Specifications
Show/hide table
车型 | UPS 250 | UPS 150 | UPS 300 |
---|---|---|---|
额定功率 | 250 kVA | 150 kVA | 300 kVA |
225 kW | 120 kW | 240 kW | |
输入 | |||
电压 | 380/400/415 +10 % / −15 %(可编程)(1) | 480 +10 %/−15 %(可编程) | |
频率 - 标称 | 50 Hz 或 60 Hz | 60 HZ | |
输入电流 - 标称安培数 | 355/337/325 | 152 | 299 |
输入电流 - 最大安培数 | 400 | 320 | 440 |
非连续电流 | 420 | 320 | 420 |
功率因子 | 额定负载和标称电压下为 0.99 | ||
谐波电流畸变 | |||
线性负载 | 100% 线性负载时小于 3% | ||
非线性负载 | 100% 非线性负载时小于 8% | ||
电涌耐受力 | 符合 IEEE 587/A NSI C62.41 | ||
接渡 | 1 至 10 秒(可编程) | ||
输出 | |||
频率 - 标称 | 输入同步(正常工作)标称 ±0.2 % 自由运转 | ||
电流 | 380/361/348 | 181 | 361 |
电压 - 标称安培 | 与输入相同 | ||
电压调节 | |||
稳态 | +/-10%输入和平衡或不平衡负载时为 +/-1% | ||
飞轮模式 | 稳态平衡或不平衡负载时为 +/-1% | ||
瞬态 | 50ms 以内的 100% 负载突变为 +/-5% | ||
电压畸变 | 线性负载时低于 3%,100% 非线性负载时低于 5% | ||
过载能力-(正常工作) | |||
1000% | 10 毫秒 | ||
高达 150% | 2 分钟 | ||
高达 125% | 10 分钟 | ||
物理数据(2) | |||
效率 | 98% | 97% | 98% |
排热(BTU/ Hr) | 19946 | 16940 | 20992 |
标称/最坏情况 | |||
深度 | 34.0 in (865 mm) | ||
宽度 | 64.6 in (1, 641 mm) | ||
总高度 | 78 in (1980 mm) | ||
配重 | 4835 lb. (2194 kg) | ||
缆线进出位置 | 顶部或底部 | ||
环境 | |||
温度 | |||
营业 | |
||
存放 | |
||
湿度 | 5% 至 95%(非冷凝) | ||
海拔高度 | 高达 1000 m (3280 ft.)(高海拔的降额工作温度范围) | ||
可听噪声 | 小于 70 dBA,在 |
||
辐射和抗扰性 | FCC A 类,第 15 部分,第 J 子部分 |
Show/hide table
(1) | ± 380V 时最多 10% |
(2) | 4 线配置的重量和尺寸 |
Show/hide table
UPS 150 | ||
---|---|---|
负载百分比 | kW | 承载时间 |
100 | 120 kW | 27 秒 |
75 | 90 kW | 36 秒 |
50 | 60 kW | 52 秒 |
25 | 30 kW | 87 秒 |
Show/hide table
UPS 250 | ||
---|---|---|
负载百分比 | kW | 承载时间 |
100 | 225 | 15 秒 |
75 | 169 | 20 秒 |
50 | 112.5 | 30 秒 |
25 | 57 | 56 秒 |
Show/hide table
UPS 300 | ||
---|---|---|
负载百分比 | kW | 承载时间 |
100 | 240 kW | 14 秒 |
75 | 180 kW | 19 秒 |
50 | 120 kW | 28 秒 |
25 | 60 kW | 52 秒 |
Caterpillar Information System:
UPS 250 and UPS 300 Uninterruptible Power Supplies System Description
UPS 250 and UPS 300 Uninterruptible Power Supplies Model View Illustrations
UPS 250 and UPS 300 Uninterruptible Power Supplies Electrical System
UPS 250 and UPS 300 Uninterruptible Power Supplies Fire Prevention and Explosion Prevention
UPS 250 and UPS 300 Uninterruptible Power Supplies General Hazard Information
UPS 250 and UPS 300 Uninterruptible Power Supplies Safety Signs and Labels
Zip-Tie Installation Guide{0374, 0599, 7000} Zip-Tie Installation Guide{0374, 0599, 7000}
G3606 and G3608 Engines Engine Oil Filler - Remove and Install
3500 Generator Sets with Dynamic Gas Blending Maintenance Interval Schedule - Standby
3500 Generator Sets with Dynamic Gas Blending Maintenance Interval Schedule - Prime
C8.7 Marine Engine Exhaust Manifold - Remove and Install
C7.1 Commercial Marine Engine Coolant Contains Oil
UPS 250 and UPS 300 Uninterruptible Power Supplies Generator Set Start Module
UPS 250 and UPS 300 Uninterruptible Power Supplies UPS View Software
UPS 250 and UPS 300 Uninterruptible Power Supplies Modem
UPS 250 and UPS 300 Uninterruptible Power Supplies Ethernet Interface
UPS 250 and UPS 300 Uninterruptible Power Supplies Remote Status Panel
UPS 250 and UPS 300 Uninterruptible Power Supplies Additional Features
UPS 250 and UPS 300 Uninterruptible Power Supplies Information Plate
UPS 250 and UPS 300 Uninterruptible Power Supplies Serial Number Plate
C7.1 Commercial Marine Engine Coolant Level Is Low
UPS 250 and UPS 300 Uninterruptible Power Supplies Acronyms
UPS 250 and UPS 300 Uninterruptible Power Supplies Symbols
UPS 250 and UPS 300 Uninterruptible Power Supplies Receiving and Handling