COPY OF OWNER NOTIFICATION FOR U.S. AND CANADIAN OWNERS XYZ Corporation 3240 Arrow Drive Anywhere, YZ 99999 PRIORITY - PRODUCT IMPROVEMENT PROGRAM FOR UPDATING THE FUEL RELAY CIRCUIT ON EMCP3 CONTROLS MODELS INVOLVED - 3406C, 3412, C15, AND C18 GENSET PACKAGES Dear Caterpillar Product Owner: The existing 208-9270 Transorb can cause damage to relay 2 in the EMCP3 controller and needs to be updated on certain 3406C, 3412, C15, and C18 genset packages. You will not be charged for the service performed. Contact your local Caterpillar dealer immediately to schedule this service. The dealer will advise you of the time required to complete this service. Please refer the dealer to their Service Letter dated 05Aug2009 when scheduling this service. We regret the inconvenience this may cause you, but urge you to have this service performed as soon as possible to prevent unscheduled downtime. Caterpillar Inc. Identification #(s) Attached to 05Aug2009 Service Letter
Group Number 1
Refer to appropriate service manual as necessary. 1. Isolate Genset before commencing any work on the unit, open Genset breaker, activate Emergency Stop, disconnect the auxiliary power supply for battery charger and heaters, and disconnect battery cables. Ensure health and safety requirements are adhered to at all times. Also, ensure proper Lock Out-Tag Out procedures are followed at all times while work is being performed on the machine. Lock out generator before commencing any type of work. 2. Open control panel door and locate CR relay and remove the 208-9270 Transorb. Refer to Image 1.1.1 and Image 1.1.2. No replacement diode is required.
Image1.1.1
Image1.1.2
3. Clear generator area, reconnect batteries, and release emergency stop. 4. Run functional No Load test on Genset.
Group Number 2
Refer to appropriate service manual as necessary. 1. Isolate Genset before commencing any work on the unit, open Genset breaker, activate Emergency Stop, disconnect the auxiliary power supply for battery charger and heaters, and disconnect battery cables. Ensure health and safety requirements are adhered to at all times. Also, ensure proper Lock Out-Tag Out procedures are followed at all times while work is being performed on the machine. Lock out generator before commencing any type of work. 2. Open control panel door and locate CR relay and remove the 208-9270 diode see Image 2.1.1 and Image 2.1.2. No replacement diode is required.
Image2.1.1
Image2.1.2
3. Clear generator area, reconnect batteries, and release emergency stop. 4. Run functional No Load test on Genset.