3054 and 3056 Engines 550 Generator Set Control Panel Caterpillar


Factory Default Values of Configuration Parameters

Usage:

3054 CHN
The default factory settings that follow are for the control module that has the Check SYNC option.

Miscellaneous Settings

Table 1
Generator Poles     4    
Engine Speed Sensor Fitted     No    
AC System     3 phase, 4 wire    
Enable Generator Sequence Alarm     Yes    
Enable bus sequence alarm     Yes    
Phase Sequence     L1, L2, L3    
Display indications on display     No    
Display load switching state machine     No    
Enable fast loading feature     Yes    
Are warnings are latched     No    
Start key must be held down to crank     No    
Audible alarm prior to starting     No    
Number of start attempts     3    

Input Settings

Table 2
Low Oil Pressure Input Type     VDO 10 bar    
High cooling temperature input type     VDO
120 °C (248 °F)    

Alarm/Shutdown Settings

Table 3
Alarm/Shutdown     Trip     Return    
Low oil pressure prealarm     1.17 Bar,
117 kPa (17 psi)    
1.24 Bar, i
124 kPa (18 psi)    
Low oil pressure shutdown     1.03 Bar, 14.9 Psi
103 kPa (14.9 psi)    
-    
High coolant temp prealarm    
115 °C (239 °F)    

110 °C (230 °F)    
High coolant temp shutdown    
120 °C (248 °F)    
-    

Digital Inputs

Table 4
1     Remote start close to activate    
2     Generator closed auxiliary close to activate    
3     User configured close to activate warning active from safety on    
4     User configured close to activate shutdown always active    
5     User configured close to activate shutdown active from safety on    
6     User configured close to activate electrtical trip always active    
7     User configured close to activate electrical trip active from safety on    
8     User configured close to activate indication always active    
9     Panel lock close to activate    

Indicator Settings




Illustration 1g00867288

Indicator Identification Diagram

Table 5
1     On, Remote start present    
2     On, Panel locked by digital input    
3     On, Delayed alarms armed    
4     On, Check sync    

Output Settings

Table 6
Module Relays    
1     Energize preheat (during preheat timer)    
2     Energize Common alarm    
3     Energize close generator    
4     Energize system in auto mode    
5     Energize close generator    
6     Energize close generator request    

Table 7
Expansion A    
1     Energize Output Not Used    
2     Energize Output Not Used    
3     Energize Output Not Used    
4     Energize Output Not Used    
5     Energize Output Not Used    
6     Energize Output Not Used    
7     Energize Output Not Used    
8     Energize Output Not Used    

Table 8
Expansion B    
1     Energize Output Not Used    
2     Energize Output Not Used    
3     Energize Output Not Used    
4     Energize Output Not Used    
5     Energize Output Not Used    
6     Energize Output Not Used    
7     Energize Output Not Used    
8     Energize Output Not Used    

Timer Settings

Table 9
Starting Timers    
Start Delay     5 Seconds    
Preheat     0 Seconds    
Preheat Bypass     0 Minutes    
Sensor fail delay     2 Seconds    
Cranking Time     10 Seconds    
Crank Rest Time     10 Seconds    
Smoke Limit     0 Seconds    
Smoke Limit Off     0 Seconds    
Safety On Delay     10 Seconds    
Overspeed Overshoot     0 Seconds    

Table 10
Load Timers    
Warming Up Time     0 Seconds    
Transfer Time     0.7 Seconds    
Breaker Close Pulse     0.0 Seconds    
Breaker Trip Pulse     0.0 Seconds    
Generator Close Timer     1.3 Seconds    
Generator Open Timer     5 Seconds    

Table 11
Stopping Timers    
Return Delay     30 Seconds    
Cooling Time     30 Seconds    
ETS Solenoid Hold     0 Seconds    
Fail to Stop Delay     30 Seconds    

Table 12
Other Timers    
Battery low volts delay     1 minute    
Battery high volts delay     1 minute    
Display auto scroll timer     2 seconds    
Display page timer     5 minutes    
Reverse power alarm     0.0 seconds    

Generator Settings

Table 13
Voltage And Frequency Settings     Trip     Return    
Under volts trip     184 VAC     -    
Under volts pre alarm     196 VAC     207 VAC    
Over volts prealarm     265 VAC     253 VAC    
Over volts trip     276 VAC     -    
Under frequency trip     40.0 Hz     -    
Under frequency prealarm     42.0 Hz     45.0 Hz    
Over frequency prealarm     55.0 Hz     52.0 Hz    
Over frequency trip     57.0 Hz     -    

Table 14
Power Settings    
Generator CT primary     500 A    
Generator full load rating     500 A    
Earth fault CT primary rating     500 A    
Trip Curve/Multiplier Action     -    
Delayed overdurrent     100% (500 A) 36 Electrical trip    
Short circuit     300% (1500 A) 6 Electrical trip    
Earth fault     10% (50 A) 1000 Shutdown    
Reverse power     0.3 KW Electrical trip    

Table 15
Synchronizing (check sync) Settings    
Enable synchronising     Yes    
Check sync phase angle     10°    
Check sync frequency     0.2 Hz    
Check sync RMS voltage     5.0 VAC    
Sync advance time     0 mS    
Sync hold time     100 mS    
Fail to sync time     30.0 seconds    

Engine Settings

Table 16
Crank Disconnect Trip    
Crank disconnect on generator frequency     21.0 Hz    
Crank disconnect on generator voltage     Disabled    
Crank disconnect on alternator     Disabled    
Crank disconnect on oil pressure     Disabled    
Check oil pressure prior to starting     Yes    

Table 17
Speed Settings    
Overspeed Overshoot     0%    

Table 18
Plant Battery Settings     Trip     Return    
Under volts warning     8.0 VDC     9.0 VDC    
Over volts warning     33.0 VDC     32.0 VDC    
Alternator warning     8.0 VDC     -    

Table 19
Maintenance Alarm Settings    
Enable maintenance alarm     No    

Table 20
Exercise Scheduler Settings    
Enable exercise scheduler     No    

Table 21
Language Settings    
Default language     English (UK)    
User defined language 1     Chinese (PRC)    
User defined language 2     Not Used    
User defined language 3     Not Used    
User defined language 4     Not Used    

Output Settings

Table 22
Module Relays    
1     Energize preheat (during preheat timer)    
2     Energize Common alarm    
3     Energize close generator    
4     Energize system in auto mode    
5     Energize close generator    
6     Energize close generator request    

Table 23
Expansion A    
1     Energize Output Not Used    
2     Energize Output Not Used    
3     Energize Output Not Used    
4     Energize Output Not Used    
5     Energize Output Not Used    
6     Energize Output Not Used    
7     Energize Output Not Used    
8     Energize Output Not Used    

Table 24
Expansion B    
1     Energize Output Not Used    
2     Energize Output Not Used    
3     Energize Output Not Used    
4     Energize Output Not Used    
5     Energize Output Not Used    
6     Energize Output Not Used    
7     Energize Output Not Used    
8     Energize Output Not Used    

Timer Settings

Table 25
Starting Timers    
Start Delay     5 Seconds    
Preheat     0 Seconds    
Preheat Bypass     0 Minutes    
Sensor fail delay     2 Seconds    
Cranking Time     10 Seconds    
Crank Rest Time     10 Seconds    
Smoke Limit     0 Seconds    
Smoke Limit Off     0 Seconds    
Safety On Delay     10 Seconds    
Overspeed Overshoot     0 Seconds    

Table 26
Load Timers    
Warming Up Time     0 Seconds    
Transfer Time     0.7 Seconds    
Breaker Close Pulse     0.0 Seconds    
Breaker Trip Pulse     0.0 Seconds    
Generator Close Timer     1.3 Seconds    
Generator Open Timer     5 Seconds    

Table 27
Stopping Timers    
Return Delay     30 Seconds    
Cooling Time     30 Seconds    
ETS Solenoid Hold     0 Seconds    
Fail to Stop Delay     30 Seconds    

Table 28
Other Timers    
Battery low volts delay     1 minute    
Battery high volts delay     1 minute    
Display auto scroll timer     2 seconds    
Display page timer     5 minutes    
Reverse power alarm     0.0 seconds    

Generator Settings

Table 29
Voltage And Frequency Settings     Trip     Return    
Under volts trip     184 VAC     -    
Under volts pre alarm     196 VAC     207 VAC    
Over volts prealarm     265 VAC     253 VAC    
Over volts trip     276 VAC     -    
Under frequency trip     40.0 Hz     -    
Under frequency prealarm     42.0 Hz     45.0 Hz    
Over frequency prealarm     55.0 Hz     52.0 Hz    
Over frequency trip     57.0 Hz     -    

Table 30
Power Settings    
Generator CT primary     500 A    
Generator full load rating     500 A    
Earth fault CT primary rating     500 A    
Trip Curve/Multiplier Action     -    
Delayed overdurrent     100% (500 A) 36 Electrical trip    
Short circuit     300% (1500 A) 6 Electrical trip    
Earth fault     10% (50 A) 1000 Shutdown    
Reverse power     0.3 KW Electrical trip    

Table 31
Synchronizing (check sync) Settings    
Enable synchronising     Yes    
Check sync phase angle     10°    
Check sync frequency     0.2 Hz    
Check sync RMS voltage     5.0 VAC    
Sync advance time     0 mS    
Sync hold time     100 mS    
Fail to sync time     30.0 seconds    

Engine Settings

Table 32
Crank Disconnect Trip    
Crank disconnect on generator frequency     21.0 Hz    
Crank disconnect on generator voltage     Disabled    
Crank disconnect on alternator     Disabled    
Crank disconnect on oil pressure     Disabled    
Check oil pressure prior to starting     Yes    

Table 33
Speed Settings    
Overspeed Overshoot     0%    

Table 34
Plant Battery Settings     Trip     Return    
Under volts warning     8.0 VDC     9.0 VDC    
Over volts warning     33.0 VDC     32.0 VDC    
Alternator warning     8.0 VDC     -    

Table 35
Maintenance Alarm Settings    
Enable maintenance alarm     No    

Table 36
Exercise Scheduler Settings    
Enable exercise scheduler     No    

Table 37
Language Settings    
Default language     English (UK)    
User defined language 1     Chinese (PRC)    
User defined language 2     Not Used    
User defined language 3     Not Used    
User defined language 4     Not Used    

Caterpillar Information System:

C-15 and C-16 Industrial Engines General Information
PM820, PM822, and PM825 Cold Planer Track Drive Planetary Oil Sample - Obtain
CIPI UNDERCARRIAGE Arrangements: 9Q-5262, 191-4041, and 204-9207 S·O·S Oil Analysis
CIPI UNDERCARRIAGE Arrangements: 3Q6662, 6Z7861, 6Z7885, 6Z7947, 6Z7957, 6Z7999, 9Q5044, 9Q5065, 9Q5082, 9Q5090, 9Q5093, 9Q5115, 9Q5118, 9Q5126, 9Q5135, 9Q5141, 9Q5168, 9Q5175, 9Q5206, 9Q5255, 9Q5259, 9Q5268, 9Q5412, 9Q5436, 9Q5464, 9Q5514, 9Q5617, 9 Front Idler - Disassemble
CIPI UNDERCARRIAGE Arrangements: 3Q6662, 6Z7861, 6Z7885, 6Z7947, 6Z7957, 6Z7999, 9Q5044, 9Q5065, 9Q5082, 9Q5090, 9Q5093, 9Q5115, 9Q5118, 9Q5126, 9Q5135, 9Q5141, 9Q5168, 9Q5175, 9Q5206, 9Q5255, 9Q5259, 9Q5268, 9Q5412, 9Q5436, 9Q5464, 9Q5514, 9Q5617, 9 Front Idler, Recoil Spring and Hydraulic Track Adjuster - Remove and Install
G3500 Engines Overhaul (Major)
CIPI UNDERCARRIAGE Arrangements: 3Q6662, 6Z7861, 6Z7885, 6Z7947, 6Z7957, 6Z7999, 9Q5044, 9Q5065, 9Q5082, 9Q5090, 9Q5093, 9Q5115, 9Q5118, 9Q5126, 9Q5135, 9Q5141, 9Q5168, 9Q5175, 9Q5206, 9Q5255, 9Q5259, 9Q5268, 9Q5412, 9Q5436, 9Q5464, 9Q5514, 9Q5617, 9 Track - Connect
CIPI UNDERCARRIAGE Arrangements: 3Q6662, 6Z7861, 6Z7885, 6Z7947, 6Z7957, 6Z7999, 9Q5044, 9Q5065, 9Q5082, 9Q5090, 9Q5093, 9Q5115, 9Q5118, 9Q5126, 9Q5135, 9Q5141, 9Q5168, 9Q5175, 9Q5206, 9Q5255, 9Q5259, 9Q5268, 9Q5412, 9Q5436, 9Q5464, 9Q5514, 9Q5617, 9 Track - Separate
C12 Marine Engines Diagnostic Flash Code Retrieval
CIPI UNDERCARRIAGE Arrangements: 3Q6662, 6Z7861, 6Z7885, 6Z7947, 6Z7957, 6Z7999, 9Q5044, 9Q5065, 9Q5082, 9Q5090, 9Q5093, 9Q5115, 9Q5118, 9Q5126, 9Q5135, 9Q5141, 9Q5168, 9Q5175, 9Q5206, 9Q5255, 9Q5259, 9Q5268, 9Q5412, 9Q5436, 9Q5464, 9Q5514, 9Q5617, 9 Track Roller - Install
G3500 Engines Ignition System Spark Plugs - Inspect/Replace
CIPI UNDERCARRIAGE Arrangements: 3Q6662, 6Z7861, 6Z7885, 6Z7947, 6Z7957, 6Z7999, 9Q5044, 9Q5065, 9Q5082, 9Q5090, 9Q5093, 9Q5115, 9Q5118, 9Q5126, 9Q5135, 9Q5141, 9Q5168, 9Q5175, 9Q5206, 9Q5255, 9Q5259, 9Q5268, 9Q5412, 9Q5436, 9Q5464, 9Q5514, 9Q5617, 9 Track Roller - Assemble
3408E and 3412E Industrial Engines Flywheel Housing
797 Off-Highway Truck Braking System Relief Valve (Brake Oil Cooler) - Primary and Secondary
Electronic Modular Control Panel II (EMCP II) Electronic Control Module (Engine)
CPT372 Truck Mounted Pumper Reference Material
CIPI UNDERCARRIAGE Arrangements: 3Q6662, 6Z7861, 6Z7885, 6Z7947, 6Z7957, 6Z7999, 9Q5044, 9Q5065, 9Q5082, 9Q5090, 9Q5093, 9Q5115, 9Q5118, 9Q5126, 9Q5135, 9Q5141, 9Q5168, 9Q5175, 9Q5206, 9Q5255, 9Q5259, 9Q5268, 9Q5412, 9Q5436, 9Q5464, 9Q5514, 9Q5617, 9 Front Idler - Assemble
Electronic Modular Control Panel II (EMCP II) GSC CID 0110 - FMI 02 (for EUI Engines)
3408E and 3412E Industrial Engines Flywheel and Flywheel Housing Runout
CIPI UNDERCARRIAGE Arrangements: 3Q6662, 6Z7861, 6Z7885, 6Z7947, 6Z7957, 6Z7999, 9Q5044, 9Q5065, 9Q5082, 9Q5090, 9Q5093, 9Q5115, 9Q5118, 9Q5126, 9Q5135, 9Q5141, 9Q5168, 9Q5175, 9Q5206, 9Q5255, 9Q5259, 9Q5268, 9Q5412, 9Q5436, 9Q5464, 9Q5514, 9Q5617, 9 Recoil Spring - Disassemble
SR4 Generator with VR3 or VR4 Voltage Regulator Bearing - Remove and Install
SR4 Generator with VR3 or VR4 Voltage Regulator Exciter - Remove and Install
SR4 Generator with VR3 or VR4 Voltage Regulator Generator - Remove
SR4 Generator with VR3 or VR4 Voltage Regulator Generator - Install
Back to top
The names Caterpillar, John Deere, JD, JCB, Hyundai or any other original equipment manufacturers are registered trademarks of the respective original equipment manufacturers. All names, descriptions, numbers and symbols are used for reference purposes only.
CH-Part.com is in no way associated with any of the manufacturers we have listed. All manufacturer's names and descriptions are for reference only.