ELECTRIC PROTECTIVE SYSTEM FOR ENGINES EQUIPPED WITH REVERSA Caterpillar


System Problem Index

Usage:

Engine Will Not Start:

Overspeed Switch Closed (Battery Voltage at Speed Switch Terminal ESS-7)

Overspeed Trips (Light ON) When Power is First Applied With Engine Stopped

Reversal Indication (System Voltage Across Strip Terminals TS-21 & TS-27)

Speed Switch Will Not Reset After Reversal Shutdown Indication

Starter Motor Cranks Intermittently

Starter Motor Cranking Stops Too Soon

Starter Motor Will Not Crank

Engine Runs, But There is Still a Problem:

Overspeed Trips (Light ON) at Wrong Speed

Overspeed Trips Intermittently (Light ON and OFF) With Engine Running

Overspeed Will Not Trip (Light OFF) During 75% Overspeed Verify Test

Reversal Trips Intermittently (Light ON and OFF)

Starter Motor Cranking Stops at Wrong Speed

Starter Motor Will Not Disengage

Engine Will Not Shut Down:

Engine RPM is Above Oil Step RPM and Engine Oil Pressure is Lower Than Preset Value (35 psi), But No Engine Shutdown

Engine RPM is Below Oil Step RPM and Engine Oil Pressure is Lower Than Preset Value (15 psi), But No Engine Shutdown

Overspeed Trips (Light ON), But No Engine Shutdown

Reversal Conditions Exist (Actual or Simulated), But No Engine Shutdown

Caterpillar Information System:

ELECTRIC PROTECTIVE SYSTEM FOR ENGINES EQUIPPED WITH REVERSA Electric Protective System Functional Test
ELECTRIC PROTECTIVE SYSTEM FOR ENGINES EQUIPPED WITH REVERSA Introduction To The Troubleshooting Guide
ELECTRIC PROTECTIVE SYSTEM FOR ENGINES EQUIPPED WITH REVERSA Systems Operation
SUPPLEMENT FOR ALTRONIC IGNITION SYSTEM Altronic Magneto
2301 ELECTRIC GOVERNOR FOR GENERATOR SET AND INDUSTRIAL ENGI Service Procedures
2301 ELECTRIC GOVERNOR FOR GENERATOR SET AND INDUSTRIAL ENGI Problem No. 8: Engine Does Not Parallel
2301 ELECTRIC GOVERNOR FOR GENERATOR SET AND INDUSTRIAL ENGI Problem No. 7: Engine Does Not Share Load (For Load Share Units Only)
2301 ELECTRIC GOVERNOR FOR GENERATOR SET AND INDUSTRIAL ENGI Problem No. 6: Engine Overspeeds
2301 ELECTRIC GOVERNOR FOR GENERATOR SET AND INDUSTRIAL ENGI Problem No. 5: Engine Speed Not Constant
2301 ELECTRIC GOVERNOR FOR GENERATOR SET AND INDUSTRIAL ENGI Problem No. 4: Engine Will Not Decelerate. Engine Will Not Idle.
2301 ELECTRIC GOVERNOR FOR GENERATOR SET AND INDUSTRIAL ENGI Problem No. 3: Engine Will Not Carry Load (Low Power)
2301 ELECTRIC GOVERNOR FOR GENERATOR SET AND INDUSTRIAL ENGI Problem No. 2: Engine Will Not Start
ELECTRIC PROTECTIVE SYSTEM FOR ENGINES EQUIPPED WITH REVERSA System Troubleshooting Charts
ELECTRIC PROTECTIVE SYSTEM FOR ENGINES EQUIPPED WITH REVERSA Procedure A
ELECTRIC PROTECTIVE SYSTEM FOR ENGINES EQUIPPED WITH REVERSA Procedure B
ELECTRIC PROTECTIVE SYSTEM FOR ENGINES EQUIPPED WITH REVERSA Procedure C
ELECTRIC PROTECTIVE SYSTEM FOR ENGINES EQUIPPED WITH REVERSA Procedure D
ELECTRIC PROTECTIVE SYSTEM FOR ENGINES EQUIPPED WITH REVERSA Procedure E
ELECTRIC PROTECTIVE SYSTEM FOR ENGINES EQUIPPED WITH REVERSA Procedure F
ELECTRIC PROTECTIVE SYSTEM FOR ENGINES EQUIPPED WITH REVERSA Procedure G
ELECTRIC PROTECTIVE SYSTEM FOR ENGINES EQUIPPED WITH REVERSA Electric Protective System Wiring Diagrams
GENERATOR SET, INDUSTRIAL AND MARINE ENGINES ELECTRIC PROTEC Systems Operation
GENERATOR SET, INDUSTRIAL AND MARINE ENGINES ELECTRIC PROTEC Electric Protective System Functional Test
GENERATOR SET, INDUSTRIAL AND MARINE ENGINES ELECTRIC PROTEC Speed Specification Chart