Usage:
CONFIDENTIAL TIBU3577-01
TECHNICAL INFORMATION BULLETIN |
July 24, 2002 |
Uninterruptible Power Supply |
UPS250 (APZ, CNM) UPS300 (CNJ, CPZ) UPS500 (CSE) UPS600 (CTX) UPS750 (CPM) UPS900 (CRY) |
Component Code: 7600 |
SUBJECT: New Flash Files Added to SIS Web for UPS Product
UPS View 2.4 Update
File 2223478.exe is a self-extracting .zip file that contains the file UPSView24Update.exe. File 2223478.exe is located on the flash file directory of SIS Web. Run UPSView24Update.exe in order to update existing UPS View 2.2 to UPS View 2.4. File UPSView24Update.exe can only be used to update existing UPS View 2.2 software. File UPSView24Update.exe cannot be used to install UPS View 2.4.
UPS View 2.4 has the following features:
- Added functionality over UPS View 2.2
- Supports UPS Firmware Revision 2.4 (see below)
- Fully compatible with all previously installed UPS systems
UPS Firmware Revision 2.4
Files 2065418.exe and 2065410.exe are self-extracting .zip files that contain the needed files to update UPS 300 series firmware to version 2.4. Files 2065418.exe and 2065410.exe are located on the flash file directory of SIS Web.
Firmware revision 2.4 supports upcoming product enhancements and has enhancements for installed systems that include the following:
- Allows the use of added features from UPS View 2.4 software
- A new fault bit for DC Voltage Imbalance has been added
- Factory options are displayed when "CTRL-N" is pressed (when the Show Configuration Page is displayed on the LCD Display)
- A new feature has been added to the Deadline Timer Circuit in order to test for a successful transfer from the Boot Monitor to the APOS application
It is recommended that Firmware Version 2.4 be installed at the next scheduled service call on existing machines or installed any time one of the following circuit boards is replaced:
If the 201-2187 Controller or the 201-2189 Board Assembly is replaced on a currently installed Multi-Module UPS System, all UPS modules must be updated to Firmware Revision 2.4.
For instructions on updating firmware on UPS 300 Series systems, refer to RENR2476, Systems Operation, Testing and Adjusting, "UPS 250, UPS 300, UPS 500, UPS 750, and UPS 900 Uninterruptible Power Supply".
COPYRIGHT 2002 CATERPILLAR
ALL RIGHTS RESERVED