Generator Removal
Usage:
Remove Generator From Engine
1. Remove the rear panel and louvers from the generator frame. Put pieces of cardboard or sheet metal between the rotor and the stater. See GENERATOR BEARING REMOVAL.
2. Remove cover (1) from the generator.
3. Remove bolts (4) that fasten the plates to the flywheel.
4. Remove bolts (3) that fasten the generator to the flywheel housing.
5. Fasten a hoist to the generator. Remove the four bolts (2) that hold the generator on the mount or rail.
6. If the generator is equipped with a control panel, disconnect wires (5) from the engine at the terminal strip.
7. Remove nut (6) and pull the conduit and wires (5) out of the generator housing.
8. Remove the generator with a hoist.
Caterpillar Information System:
SR4 GENERATOR Generator Bearing (Inside Bearing Type RFA)
SR4 GENERATOR Generator Bearing (Outside Bearing Type RFA)
SR4 GENERATOR Control Panel
SR4 GENERATOR Testing And Adjusting
SR4 GENERATOR Systems Operation
SRCR GENERATOR Generator Rewind Data
SRCR GENERATOR Alignment Of Single Bearing Generators (Typical)
SRCR GENERATOR Bearing Retainer And Brush Yoke Assembly
SRCR GENERATOR Rotating Field
SRCR GENERATOR Generator Drive Assembly
SRCR GENERATOR Generator Covers
SRCR GENERATOR SRCR Generators
SR4 GENERATOR Alignment Of Single-Bearing Generators (Typical)
SR4 GENERATOR Rotor Assembly
SR4 GENERATOR Stator Assembly
SR4 GENERATOR Systems Operation
FLOOR-STANDING SWITCHGEAR Operation
FLOOR-STANDING SWITCHGEAR Automatic Start-Stop
FLOOR-STANDING SWITCHGEAR Alternating Current Components Troubleshooting
FLOOR-STANDING SWITCHGEAR Automatic Start-Stop Troubleshooting
GENERATOR SET CONTROL PANEL Components
GENERATOR SET CONTROL PANEL Systems Operation
GENERATOR SET CONTROL PANEL Schematics And Wiring Diagrams
CATERPILLAR SWITCHGEAR Systems Operation