |
4002 | ATS in Emergency Position | X | X |
4003 | Battery Charger Failure | X | X |
4004 | Generator Breaker Closed | X | X |
4005 | Utility Breaker Closed | X | X |
4006 | Engine in Cool Down | X | |
4007 | Generator Control Not in Auto | X | |
4028 | Earth Fault | X | X |
4029 | Earth Leakage | X | X |
User Defined Input #1 | Range
701-716 |
X | |
User Defined Input #2 | Range
701-716 |
X | |
User Defined Input #3 | Range
701-716 |
X | |
User Defined Input #4 | Range
701-716 |
X | |
User Defined Input #5 | Range
701-716 |
X | |
User Defined Input #6 | Range
701-716 |
X | |
User Defined Input #7 | Range
701-716 |
X | |
User Defined Input #8 | Range
701-716 |
X | |
User Defined Input #9 | Range
701-716 |
X | |
User Defined Input #10 | Range
701-716 |
X | |
User Defined Input #11 | Range
701-716 |
X | |
User Defined Input #12 | Range
701-716 |
X |
(1) | Input configured as "Emergency Stop Shutdown" (SPN 970) will not perform a shutdown when activated. Use only to create an event log message in the EMCP 3 if desired. |
The discrete I/O module has eight "Form C" relay outputs. Each output can be configured to signal one of many possible events. Each output can be configured for either general events or for specific events. The Cat ET Service Tool (CST) is used in order to configure the discrete I/O module outputs.
For general events, each output activates whenever any "Alarm Condition", "Shutdown Condition", or any combination of the two conditions exist.
For specific events, each output activates whenever the diagnostic message contains the SPN and Failure Mode Identifier (FMI) combination that matches the SPN and FMI combination that is programmed for that particular output.
The FMI defines the nature of the event, such as above range or below range. The FMI includes events such as high or low alarms, shutdowns, or condition exists.
The output configuration parameters are shown in table 3.
Configuration Parameters for Each Output | ||
---|---|---|
Set Point Parameter | Range | |
Output #nn SPN | Any SPN supported by EMCP 3 | |
Output #nn Trigger Condition | Disabled | |
Specific | Condition Exists
Open Circuit Diagnostic High Shutdown High Warning Low Shutdown Low Warning Warning or Shutdown Warning, Shutdown, or Short Circuit Diagnostic |
|
General | Open Circuit Diagnostic
Shutdown Warning Warning, Shutdown, or Short Circuit Diagnostic |
The discrete I/O module exhibits the following configuration behaviors.
- Maintains functionality with no loss in performance during single set point configuration
- Maintains functionality with no loss in performance while communicating on the data link
- Retains all configured values in non-volatile memory
- Configured on the secondary data link (CAN2) using the CST.
Table 4 lists the specifications for the input/output module.
Input/Output Module Specifications | |
---|---|
Nominal Voltage | 9 VDC to 32 VDC |
Operating Voltage Range | 12 VDC
24 VDC (external power supplies) |
Ambient Operating Temperature | -40 degrees Celsius to 70 degrees Celsius |
Output Relay Contact Ratings | 2A @120 VAC
2A @ 30 VDC 2A @ 277 VAC |