K65-12B Voltage Regulator Caterpillar


Voltage Adjustment Range - Calibrate

Usage:

SR4BHV A4X



Illustration 1g00899851

K65-12B Voltage Regulator

(1) Factory calibration adjustment

(2) Voltage adjustment




Illustration 2g01021519

------ DANGER! ------

The Cat K65-12B Voltage Regulator presents an electrical shock/electrocution hazard. This hazard will cause serious injury or death.

Service by trained personnel only.

The terminals and heat sinks are live at hazardous voltages when power is applied and for up to 8 minutes after power is removed.



NOTICE

Do not operate generator at a voltage greater than 5% above the name plate rating.


The factory calibration adjustment (1) should be used by the factory technicians only. The following procedure can be used if the factory calibration has been disturbed:

  1. Remove the seal from the factory calibration adjustment (1) .

  1. Start the genset.

  1. Run the genset at no load.

  1. Turn the factory calibration adjustment (1) in a fully counterclockwise direction.

  1. Turn the voltage adjust rheostat (2) in a fully clockwise direction.

  1. Slowly turn the factory calibration adjustment (1) CW until the voltage on 20-22-24 is 144 ± 1 ACV.

  1. Turn the voltage adjust rheostat (2) CCW.

  1. Verify that the voltage on 20-22-24 is less than 90 ACV. The unit is calibrated.

  1. Seal the factory calibration adjustment (1) .
Back to top