Usage:
1. Remove cover assembly (1) and door assembly (2) from the generator.
2. Remove the terminal marker from the regulator terminal strip. Disconnect wires (3), (5 and 6) from the terminal strip.
3. Disconnect wire (4) from the bus bar assembly. Remove all of the plastic straps that hold wire (4) in position and remove the wire from the droop transformer.
4. Remove the screws and remove droop transformer (5) from the generator.
5. Put droop transformer (5) in position on the generator and install the screws to hold it in position.
6. Install wire (4) through the droop transformer and connect wire (4) to the bus bar assembly. Install the plastic straps to hold the wire in position.
7. Connect wires (3), (5 and 6) to the regulator terminal strip. Install the terminal marker on the terminal strip.
8. Install door assembly (2) and cover assembly (1) on the generator.