Factory Default Values of Configuration Parameters
The default factory settings that follow are for the control module that has the Check SYNC option.
Miscellaneous Settings
Show/hide table
Generator Poles     | 4     |
Engine Speed Sensor Fitted     | No     |
AC System     | 3 phase, 4 wire     |
Enable Generator Sequence Alarm     | Yes     |
Enable bus sequence alarm     | Yes     |
Phase Sequence     | L1, L2, L3     |
Display indications on display     | No     |
Display load switching state machine     | No     |
Enable fast loading feature     | Yes     |
Are warnings are latched     | No     |
Start key must be held down to crank     | No     |
Audible alarm prior to starting     | No     |
Number of start attempts     | 3     |
Input Settings
Show/hide table
Low Oil Pressure Input Type     | VDO 10 bar     |
High cooling temperature input type     | VDO 120 °C (248 °F)     |
Alarm/Shutdown Settings
Show/hide table
Alarm/Shutdown     | Trip     | Return     |
---|---|---|
Low oil pressure prealarm     | 1.17 Bar, 117 kPa (17 psi)     |
1.24 Bar, i 124 kPa (18 psi)     |
Low oil pressure shutdown     | 1.03 Bar, 14.9 Psi 103 kPa (14.9 psi)     |
-     |
High coolant temp prealarm     | 115 °C (239 °F)     |
110 °C (230 °F)     |
High coolant temp shutdown     | 120 °C (248 °F)     |
-     |
Digital Inputs
Show/hide table
1     | Remote start close to activate     |
2     | Generator closed auxiliary close to activate     |
3     | User configured close to activate warning active from safety on     |
4     | User configured close to activate shutdown always active     |
5     | User configured close to activate shutdown active from safety on     |
6     | User configured close to activate electrtical trip always active     |
7     | User configured close to activate electrical trip active from safety on     |
8     | User configured close to activate indication always active     |
9     | Panel lock close to activate     |
Indicator Settings
Show/hide table
Illustration 1 | g00867288 |
Indicator Identification Diagram |
Show/hide table
1     | On, Remote start present     |
2     | On, Panel locked by digital input     |
3     | On, Delayed alarms armed     |
4     | On, Check sync     |
Output Settings
Show/hide table
Module Relays     | |
---|---|
1     | Energize preheat (during preheat timer)     |
2     | Energize Common alarm     |
3     | Energize close generator     |
4     | Energize system in auto mode     |
5     | Energize close generator     |
6     | Energize close generator request     |
Show/hide table
Expansion A     | |
---|---|
1     | Energize Output Not Used     |
2     | Energize Output Not Used     |
3     | Energize Output Not Used     |
4     | Energize Output Not Used     |
5     | Energize Output Not Used     |
6     | Energize Output Not Used     |
7     | Energize Output Not Used     |
8     | Energize Output Not Used     |
Show/hide table
Expansion B     | |
---|---|
1     | Energize Output Not Used     |
2     | Energize Output Not Used     |
3     | Energize Output Not Used     |
4     | Energize Output Not Used     |
5     | Energize Output Not Used     |
6     | Energize Output Not Used     |
7     | Energize Output Not Used     |
8     | Energize Output Not Used     |
Timer Settings
Show/hide table
Starting Timers     | |
---|---|
Start Delay     | 5 Seconds     |
Preheat     | 0 Seconds     |
Preheat Bypass     | 0 Minutes     |
Sensor fail delay     | 2 Seconds     |
Cranking Time     | 10 Seconds     |
Crank Rest Time     | 10 Seconds     |
Smoke Limit     | 0 Seconds     |
Smoke Limit Off     | 0 Seconds     |
Safety On Delay     | 10 Seconds     |
Overspeed Overshoot     | 0 Seconds     |
Show/hide table
Load Timers     | |
---|---|
Warming Up Time     | 0 Seconds     |
Transfer Time     | 0.7 Seconds     |
Breaker Close Pulse     | 0.0 Seconds     |
Breaker Trip Pulse     | 0.0 Seconds     |
Generator Close Timer     | 1.3 Seconds     |
Generator Open Timer     | 5 Seconds     |
Show/hide table
Stopping Timers     | |
---|---|
Return Delay     | 30 Seconds     |
Cooling Time     | 30 Seconds     |
ETS Solenoid Hold     | 0 Seconds     |
Fail to Stop Delay     | 30 Seconds     |
Show/hide table
Other Timers     | |
---|---|
Battery low volts delay     | 1 minute     |
Battery high volts delay     | 1 minute     |
Display auto scroll timer     | 2 seconds     |
Display page timer     | 5 minutes     |
Reverse power alarm     | 0.0 seconds     |
Generator Settings
Show/hide table
Voltage And Frequency Settings     | Trip     | Return     |
---|---|---|
Under volts trip     | 184 VAC     | -     |
Under volts pre alarm     | 196 VAC     | 207 VAC     |
Over volts prealarm     | 265 VAC     | 253 VAC     |
Over volts trip     | 276 VAC     | -     |
Under frequency trip     | 40.0 Hz     | -     |
Under frequency prealarm     | 42.0 Hz     | 45.0 Hz     |
Over frequency prealarm     | 55.0 Hz     | 52.0 Hz     |
Over frequency trip     | 57.0 Hz     | -     |
Show/hide table
Power Settings     | |
---|---|
Generator CT primary     | 500 A     |
Generator full load rating     | 500 A     |
Earth fault CT primary rating     | 500 A     |
Trip Curve/Multiplier Action     | -     |
Delayed overdurrent     | 100% (500 A) 36 Electrical trip     |
Short circuit     | 300% (1500 A) 6 Electrical trip     |
Earth fault     | 10% (50 A) 1000 Shutdown     |
Reverse power     | 0.3 KW Electrical trip     |
Show/hide table
Synchronizing (check sync) Settings     | |
---|---|
Enable synchronising     | Yes     |
Check sync phase angle     | 10°     |
Check sync frequency     | 0.2 Hz     |
Check sync RMS voltage     | 5.0 VAC     |
Sync advance time     | 0 mS     |
Sync hold time     | 100 mS     |
Fail to sync time     | 30.0 seconds     |
Engine Settings
Show/hide table
Crank Disconnect Trip     | |
Crank disconnect on generator frequency     | 21.0 Hz     |
Crank disconnect on generator voltage     | Disabled     |
Crank disconnect on alternator     | Disabled     |
Crank disconnect on oil pressure     | Disabled     |
Check oil pressure prior to starting     | Yes     |
Show/hide table
Speed Settings     | |
---|---|
Overspeed Overshoot     | 0%     |
Show/hide table
Plant Battery Settings     | Trip     | Return     |
---|---|---|
Under volts warning     | 8.0 VDC     | 9.0 VDC     |
Over volts warning     | 33.0 VDC     | 32.0 VDC     |
Alternator warning     | 8.0 VDC     | -     |
Show/hide table
Maintenance Alarm Settings     | |
---|---|
Enable maintenance alarm     | No     |
Show/hide table
Exercise Scheduler Settings     | |
---|---|
Enable exercise scheduler     | No     |
Show/hide table
Language Settings     | |
---|---|
Default language     | English (UK)     |
User defined language 1     | Chinese (PRC)     |
User defined language 2     | Not Used     |
User defined language 3     | Not Used     |
User defined language 4     | Not Used     |
Output Settings
Show/hide table
Module Relays     | |
---|---|
1     | Energize preheat (during preheat timer)     |
2     | Energize Common alarm     |
3     | Energize close generator     |
4     | Energize system in auto mode     |
5     | Energize close generator     |
6     | Energize close generator request     |
Show/hide table
Expansion A     | |
---|---|
1     | Energize Output Not Used     |
2     | Energize Output Not Used     |
3     | Energize Output Not Used     |
4     | Energize Output Not Used     |
5     | Energize Output Not Used     |
6     | Energize Output Not Used     |
7     | Energize Output Not Used     |
8     | Energize Output Not Used     |
Show/hide table
Expansion B     | |
---|---|
1     | Energize Output Not Used     |
2     | Energize Output Not Used     |
3     | Energize Output Not Used     |
4     | Energize Output Not Used     |
5     | Energize Output Not Used     |
6     | Energize Output Not Used     |
7     | Energize Output Not Used     |
8     | Energize Output Not Used     |
Timer Settings
Show/hide table
Starting Timers     | |
---|---|
Start Delay     | 5 Seconds     |
Preheat     | 0 Seconds     |
Preheat Bypass     | 0 Minutes     |
Sensor fail delay     | 2 Seconds     |
Cranking Time     | 10 Seconds     |
Crank Rest Time     | 10 Seconds     |
Smoke Limit     | 0 Seconds     |
Smoke Limit Off     | 0 Seconds     |
Safety On Delay     | 10 Seconds     |
Overspeed Overshoot     | 0 Seconds     |
Show/hide table
Load Timers     | |
---|---|
Warming Up Time     | 0 Seconds     |
Transfer Time     | 0.7 Seconds     |
Breaker Close Pulse     | 0.0 Seconds     |
Breaker Trip Pulse     | 0.0 Seconds     |
Generator Close Timer     | 1.3 Seconds     |
Generator Open Timer     | 5 Seconds     |
Show/hide table
Stopping Timers     | |
---|---|
Return Delay     | 30 Seconds     |
Cooling Time     | 30 Seconds     |
ETS Solenoid Hold     | 0 Seconds     |
Fail to Stop Delay     | 30 Seconds     |
Show/hide table
Other Timers     | |
---|---|
Battery low volts delay     | 1 minute     |
Battery high volts delay     | 1 minute     |
Display auto scroll timer     | 2 seconds     |
Display page timer     | 5 minutes     |
Reverse power alarm     | 0.0 seconds     |
Generator Settings
Show/hide table
Voltage And Frequency Settings     | Trip     | Return     |
---|---|---|
Under volts trip     | 184 VAC     | -     |
Under volts pre alarm     | 196 VAC     | 207 VAC     |
Over volts prealarm     | 265 VAC     | 253 VAC     |
Over volts trip     | 276 VAC     | -     |
Under frequency trip     | 40.0 Hz     | -     |
Under frequency prealarm     | 42.0 Hz     | 45.0 Hz     |
Over frequency prealarm     | 55.0 Hz     | 52.0 Hz     |
Over frequency trip     | 57.0 Hz     | -     |
Show/hide table
Power Settings     | |
---|---|
Generator CT primary     | 500 A     |
Generator full load rating     | 500 A     |
Earth fault CT primary rating     | 500 A     |
Trip Curve/Multiplier Action     | -     |
Delayed overdurrent     | 100% (500 A) 36 Electrical trip     |
Short circuit     | 300% (1500 A) 6 Electrical trip     |
Earth fault     | 10% (50 A) 1000 Shutdown     |
Reverse power     | 0.3 KW Electrical trip     |
Show/hide table
Synchronizing (check sync) Settings     | |
---|---|
Enable synchronising     | Yes     |
Check sync phase angle     | 10°     |
Check sync frequency     | 0.2 Hz     |
Check sync RMS voltage     | 5.0 VAC     |
Sync advance time     | 0 mS     |
Sync hold time     | 100 mS     |
Fail to sync time     | 30.0 seconds     |
Engine Settings
Show/hide table
Crank Disconnect Trip     | |
Crank disconnect on generator frequency     | 21.0 Hz     |
Crank disconnect on generator voltage     | Disabled     |
Crank disconnect on alternator     | Disabled     |
Crank disconnect on oil pressure     | Disabled     |
Check oil pressure prior to starting     | Yes     |
Show/hide table
Speed Settings     | |
---|---|
Overspeed Overshoot     | 0%     |
Show/hide table
Plant Battery Settings     | Trip     | Return     |
---|---|---|
Under volts warning     | 8.0 VDC     | 9.0 VDC     |
Over volts warning     | 33.0 VDC     | 32.0 VDC     |
Alternator warning     | 8.0 VDC     | -     |
Show/hide table
Maintenance Alarm Settings     | |
---|---|
Enable maintenance alarm     | No     |
Show/hide table
Exercise Scheduler Settings     | |
---|---|
Enable exercise scheduler     | No     |
Show/hide table
Language Settings     | |
---|---|
Default language     | English (UK)     |
User defined language 1     | Chinese (PRC)     |
User defined language 2     | Not Used     |
User defined language 3     | Not Used     |
User defined language 4     | Not Used     |
Caterpillar Information System:
C-15 and C-16 Industrial Engines General Information
PM820, PM822, and PM825 Cold Planer Track Drive Planetary Oil Sample - Obtain
CIPI UNDERCARRIAGE Arrangements: 9Q-5262, 191-4041, and 204-9207 S·O·S Oil Analysis
CIPI UNDERCARRIAGE Arrangements: 3Q6662, 6Z7861, 6Z7885, 6Z7947, 6Z7957, 6Z7999, 9Q5044, 9Q5065, 9Q5082, 9Q5090, 9Q5093, 9Q5115, 9Q5118, 9Q5126, 9Q5135, 9Q5141, 9Q5168, 9Q5175, 9Q5206, 9Q5255, 9Q5259, 9Q5268, 9Q5412, 9Q5436, 9Q5464, 9Q5514, 9Q5617, 9 Front Idler - Disassemble
CIPI UNDERCARRIAGE Arrangements: 3Q6662, 6Z7861, 6Z7885, 6Z7947, 6Z7957, 6Z7999, 9Q5044, 9Q5065, 9Q5082, 9Q5090, 9Q5093, 9Q5115, 9Q5118, 9Q5126, 9Q5135, 9Q5141, 9Q5168, 9Q5175, 9Q5206, 9Q5255, 9Q5259, 9Q5268, 9Q5412, 9Q5436, 9Q5464, 9Q5514, 9Q5617, 9 Front Idler, Recoil Spring and Hydraulic Track Adjuster - Remove and Install
G3500 Engines Overhaul (Major)
CIPI UNDERCARRIAGE Arrangements: 3Q6662, 6Z7861, 6Z7885, 6Z7947, 6Z7957, 6Z7999, 9Q5044, 9Q5065, 9Q5082, 9Q5090, 9Q5093, 9Q5115, 9Q5118, 9Q5126, 9Q5135, 9Q5141, 9Q5168, 9Q5175, 9Q5206, 9Q5255, 9Q5259, 9Q5268, 9Q5412, 9Q5436, 9Q5464, 9Q5514, 9Q5617, 9 Track - Connect
CIPI UNDERCARRIAGE Arrangements: 3Q6662, 6Z7861, 6Z7885, 6Z7947, 6Z7957, 6Z7999, 9Q5044, 9Q5065, 9Q5082, 9Q5090, 9Q5093, 9Q5115, 9Q5118, 9Q5126, 9Q5135, 9Q5141, 9Q5168, 9Q5175, 9Q5206, 9Q5255, 9Q5259, 9Q5268, 9Q5412, 9Q5436, 9Q5464, 9Q5514, 9Q5617, 9 Track - Separate
C12 Marine Engines Diagnostic Flash Code Retrieval
CIPI UNDERCARRIAGE Arrangements: 3Q6662, 6Z7861, 6Z7885, 6Z7947, 6Z7957, 6Z7999, 9Q5044, 9Q5065, 9Q5082, 9Q5090, 9Q5093, 9Q5115, 9Q5118, 9Q5126, 9Q5135, 9Q5141, 9Q5168, 9Q5175, 9Q5206, 9Q5255, 9Q5259, 9Q5268, 9Q5412, 9Q5436, 9Q5464, 9Q5514, 9Q5617, 9 Track Roller - Install
G3500 Engines Ignition System Spark Plugs - Inspect/Replace
CIPI UNDERCARRIAGE Arrangements: 3Q6662, 6Z7861, 6Z7885, 6Z7947, 6Z7957, 6Z7999, 9Q5044, 9Q5065, 9Q5082, 9Q5090, 9Q5093, 9Q5115, 9Q5118, 9Q5126, 9Q5135, 9Q5141, 9Q5168, 9Q5175, 9Q5206, 9Q5255, 9Q5259, 9Q5268, 9Q5412, 9Q5436, 9Q5464, 9Q5514, 9Q5617, 9 Track Roller - Assemble
3408E and 3412E Industrial Engines Flywheel Housing
797 Off-Highway Truck Braking System Relief Valve (Brake Oil Cooler) - Primary and Secondary
Electronic Modular Control Panel II (EMCP II) Electronic Control Module (Engine)
CPT372 Truck Mounted Pumper Reference Material
CIPI UNDERCARRIAGE Arrangements: 3Q6662, 6Z7861, 6Z7885, 6Z7947, 6Z7957, 6Z7999, 9Q5044, 9Q5065, 9Q5082, 9Q5090, 9Q5093, 9Q5115, 9Q5118, 9Q5126, 9Q5135, 9Q5141, 9Q5168, 9Q5175, 9Q5206, 9Q5255, 9Q5259, 9Q5268, 9Q5412, 9Q5436, 9Q5464, 9Q5514, 9Q5617, 9 Front Idler - Assemble
Electronic Modular Control Panel II (EMCP II) GSC CID 0110 - FMI 02 (for EUI Engines)
3408E and 3412E Industrial Engines Flywheel and Flywheel Housing Runout
CIPI UNDERCARRIAGE Arrangements: 3Q6662, 6Z7861, 6Z7885, 6Z7947, 6Z7957, 6Z7999, 9Q5044, 9Q5065, 9Q5082, 9Q5090, 9Q5093, 9Q5115, 9Q5118, 9Q5126, 9Q5135, 9Q5141, 9Q5168, 9Q5175, 9Q5206, 9Q5255, 9Q5259, 9Q5268, 9Q5412, 9Q5436, 9Q5464, 9Q5514, 9Q5617, 9 Recoil Spring - Disassemble
SR4 Generator with VR3 or VR4 Voltage Regulator Bearing - Remove and Install
SR4 Generator with VR3 or VR4 Voltage Regulator Exciter - Remove and Install
SR4 Generator with VR3 or VR4 Voltage Regulator Generator - Remove
SR4 Generator with VR3 or VR4 Voltage Regulator Generator - Install