- Engines:
- G3606 (S/N: 3XF)
- G3608 (S/N: 4WF)
- G3612 (S/N: 1YG)
- G3616 (S/N: 4CG)
Description of Change: A Power Up Time Delay Relay (PUTDR) is being added to the Engine Supervisory System (ESS) panel. The PUTDR will help ensure that the proper shutdown sequence is executed prior to reapplying power. The new PUTDR will cause the ESS to wait for 5 seconds before turning on the power if the Mode Control Switch is moved from the OFF/RESET to any other position.
Adaptable To: The components that follow are parts of the new PUTDR:
Figure 1 shows the new components. The new components can be installed in the ESS panels that do not include the PUTDR.Illustration 1 | g00756287 |
This illustration shows the locations of the PUTDR components. (1) 198-3389 Time Delay Relay (2) 198-6908 Retainer Clip (3) 198-6909 Terminal Socket |
Field Installation Of The PUTDR
Do not operate or work on this engine unless you have read and understand the instructions and warnings in the Operation and Maintenance Manual. Failure to follow the instructions or heed the warnings could result in injury or death. Contact any Caterpillar dealer for replacement manuals. Proper care is your responsibility. |
Refer to the applicable Operation And Maintenance Manual, "General Hazard Information" before you begin this procedure. Attach a "Do Not Operate Tag" to the "Mode Control Switch" before starting this procedure.
The components that are identified in Figure 1 are required for this installation procedure.
Illustration 2 | g00756298 |
This illustration shows the wiring connections between the PUTDR and the ESS panel. |
- Disconnect ESS terminal (568) from ESS terminal (533) .
- Connect PUTDR terminal socket (A) to ESS terminal (568) and connect PUTDR terminal socket (A) to PUTDR terminal socket (7) .
- Connect PUTDR terminal socket (4) to ESS terminal (533) .
- Connect PUTDR terminal socket (B) to ESS terminal (353) .