3606, 3608, 3612, 3616 and 3618 Engines and C280-12, C280-16, C280-6 and C280-8 Marine Engines Panel View Monitor Caterpillar


Diagnostic Indicator Is On - Troubleshoot

Usage:

3616 1FN

Terminal Messages

Status Messages - Status messages indicate that the terminal is performing an operation that may limit access to the terminal. The message will disappear when the terminal completes the operation or when the condition is satisfied.

Reminder Messages - Reminder messages indicate a minor fault or mistake. Reminder messages appear when an invalid operation is attempted. Pressing any button on the touchscreen will remove the message.

Warning Messages - Warning messages indicate that the operation may produce undesirable results. A warning message must be responded to as indicated in the message.

Fault Messages - Fault messages indicate that the terminal has detected a condition which will prevent further operation. The current application will halt. The terminal must be reset in order to recover from this type of error.

See the following table for information about individual terminal messages:

Table 1
Error Number     Terminal Messages     Type     Meaning     Recommended Action    
200-206, 300, 318-321, 328, 329, 331, 346, 347, 355, 356, 358, 367, 404, 411, 416, 417, 421-425, 447-449, 457, 459, 700, 1105, 1111, 1113, 1115, 1207-1211, 2002-2009, 2016, 2018, 2021, 2028 and 2029     A fault has occurred. Error = X     Minor Fault or Terminal Fault     A minor fault was detected that could impact terminal operation or a terminal fault was detected.     Press any key to recover from a minor fault. For terminal faults, contact technical support with the error code.    
208     Write to logic controller failed     Comm Status     Controller does not accept data from the terminal. Controller is not connected.     Check connections (on Remote I/O units). Verify that controller is in run mode and not busy. Verify that controller data files are not in use by other applications.    
303     Aborted.     Reminder / File Transfer Status     The terminal received an abort command during a file transfer.     Try again.    
304     File read access error     Reminder     Error reading the source file from a source device.     Try again. If problem continues, contact technical support.    
305     File write access error     Reminder     Error writing source file.     Try again. If problem continues, contact technical support.    
307     File not supported     Reminder / File Transfer Status     File is incompatible with the terminal's firmware.     Contact technical support to verify compatibility. File must be a .PVA file.    
308     Timeout     Reminder / File Transfer Status     The terminal was waiting for the partner device in a file transfer, but the terminal timed out before the data or expected reply was received.     Check cable connections or data corruption with noise on cable. Verify that the computer was not reset. Try again.    
309-311     Data corrupted. Verify file and retry.     Reminder / File Transfer Status     The data checksum failed in a file transfer.     Check electrical and cable connections. Try the file transfer again.    
312     Unknown device     Reminder / File Transfer Status     Verify the file type entered. Try again.     Destination or source device is invalid for a read or write application transfer.    
313     File too large     Reminder / File Transfer Status     Reduce application size. See Appendix A for terminal requirements. If copying to a card, check card space.     File too large to be transferred to the terminal. In a memory card transfer, the card does not have enough space.    
314     No Card Inserted     Reminder     Install a memory card and try again.     You tried to transfer data to/from a memory card but there is no card in the card slot.    
315     Unformatted card     Reminder     Memory card is unformatted, contains an unrecognizable format or is corrupt.     Reformat the card or replace it with a new card if corrupt. Try again.    
316     Write Protected Card     Reminder / File Transfer Status     A write command to the card failed because the card switch is in the protected mode.     Select write mode by changing the switch on the top edge of the card. Try again.    
317     File exists. Cannot overwrite     Reminder / File Transfer Status     See message 342. This message only occurs when the file cannot be renamed.     Change the file name or save to a new memory card.    
323     No application on PV terminal     Reminder / File Transfer Status     You tried to load an application on a memory card but there is no application in the terminal.     View the Terminal Info screen to see if an application is loaded in the terminal.    
324     Check card status     Reminder / File Transfer Status     Problem formatting the memory card.     Try a new memory card.    
325     Unformatted card     Reminder     Memory card is unformatted, contains an unrecognizable format or is corrupt.     Reformat the card or replace it with a new card. Try again.    
326     No Card Inserted     Reminder     You tried to transfer data to/from a memory card but there is no card in the card slot.     Install a memory card and try again.    
327     No files     Reminder     You tried to transfer a file from the memory card but there are no files on the card.     Use memory card containing application (.PVA) files.    
330     Write Protected Card     Reminder / File Transfer Status     A write command to the card failed because the card switch is in the protected mode.     Select write mode by changing the switch on the top edge of the card. Try again.    
332     No application on PV terminal     before removal.     You tried to load an application on a memory card but there is no application in the terminal.     View the Terminal Info screen to see if an application is loaded in the terminal.    
333     File in use - Request denied     Reminder     Attempt to format memory card containing a file used by the application. This usually occurs when an application requires a font file on the memory card.     Format the memory card on a computer or a PanelView terminal that does not have an application loaded.    
334     Unexpected card removal. Please disconnect card before removal.     Reminder / File Transfer Status     You removed the memory card during normal operation and did not press the Disconnect button on the Memory Card configuration screen.     Press the Disconnect Card button to close the files on the card. When prompted, remove the card from the slot and then re-insert the card. Enter Configuration Mode and press the Run Mode button.    
340     Format erases entire card: 0 - Abort, 1 - Continue     Warning     Operator pressed Erase / Format Card on the Memory Card configuration screen.     Enter appropriate response: 0 to abort, 1 to continue    
341     Proceed with download? 0 - Abort, 1 - Continue     Warning     You pressed, Restore From Card on the Memory Card configuration screen.     Enter appropriate response: 0 to abort, 1 to continue    
342     The PVA File exists. 0 - Abort, 1 - Upload with new PVA filename     Reminder / File Transfer Status     You pressed, Save To Card on the Memory Card configuration screen when the file exists on the card.     Enter appropriate response: 0 to abort, 1 to upload new PVA file.    
361     Value not in range     Reminder     Entered value is outside of valid range.     Enter a value within the valid range.    
364     Closing Files. ..     Status     Terminal is preparing for removal of memory card.     Wait for files to close before removing memory card.    
365     Remove card. ..     Reminder     You must remove the memory card for the terminal to continues operation.     Remove the memory card.    
366     Card disconnection will require card removal to continue operation.     Warning     Attempt to disconnect the memory card.     After memory card is disconnected it must be removed from card slot before the terminal will operate.    
392     File not supported     Reminder / File Transfer Status     File is incompatible with the terminal type.     In PanelBuilder32, select the Setup tab on the Application Settings dialog and select the correct terminal type.    
393     File not supported     Reminder / File Transfer Status     File is incompatible with the communication protocol of the terminal.     In PanelBuilder32, select the Setup tab on the Application Settings dialog and make sure the protocol matches your terminal.    
394     File not supported     Reminder / File Transfer Status     File is incompatible with the terminal's firmware.     In PanelBuilder32, click the Catalog & Revisions button on the Setup tab on the Application Settings dialog. Select a firmware version that matches your terminal.    
395     File not supported     Reminder / File Transfer Status     File is incompatible with the operator input type (keypad, touch or keypad and touch) of terminal.     In PanelBuilder32, select the Setup tab on the Application Settings dialog. Select the type of operator input that matches your terminal.    
396     File not supported     Reminder / File Transfer Status     File is incompatible with the terminal.     Download the file to the terminal again. If problem reoccurs, contact technical support.    
415     Retained memory lost. Presets were loaded.     Reminder     The battery backed memory was invalid during startup. The system defaulted to preset values instead of the last states.     No action necessary. Terminal reverts to defaults.    
436     Logic Controller has screen control     Reminder     You tried to change the application screen but it is configured for controller only access.     No action required, controller will change screens as programmed.    
634     Read Fail or Write Fail     Status     ControlLogix Tag or address does not exist or is the wrong data type. Designated slot does not contain a ControlLogix Processor.     Check tag address. Check for data type mismatch. Verify ControlLogix slot location.    
1109     Font file unavailable, Font error = ****     Minor Fault or Terminal Fault     You downloaded an application to the PanelView without the appropriate memory card (containing the font file) inserted in the card slot of the terminal.     From the Memory Card screen, press the Disconnect button to close the files on the card. Remove the card from the card slot. Locate the card containing the font file or copy the correct font file to a card. Insert the correct memory card in the card slot and enter Run mode.    
1110     No valid application     Reminder     You tried to run an application that has not been downloaded to the terminal.     Download application to terminal.    
1118     Access denied.     Status     Wrong password entered.     Enter a valid password.    
1119     Access denied.     Status     Password not recognized     Enter a valid password.    
1120     Security tampering.     Status     PVA file was corrupted - attempt to bypass security was detected     New application file must be downloaded to the terminal.    
1121     No operator selected.     Status     There is no currently selected operator, but a password change has been requested     Select the operator requiring the new password.    
1122     Password change is not allowed.     Reminder     Password is unchangeable     Password cannot be changed at the current level of security.    
1123     Password change is not allowed.     Reminder     Operator cannot change password     Current operator does not have access for password changes.    
1124     New password must be entered before it can be verified.     Reminder     New pass words must be entered twice.     Enter the new password again to verify that it was entered correctly.    
1125     New and verify passwords differ.     Status     The same password was not entered for verification.     Enter the same password for New and Verify.    
1126     Please verify new password.     Reminder     New pass words must be entered twice.     Enter the new password again.    
1127     Password changed     Reminder     Password change is effective.     You must use new password for security access.    
2005     Application file: Insufficient RAM     Terminal Fault     Application file may be too large.     Try again. If possible, reduce the size of the application.    
2007 - 2010     Application file contains errors     Terminal Fault     Application contains incompatible data.     Check application and try again.    
2011     Retained memory lost. Presets were loaded.     Reminder     The battery backed memory was invalid during startup. The system defaulted to preset values instead of the last states.     No action necessary. Terminal reverts to defaults.    
2012     Application file: Too many retained memory devices     Terminal Fault     The battery-backed RAM is too full to hold all devices requiring presets.     Reduce the number of control objects. Use global objects.    
2014     Hardware configuration is corrupted     Terminal Fault     The terminal hardware configuration is corrupt.     Contact technical support.    
2030, 2031     Hardware and firmware do not match     Terminal Fault     A mismatch exists between the terminal firmware and the terminal hardware.     Verify that the series and revision markings on the back of the terminal are compatible with the firmware.    

EtherNet/IP Codes

The messages that are shown on the following table will appear on the terminal screen as "DC Error=xx". If an alert is displayed that is not listed in the table, contact technical support.

Table 2
Error Number     Terminal Messages     Type     Meaning     Recommended Action    
xx,xx,xx Number depends on hardware fault detected.     Communication Interface Fault     Critical Fault     A hardware problem was detected during power-up. If you ignore message and display the EtherNet/IP Communications Scree, the Comm Status displays "Comms hardware fault:" without an error number. The FW revision, serial number and EtherNet/IP address fields are displayed.     Contact technical support to have unit repaired.    
770     Buffer overflow     Comm Status     Internal error occurred.     Contact technical support.    
771     Buffer overflow     Comm Status     Internal error occurred.     Contact technical support.    
1799     Heap Partition empty     Comm Status     Internal error occurred.     Contact technical support.    
16387     Comms not started yet     Comm Status     The PanelView has not connected to the network.     Check IP configuration (on the Communication Setup scree) and wait for PanelView to connect to the network.    
16388     CIP S/N is not valid     Critical fault.     DC incorrectly configured.     Contact technical support.    
16389     Out of buffers     Critical fault.     No buffers are available for read or write operations.     Contact technical support.    
16390     An intial write failed     Comm Warning     Write to Logic Controller on Startup was configured and on powerup, the PanelView could not write initial values to a node's data table address. or Write to Logic Controller on Startup was not configured and the PanelView was unable to write a controller. Note: The error is only displayed on the first write attempt.     Check/define data table address in the controller. Check communication connections and node configuation in the application.    
16391     PV write failed     Comm Warning     PanelView is communicating with the controller. The data table address does not exist.     Check/define data table address in the controller.    
16392     PV write timeout     Comm Warning     PanelView is communicating with the logic controller.     Check connections and node configuration in the application.    
16393     PV read fail     Comm Warning     PanelView is communicating with the controller. The data table address does not exist.     Check/define data table address in the controller.    
16394     PV read timeout     Comm Warning     PanelView is not communicating with the controller.     Check/define data table address in the controller.    
16397     CN object received a reset request     Comm Warning     An Ethernet object reveived a reset request from a device on the network.     The PanelView does not support network resets.    
16398     The Connection Originator is indicating it is in Program Mode     Comm Warning     The logic controller is offline (in Program Mode). The COMM LED on the Configuration Mode menu is off.     Place the logic controller in run mode to resume communication.    
16399     A fatal CPU fault occurred     Critical Fault     A fatal CPU fault occurred.     Contact technical support.    
16401     The RAM check failed     Critical Fault     RAM verification failed at startup.     Contact technical support.    
16402     The CRC check of the firmware failed     Critical Fault     CRC verification failed at startup.     Contact technical support.    
16403     OS startup failed     Critical Fault     Operating system failed to start.     Contact technical support.    
16404     PV Client Task Fault     Critical Fault     Internal error has occurred.     Contact technical support.    
16405     Invalid preset information received from motherboard.     Critical Fault     Internal error has occurred.     Contact technical support.    
16406, 16407     Connection with Addr or scan rate invalid or no connection being attempted.     Critical Fault     Internal error has occurred.     Contact technical support.    
16408     No buffers available for read operation     Critical Fault     Internal error has occurred.     Contact technical support.    
16409     DC couldnt send out the write request in time.     Critical Fault     Too many write operations are occurring.     Contact technical support.    
16410     Too many clients attempted to connect to server     Critical Fault     Internal error has occurred.     Contact technical support.    
16411     XS-WD creation error     Critical Fault     Internal error has occurred.     Contact technical support.    
16412     XS-WD start error     Critical Fault     Internal error has occurred.     Contact technical support.    
16413     Enet addr is not valid     Communication Warning     The EtherNet address for a device on the EtherNet/IP network is invalid.     Contact technical support.    
16414     Duplicate IP address detected     Critical Fault     The PanelVIew has the same IP address as another device on the EtherNet/IP network.     Change the IP address of the PanelView (on the Communication Setup screen) so that is unique on the network.    
16415     Unknown error detected     Communication Warning     An operating system message has occurred.     Contact technical support.    
16416     No network link     Critical Fault     Communications has not been established with network.     Check Ethernet cable.    
16417     DHCP/BootP Enable failed     Communication Warning     The DHCP/BootP Enable server failed to allocate an IP address, subnet mask and gateway address to the PanelView terminal     Check DHCP/BootP Enable server on your network.    
16418     Invalid IP Address or Subnet Mask     Communication Warning     The IP address or the subnet mask of the PanelView terminal is not valid. Important: The Gateway Address cannot be entered at the termina; you must configure this address in the Communication Setup dialog of PanelBuilder32.     Enter a valid IP address and/or the subnet mask of the PanelView terminal on the Communication Setup screen. This error occurs if the downloaded application has DHCP/BootP enabled and it is then disabled at the terminal. On a restart, the terminal will not have the necessary information (IP Address, Subnet Mask, Gateway Address) to connect to the network.    
16420     Invalid Gateway Address     Communication Warning     The Gateway Address is not valid.     Change the Gateway Address in the PanelBuilder32 software.    

Caterpillar Information System:

3606, 3608, 3612, 3616 and 3618 Engines and C280-12, C280-16, C280-6 and C280-8 Marine Engines Panel View Monitor Board (Backlight) - Replace
3606, 3608, 3612, 3616 and 3618 Engines and C280-12, C280-16, C280-6 and C280-8 Marine Engines Panel View Monitor Battery - Replace
3606, 3608, 3612, 3616 and 3618 Engines and C280-12, C280-16, C280-6 and C280-8 Marine Engines Panel View Monitor Monitor - Clean
PMG3516 Power Module Voltage Connections
G3500B Engines Valve System Components
Installation and Operation of the Caterpillar Messenger Driver Information Display{7490} Installation and Operation of the Caterpillar Messenger Driver Information Display{7490}
TK711, TK721, TK722 and TK732 Track Feller Bunchers Welding on Machines and Engines with Electronic Controls
G3600 Engines Pressure Switch
3054 and 3056 Marine Generator Set Engines Fuel Injection Nozzle - Test
2002/09/01 The O-Ring Seal In The Air Inlet Elbow Group Is Available For Parts Service {7555}
2011/01/24 Specifications for Turbocharger Bearing Clearances {1052}
3126B and 3126E Truck Engines Water Pump
PMG3516 Power Module Performance Parameters
PMG3516 Power Module Sensors and Electrical Components
PMG3516 Power Module Alarms and Shutoffs
PMG3516 Power Module Before Starting Engine
PMG3516 Power Module Cold Weather Starting
PMG3516 Power Module Generator Operation
PMG3516 Power Module Parallel Operation
3512 and 3516 EUI Engines for Caterpillar Built Machines Crankshaft
3606, 3608, 3612, 3616 and 3618 Engines and C280-12, C280-16, C280-6 and C280-8 Marine Engines Panel View Monitor Memory Module - Replace
PMG3516 Power Module Voltage Regulator Options
PMG3516 Power Module Roading
G3600 Engines Aftercooler - Two-Stage
Back to top
The names Caterpillar, John Deere, JD, JCB, Hyundai or any other original equipment manufacturers are registered trademarks of the respective original equipment manufacturers. All names, descriptions, numbers and symbols are used for reference purposes only.
CH-Part.com is in no way associated with any of the manufacturers we have listed. All manufacturer's names and descriptions are for reference only.