1998/03/23 Caterpillar


Use 142-5055 Insulation Tester Group To Measure And Check Insulation Resistance{4450,0785}

Usage:


All Generator Sets

Warranty: M

Features/Benefits

* Replaces canceled 9U-6003 Insulation Tester.
* Used to measure and check insulation resistance for electrical power generation.
* Separate voltmeter range operates from 0 to 600 VDC at 50/60 Hz and to 450 VDC at 400 Hz.
* Analog scale reads up to 10 GW for high insulation resistance readings.
* Meter ranges from 100 kW digital and 10 MW analog to test for faults on motors, generators, or relays.
* Tool defaults to voltmeter operation whenever an external voltage greater than 25 VDC or VAC is detected (only exception is when meter is off or preforming battery condition test).
* Auto shut-off feature turns an unused unit off after 5 minutes.
* Display includes solid state analog arc .
* Battery condition test position measures voltage on a simulated load.
* Operates at temperatures from -20°C to +40°C (-4.0°F to 104.0°F)
* Case is weather and dust proof.

Specifications/Technical Information

Insulation Ranges:

Nominal test voltage - 500 VDC
Measuring range (on all ranges) - 0.01 to 999
M/Omega/
Measuring range (on analogue scale) - 0 to 10
G/Omega/
Terminal voltage on open circuit VDC - ±15% maximum
Short circuit current - less than 2 mA
Test current on load - 1 mA at minimum
... pass values of insulation specified
... in BS7671, HD384, and IEC364
Accuracy at 20°C (68°F) - ±2% and ±2 digits

Continuity Ranges:

Measuring range - 0.01 to 99.9 /Omega/
... /(0 to 5 /Omega/ on analogue scale)
Open circuit voltage - 5 ± 1 volt
Short circuit current - 205 ± 5 mA
Accuracy
at 20°C (68°F) - 1 to 9.99 /Omega/, ±2%, ±2 digits;
... 10 to 9.99 /Omega/ ±5%
Zero offset adjust - 0 to 9.99 /Omega/
Continuity buzzer - operates at less than 5 /Omega/
Resistance Range (can be used for diode testing):
Measuring range - 0.1 to 100 k/Omega/
... (0 to 10 M/Omega/ on analog scale)
Open circuit voltage - 5 ± 1 volt
Short circuit current - 20 ± 5 ×A
Accuracy at 20°C (68°F) - ±5%, ±2 digits

Voltage Range:

Measuring range - 0 to 600 VDC
- 0 to 600 VAC (50/60 Hz)
- 0 to 450 VAC (400 Hz)
... or 0 to 500 volts on analogue scale
Accuracy
at 20°C (68°F) - less than 450 VDC
... or VAC (50/60 Hz): ±1%, ±2 digits
- greater than 450 VDC
... or VAC (50/60 Hz): ±2%, ±2 digits
- 450 VDC at 400 Hz: ±5%, ±2 digits

Temperature Coefficient:

All ranges - less than 0.1% per °C


(A) 142-5055 Insulation Tester.
(2) Carrying Case.
(3) 9U-6004 Test Lead Set.
Not shown:
1U-9533 Battery, AA 1.5 Volt Alkaline.
1U-9538 Battery, AA 1.5 Volt Heavy Duty.
4C-5535 Fuse, 500 md.

Service Requirements

For service, contact one of the following suppliers:

AVO International
Archcliffe Rd.
Dover
Kent CT 17 9EN, England
Phone: 44 (0) 1304 502100
Fax: 44 (0) 1304 207342

AVO International
510 Township Line Rd.
Bluebell, PA 19422-2795, U.S.A.
Phone: (215) 646-9200
Fax: (215) 643-7215

Caterpillar Information System:

1998/03/23 Use 152-2067 Differential Pressure Gauge To Monitor Aftercooler Pressure Drop In Applications With Crankcase Fumes Recirculation{1063}
1998/03/23 Use 143-8995 Leak Down Check Tool And 143-8997 Check (Dummy) Valve For Testing Check Valves{1106,0701}
1998/03/23 Use 155-3046 Hex Socket To Remove And Install TPS 57D Turbocharger Band Clamps{1056}
1998/03/23 Use 9U-5156 Tool Group (Part Of 9U-5107 Group) To Clean Prechamber Seats{1106,0680}
1998/03/23 Use 147-5482 Valve Lash Gauge Group To Measure Valve Lash{0766}
1998/03/23 Use 140-2266 Harness Assembly (70-Pin Breakout "T") For Testing And Adjusting{1900,0781}
1998/03/09 Use 134-5195 Adapter Cable For T-harness In Electronic Control Systems{1900,0781}
1998/03/09 Use 129-2018 Power Cable Assembly To Gain Access To ECM Data{1900,0781}
1998/03/09 New Hardened Washer Improves Seat Suspension Service Life{7324}
1998/03/02 Use 139-2788 Ferrule (AWG 24-12) And 139-2789 Ferrule (AWG 10-6) Crimp Tools For Repairing 3500 SR4B Generator Wiring Harness {1403}
1998/03/02 Use 140-9944 Terminal Kit To Repair Wiring Harness {1400,0700}
1998/02/09 Replacement Available For 7M-7260 Liquid Gasket {0648,0649,0651}
1998/03/23 Replacement Available For 7M-7260 Liquid Gasket{0648,0649,0651}
1998/03/23 Use 143-6092 Pressure Meter To Measure Differential, Static, And Peak Pressures In Hydraulic Systems{3000,4100,4112,4351,5050,5070,5450,5454,0727}
1998/03/23 Replacements Products Available For 4C-4079 Brake And Component Cleaner{0680}
1998/03/30 Use Calibration Tools To Set, Test, And Adjust Heavy Sleeve Metering Fuel System {1250,1251}
1998/03/30 Use 7X-1703 Adapter Group For Mounting 7X-1700 Communication Adapter On 8T-8697 ECAP {1900,0781}
1998/03/30 Use 9U-6803 Tester For Hydraulic Cylinders {7562}
1998/03/30 Use 137-2700 Bore Welding Group (110V), 138-8215 Bore Welding Group (110V With Auto-Skip), 138-8212 Bore Welding Group (220V) And 138-8213 Bore Welding Group (220V With Auto-Skip) For Building Up Worn Or Damaged Bores {0672}
1998/03/30 Use Measuring Tools For Crimp Diameter {0700}
1998/03/30 Use 1U-6189 Lamp Tool For Removal And Installation Of Small Control Panel Bulbs {1400,0709}
1998/03/30 Use 136-3642 Crimp Tool Group For 4C-9900 And 6V-4900 Presses {5057}
1998/05/04 Improved Alternator Groups Now Available{1405}
1998/05/04 ROPS Instruction Film Available Through Parts Service{7177,7405}