SR 4 AND SRCR GENERATORS - OPERATION & MAINTENANCE Caterpillar


Generator Storage

Usage:

Storage Procedure

When a generator is in storage for any length of time, moisture condenses in the windings. Minimize the condensation by use of a dry storage space and space heaters.

If a brush-type generator (SRCR) is to be in storage for a year or more, lift the brushes off the slip ring to prevent damage to the slip ring by chemical action.

After Storage

NOTE: Test the main stator windings with a megohmmeter in the following situations:

1. Before initial startup of generator set.
2. Every 3 months* if generator is operating in a humid environment.
3. If generator has not been run under load for 3 months* or more.

The megohmmeter test is described in Service Manuals SENR2180 or SENR7968. A reading of 1 meghom or less indicates that the winding has absorbed too much moisture.

To remove moisture caused by high humidity, use one of the following methods to make the generator dry:

1. Energize space heaters in generator if so equipped.
2. Put the generator in an oven at a temperature of not more than 85°C (185°F) for four hours.


NOTICE

If an oven is used for drying, use a forced air type rather than a radiant type. Radiant ovens can cause localized overheating.


3. Space heaters of the same type used in marine applications, can be installed on generators. (See the Parts Book.) These heaters heat the windings to remove moisture and should be connected at all times in high humidity conditions whenever the generator is not running.
4. Use a canvas enclosure around the generator and heating lamps to increase the temperature. Make an opening in the top for release of moisture.
5. Send a low voltage current through the windings to increase the temperature of the windings. Do not exceed 85°C (185°F).

If the megohmmeter test reads under 1 megohm after the drying or if it goes below 1 megohm shortly after drying, contact your Caterpillar dealer. The insulation has deteriorated and should be reconditioned.


*This is a guideline only. It may be necessary to megger more frequently if environment is extremely humid, salty or if the last megger test was close to 1 megohm.

Caterpillar Information System:

SR 4 AND SRCR GENERATORS - OPERATION & MAINTENANCE Standby Electric Sets
SR 4 AND SRCR GENERATORS - OPERATION & MAINTENANCE Stopping
SR 4 AND SRCR GENERATORS - OPERATION & MAINTENANCE Electronic (2301) Governor
SR 4 AND SRCR GENERATORS - OPERATION & MAINTENANCE Parallel Operation of Governors
SR 4 AND SRCR GENERATORS - OPERATION & MAINTENANCE Parallel Operation of Governors
SR 4 AND SRCR GENERATORS - OPERATION & MAINTENANCE Circulating Currents
SR 4 AND SRCR GENERATORS - OPERATION & MAINTENANCE Load Division-(Speed Droop)
SR 4 AND SRCR GENERATORS - OPERATION & MAINTENANCE Parallel Operation
SR 4 AND SRCR GENERATORS - OPERATION & MAINTENANCE Single Unit Operation
SR 4 AND SRCR GENERATORS - OPERATION & MAINTENANCE Oilfield Generator
SR 4 AND SRCR GENERATORS - OPERATION & MAINTENANCE Generator Set Control Panel (If Equipped)
SR 4 AND SRCR GENERATORS - OPERATION & MAINTENANCE Generator Set Control Panel (If Equipped)
SR 4 AND SRCR GENERATORS - OPERATION & MAINTENANCE Generator Lubrication and Maintenance
SR 4 AND SRCR GENERATORS - OPERATION & MAINTENANCE Generator Lubrication and Maintenance
SR 4 AND SRCR GENERATORS - OPERATION & MAINTENANCE Generator Lubrication and Maintenance
SUPPLEMENT TO OPERATION & MAINTENANCE INSTRUCTIONS FOR MACHINES POWERED Introduction
SUPPLEMENT TO OPERATION & MAINTENANCE INSTRUCTIONS FOR MACHINES POWERED Starting the Engine
SUPPLEMENT TO OPERATION & MAINTENANCE INSTRUCTIONS FOR MACHINES POWERED When Required
3304 and 3306 Industrial and Generator Set Engines Foreword
3304 and 3306 Industrial and Generator Set Engines Model Views
3304 and 3306 Industrial and Generator Set Engines Safety
3304 and 3306 Industrial and Generator Set Engines Before Starting
3304 and 3306 Industrial and Generator Set Engines Starting the Engine
3304 and 3306 Industrial and Generator Set Engines Operating the Engine
Back to top
The names Caterpillar, John Deere, JD, JCB, Hyundai or any other original equipment manufacturers are registered trademarks of the respective original equipment manufacturers. All names, descriptions, numbers and symbols are used for reference purposes only.
CH-Part.com is in no way associated with any of the manufacturers we have listed. All manufacturer's names and descriptions are for reference only.