Electronic Modular Control Panel II (EMCP II) For MUI Engines Caterpillar


Synchronizing Lights Module

Usage:

3304 02B



Illustration 1g00327824

Synchronizing Lights Module

(1) Synchronizing lights. (2) Synchronizing switch.

The synchronizing lights module is optional. The synchronizing lights module is located on the instrument panel (right side).

The synchronizing lights module is not used when the panel is equipped with an electronic governor.

Synchronizing lights (SL) are used as an aid for paralleling the generators that are independent of the load. Two lights are in the module. Each light is connected to the side with the load of the generator output circuit breaker. The voltage of two phases are measured. The lights are used to indicate to the operator when the voltages are in-phase. Close the circuit breaker now. The generator is on the line with the other generators.

Note: For a complete explanation on the procedure to parallel two units, make reference to the Operation And Maintenance Manual, SEBU6918, "SR4B Generators and Control Panels".

Installation Of The Synchronizing Module

------ WARNING! ------

To avoid electrical shock and personal injury, shutdown all on-line gensets before installing or repairing the synchronizing module.

----------------------

Note: For the connection of the synchronizing light module, see the Testing And Adjusting, "Schematic and Wiring Diagrams".

Make an orderly shutdown of all generators connected to the system. Connect the wires of the synchronizing light module to the terminals, as shown below.

  1. Connect wire L1 to terminal L1 of TS1 in the generator housing.

  1. Wire L3 to terminal L3 of TS1 in the generator housing.

  1. Wire T11 to terminal 2 of fuse F13 on the AC transformer box (ATB).

  1. Wire T13 to terminal 2 of fuse F15 on the AC transformer box (ATB).

The customer is responsible for providing the proper electrical material that is needed to connect L1 and L3. L1 and L3 connect to the side of the generator output circuit breaker with the load. See the Testing And Adjusting, "Schematics And Wiring Diagrams".

Adjust the connection of the wires on the taps of the synchronizing resistors. Adjust the connection for the particular AC voltage for the generator to the requirements below.

208 ACV line to line ... taps E to D (1760Ohms)
240 ACV line to line ... taps E to C (2400Ohms)
300 ACV line to line ... taps E to B (5600Ohms)
380 ACV line to line ... taps E to B (5600Ohms)
400 ACV line to line ... taps E to B (5600Ohms)
416 ACV line to line ... taps E to A (7200Ohms)
480 ACV line to line ... taps E to A (7200Ohms)

Note: Remove the synchronizing module cover for access to the resistor taps.

Example - The following connection is for a generator with a line voltage of 400 volts. Connect wire T11 to tap B of SLR1. Also, connect wire T13 to tap B of SLR2. See the Testing And Adjusting, "Schematics And Wiring Diagrams".

Caterpillar Information System:

Electronic Modular Control Panel II (EMCP II) for EUI Engines Relay Driver Module
Electronic Modular Control Panel II (EMCP II) For MUI Engines Alarm Module Control (Custom)
3612 and 3616 Fast Vessel Engines Driven Equipment - Check
TK711, TK721, TK722 and TK732 Track Feller Bunchers Battery Hold-Down - Tighten
TK711, TK721, TK722 and TK732 Track Feller Bunchers Battery - Clean
Electronic Modular Control Panel II (EMCP II) For MUI Engines Alarm Module Control (NFPA 110)
3612 and 3616 Fast Vessel Engines Aftercooler Condensation - Drain
3600 Heavy Fuel Engines Cylinders - Inspect
Electronic Modular Control Panel II (EMCP II) For PEEC Engines Alarm Modules
3512 and 3516 EUI Engines and 784B, 785B, 789B and 793B Off-Highway Truck/Tractors Cylinder Block
3600 Heavy Fuel Engines Cooling System Coolant (DEAC) - Change
C27 PET GEN SET Electric Power Generation and C27 KNOCKDOWN K Petroleum Power Train Package Crankshaft Vibration Damper - Inspect
Electronic Modular Control Panel II (EMCP II) For MUI Engines Synchronizing Lights Module With Reverse Power Relay
Electronic Modular Control Panel II (EMCP II) For MUI Engines Customer Interface Module
Electronic Modular Control Panel II (EMCP II) For MUI Engines System Communication Module (Customer)
G3612 and G3616 Engines Electrical System
3406C Engines for Caterpillar Built Machines Engine Design
G3612 and G3616 Engines General Information (Electrical System)
3612 and 3616 Fast Vessel Engines Engine Air Precleaner - Clean
3406C (PEEC III) Truck Engine Fuel Injection Pump
3304B and 3306B Engines for Caterpillar Built Machines Automatic Timing Advance - Install
G3612 and G3616 Engines Basic Block
G3612 and G3616 Engines Engine Design
3304B and 3306B Engines for Caterpillar Built Machines Automatic Timing Advance - Disassemble
Back to top
The names Caterpillar, John Deere, JD, JCB, Hyundai or any other original equipment manufacturers are registered trademarks of the respective original equipment manufacturers. All names, descriptions, numbers and symbols are used for reference purposes only.
CH-Part.com is in no way associated with any of the manufacturers we have listed. All manufacturer's names and descriptions are for reference only.