Troubleshooting Procedure for the AGC-4 Generator Controller{4490} Caterpillar


Troubleshooting Procedure for the AGC-4 Generator Controller{4490}

Usage:

PMG3516 JKK
Power Module:
PM3516 (S/N: NBR1-UP)
PMG3516 (S/N: JKK1-UP)

Introduction

This Special Instruction provides basic troubleshooting procedures for the AGC-4 controller. Do not perform this procedure until you have read and understand the information.

Safety Section


NOTICE

Installing and operating the controller involves working with dangerous currents and voltages. The installation must only be performed by authorized personnel who have been trained to work with live electrical equipment.


Note: When working with the controller there are hazardous live currents and voltages. Do not touch any AC measurement inputs as the inputs could lead to serious injury or death.


NOTICE

The DEIF controller must not be tampered with by unauthorized personnel. If the controller is opened, the warranty becomes void.



NOTICE

The controller is delivered from the factory with default factory settings. The settings are based on average values and are not necessarily the correct settings for the engine/generator set. Check the settings before running the engine/generator set.


Troubleshooting Procedure

Navigating the Display




Illustration 1g03733279

(1) Stop button

(2) Start button

(3) Info button

(4) Alarm lamp

(5) Select button

(6) Remote button

(7) Local button

(8) Breaker open/close button

To change the controller mode, press remote (6) or local (7) button. The genset is controlled remotely by the power management system in the "REMOTE" mode. In "LOCAL" mode the genset is controlled directly by the display.

Press breaker open/close (8) once to close the breaker. When the breaker is closed the green "ON" lamp will be illuminated. Press breaker open/close (8) again to open the breaker. With the breaker open the green "ON" lamp will turn off.

To acknowledge alarms, use the arrow keys to place the cursor under "ACK" on the display screen and press select button (5). Acknowledging the alarm will turn on alarm lamp (4). Unacknowledged alarms cause the alarm lamp (4) to flash

Symptom Based Troubleshooting

Table 1
Symptom     Probable Cause     Repair    
Display (DU-2) is not working     Bad connection or no connection from the AGC-4 controller to the DU-2 display     Check the wiring, ensure that connectors are connected, and pins are secured    
No power supply Verify 24 V power on terminals 1-2 and 98-99    
The AOP-1 is not working     Bad or no connection from the AGC-4 controller to the DU-2 display     Check the wiring, ensure that connectors are connected, and pins are secured    
Bad or no connection from the DU-2 display to the AOP-1. Ensure that the ethernet cable is securely connected at both ends    
The AOP-1 is not programmed Program the AOP-1 using the DEIF Utility Software.    
AGC-4 controller does not power up     No power supply     Verify 24 V power on terminals 1-2 and 98-99    
Internal fault in the AGC-4 Check whether the Self check OK LED is green. If the lamp is not green, and the 24 V supply on terminals 1-2 is OK, then replace the controller    
Analog load sharing is not working     Voltage higher than 15V DC has been connected to the load sharing terminals     Replace the controller    
Analog load sharing line is short-circuited Check the analog load sharing line. Remove the fault    
No Ethernet connection (Ethernet error     The AGC-4 controller has overheated     Reboot the controller    
Internal fault in the AGC-4
Bad or no Ethernet connection to the AGC-4 Check the Ethernet cable (straight or twisted)    
Controller is losing/changing parameters or options     The AGC-4 controller has overheated     1. Reboot the AGC-4 controller
2. Reload the backup of the batch file. If the problem persists, replace the control?le    
Relay output is not working     Relay is welded together     Replace the controller    
Relay is burnt out
CAN bus A and/or B is not working     The CAN bus line is longer than 300 m (984 ft)     The total cable length exceeds the maximum distance. Shorten the CAN bus line    
The CAN bus line is not terminated with 120 ohm resistors Connect a 120 ohm resistor between Can HI and LO at each end of the CAN bus line    
J1939 Engine Communication (CAN bus) is not working     The CAN bus line is short-circuited     Check the CAN bus line. Remove the fault.    
There is no power supply on terminals 98-99 Check the 24 V power supply on terminals 98-99.    
CAN bus line is not end terminated with 120 ohm resistors Connect a 120 ohm resistor between Can HI and LO at AGC-4 end of the CAN bus line. Note: Some equipment has a built-in 120 ohm end resistor    
Digital input is not working     Wiring fault     Check the voltage between the input terminal and the input common. The input should be between 8 and 32 V when the input is activated    
Input is burnt out Replace the controller    
Analog input is not working     Wiring fault     Check the analog signal between input terminal and input common    
Input is burnt out Replace the controller    
Analog output is not working     Wiring fault     Disconnect the wiring and check the output value using a multimeter    
Output has been overloaded and damaged Replace the controller    
Start prepare/Run coil output is not working     Wiring fault     Check the wiring diagram for the correct circuit    
Output relay is welded together or burnt out Replace the controller    
Internal communication error (Int. Comm. Fail)     No power supply on terminals 98-99     Check the 24V DC power supply on terminals 98-99    
Internal fault in the AGC-4 Replace the controller    
Genset does not start     EMCP not in "AUTO"mode     Place the EMCP in "AUTO" mode    

Interface Testing Procedures

Option M12:13 x DI, 4 x DO (slot 3)




Illustration 2g03733546

Typical example of the Inputs/outputs icon

Connect to the AGC-4 controller using the DEIF Utility Software. In the utility software, click the "Inputs/Outputs" tab on the left menu, as shown above.

Option M15: 4 × 4 to 20 mA (slot 6/8)




Illustration 3g03733558

Connect to the AGC-4 controller using the DEIF Utility Software. In the utility software, click "Show/Hide" the real-time readings window icon on the top menu bar, as shown above.

In the utility software, the Data tracer window opens. Click "Add". Select "Analogue 91, 93, 95 and 97 (slot 6)" and "Analogue 127, 129, 131 and 133 (slot 8)" and then click "OK". The analogue value of each input is shown.

If the values for all inputs are zero, then this option is not interfacing with the main controller. Try disconnecting one of the connected sensors. The value should now be negative.

Option EF6: PWM, 2 × +/-25 mA (slot 4)

PMW Governor (GOV) Output

Use an oscilloscope or multi-meter to measure the PWM output on terminals 69-70. If the measured value is above 0% (0% ON, 100% OFF) then the option is working.

If this output is 0% (0% ON, 100% OFF) then adjust parameter "2550 GOV output offset" to 100%. Be sure that nominal setting 1 is selected in menu 6006, and the controller is in REMOTE or LOCAL mode. If the output is still 0%, then this option is not working and the controller needs to be replaced.

Automatic Voltage Regulator (AVR) Output

Use a multi-meter to measure the output on terminals 71-72. If the measured value is above or below zero then the option is working. (The output is a +/- 25 mA output converted to voltage with a resistor across terminals 71-72.)

If the output is zero then adjust parameter "2670 AVR output. offset" to 100%. Be sure that nominal setting 1 is selected in menu 6006, and the controller is in REMOTE or LOCAL mode. If the output is still zero, then this option is not working and the controller needs to be replaced.

Option H5: CAN Engine Interface (slot 2)

Using the display, go to SETUP > SYST > COMM. Press the "Up" button until parameter "7560 Engine I/F" is visible. If this parameter is visible, then the option is activated.

Troubleshooting Alarms

Common Alarms

Table 2
Issue     Cause    
GB Close Fail     The controller activated the signal to close the breaker, but breaker position feedback did not change state    
GB Open Fail     The controller activated the signal to open the breaker, but breaker position feedback did not change state    
GB Position Fail     No feedback for breaker position (terminals 26 and 27). Alternatively, feedback on both open (terminal 26) and closed (terminal 27) breaker positions or feedback on both open (terminal 26) and closed (terminal 27) breaker positions    
Int. Comm. Fail     The controller has lost communication with the engine interface PCB. Check whether there is 24V DC on terminals 98 (+) and 99 (-). If voltage is present and the connector is seated correctly, the AGC-4 controller may have a fault. Replace the controller.    
Start Failure     The controller has performed three start attempts, but the genset failed to start.    
Stop Failure     The controller has commanded the genset to stop, however running feedback is still present    
Running Feed-back Fail     The generator is running, but running feedback is not present    
Generator Breaker (GB) External Trip     The breaker has been tripped manually by the breaker protection settings    

Table 3
Alarm     Alarm Text     Description     Possible Causes    
1000     -P> 1     Reverse power     Lack of fuel, clogged fuel filters, and so on. The engine was shut down without tripping the GB governor regulation failure    
1010     _-P> 2    
1030     I> 1     Over current     High load short circuit    
1040     _I> 2    
1050     _I> 3    
1060     _I> 4    
1090     G I> inv.     Inverse time overcurrent     High load short circuit    
1110     G Iv>     Voltage-dependent overcurrent     High load short circuit    
1130     I>> 1     Fast overcurrent     High load short circuit    
1140     _I>> 2    
1150     G U> 1     Generator overvoltage     AVR regulation failure high grid voltage (if parallel to grid)    
1160     _G U> 2    
1170     G U< 1     Generator under voltage     AVR regulation failure Low grid voltage (if parallel to grid)    
1180     _G U< 2    
1190     _G U< 3    
1210     G f> 1     Generator over frequency     Governor regulation failure High grid frequency (if parallel to grid)    
1220     _G f> 2    
1230     _G f> 3    
1240     G f< 1     Generator under frequency     Governor regulation failure Low grid frequency (if parallel to grid)    
1250     _G f< 2    
1260     _G f< 3    
1270     BB U> 1     Bus bar over voltage     High grid voltage    
1280     _BB U> 2    
1290     _BB U> 3    
1300     BB U< 1     Bus bar under voltage     Low grid voltage    
1310     _BB U< 2    
1320     _BB U< 3    
1330     _BB U< 4    
1350     BB f> 1     Bus bar over frequency     High grid frequency    
1360     _BB f> 2    
1370     _BB f> 3    
1380     BB f< 1     Bus bar under frequency     Low grid frequency    
1390     _BB f< 2    
1400     _BB f< 3    
1410     _BB f< 4    
1450     P> 1     Generator overload     High load    
1460     _P> 2    
1470     _P> 3    
1480     _P> 4    
1490     _P> 5    
1500     Unbalance I 1     Generator unbalanced current     Unbalanced phase-phase loads    
1510     G Unbalance U     Generator unbalanced voltage     Unbalanced phase-neutral loads    
1520     -Q>     Loss of excitation     AVR regulation failure    
1530     Q>     Over excitation    
1540     Neg. seq. I     Negative sequence current     Unbalanced phase-phase loads    
1550     G neg. seq. U     Negative sequence voltage     Unbalanced phase-neutral loads    
1570     Zero seq. I     Zero sequence current     Earth fault    
1580     G zero seq. U     Zero sequence voltage    
1620     BB Unbalance U     Bus bar unbalanced voltage     Unbalanced phase-phase loads    
1710     Unbalance I 2     Bus bar unbalanced current     Unbalanced phase-neutral loads    
1761     G P dep. Q<     Power dep. reactive power import     Loss of excitation AVR regulation failure    
1791     G P dep. Q>     Power dep. reactive power ex-port     Overload Over excitation AVR regulation failure    
1981     GB Ext. tripped     Generator breaker externally tripped     GB was manually tripped due to the breaker protection settings    

Genset Does Not Start

If the controller does not start the genset follow the troubleshooting steps listed below.

  1. Ensure that the EMCP is in "AUTO" mode.

  1. Check that the AGC-4 "Self Check OK" lamp is green. If the lamp is not green, replace the controller.

  1. Check the display for alarms. The "Start Failure" alarm should be present as it confirms that the AGC-4 has attempted to start the genset three times.

    If the controller is in "REMOTE" mode and no alarms are present, check the settings and/or replace the controller.

  1. If the "Start Failure" alarm is present, switch the controller to "LOCAL" mode using the display panel.

  1. If the "Start Failure" alarm is present, switch the controller to "LOCAL" mode using the display panel.

    1. Acknowledge all alarms.

    1. Verify that there is 24 V on terminal 118.

    1. Press the "START" button on the display panel.

    1. Check for 24 V on terminal 119 while cranking the engine.

      Note: There is a short delay between pressing the "START" button and the 24 V supply on terminal 119.

If continuity is present when the AGC-4 attempts to start the genset, the problem is external to the controller. Troubleshoot the system outside of the controller.

If continuity is not present, replace the controller.

Breaker Closing Problems

If the generator breaker does not close as expected, or if there is a breaker alarm follow the steps below.

  1. If the engine starts but the generator does not close, check the display for any alarms. If there are no alarms and the controller is in "REMOTE" mode, check the controller settings. Repair or replace the controller as necessary.

  1. If there is a "GB Close Gail" alarm or any other alarm, acknowledge the alarms, start the genset, and press the breaker close button on the display while in "LOCAL" mode.

  1. Check for continuity on terminals 17-18 on the AGC-4.

    Note: The signal on terminals 17-18 will be a pulse signal.

    If continuity is present when the controller attempts for send the close command, the problem is external to the controller and further troubleshooting is necessary.

    If no continuity is present, replace the controller.

Replacing the AGC-4 Controller

Follow the steps below in order to replace the controller.

  1. Connect to the faulty controller to a laptop with the DEIF utility software using an ethernet or usb cable.

  1. Supply the controller with 24 V power on terminal 1 and ground terminal (2) .

  1. Save the batch file from the controller. If you cannot save the batch file, then save one from a similar generator set.

    Note: Update the genset, running hours and so on, after uploading the batch file.

  1. Isolate the bus bar measurement terminals by removing the fuses and activating the local E-stop on the genset.

  1. Disconnect the controller power.

  1. Disconnect the display panel.

  1. Disconnect all of the green terminal blocks from the faulty controller.

  1. Remove the controller mounting screws from the switchboard.

  1. Install the new controller, attach the controller to the switchboard using the screws removed in Step 8.

  1. Connect the controller to 24 V power.

  1. Connect the new controller to a laptop computer with the DEIF utility software using an ethernet or USB cable.

  1. Download the saved batch file to the new controller.

  1. Connect the controller to the display panel.

  1. Put the controller in "LOCAL" mode and press the "START" button to verify genset operation.

  1. After verifying that the controller is operating properly, stop the genset and put the AGC-4 in "REMOTE" mode.

Caterpillar Information System:

794 AC Off-Highway Truck Final Drive Oil - Change
Spring Isolator Installation and Adjustment Procedure for Certain Generator Sets with 3500 Gas Engines{1021, 7002} Spring Isolator Installation and Adjustment Procedure for Certain Generator Sets with 3500 Gas Engines{1021, 7002}
XQC1200 and XQC1600 Power Modules Generator - Remove and Install
C7.1 Marine Engine Engine Coolant Pressure Sensor
CAT Water Delivery System (WDS) and 785D WTR OEM Off-Highway Truck/Tractor Gear Pump (Charge) - Remove and Install
CAT Water Delivery System (WDS) and 777G WTR OEM Off-Highway Truck/Tractor Piston Pump (Water Delivery) - Remove and Install
C3.4B Engines ECM Memory - Test
UPS 1000Z, UPS 1200Z, UPS500G and UPS600G Uninterruptible Power Supplys Maintenance Interval Schedule
CAT Water Delivery System (WDS) and 785D WTR OEM Off-Highway Truck/Tractor Control Valve (Water) - Assemble
C7.1 Marine Engine Engine Lifting Bracket
C7.1 Marine Engine Belt Tensioner
C7.1 Marine Engine Crankcase Breather
Air Conditioning and Heating R134a for All Cat Machines General Information
Air Conditioning and Heating R134a for All Caterpillar Machines General Troubleshooting Information
C18 Fire Pump Engine Engine Electronics
C18 Fire Pump Engine Model View Illustrations
CAT Water Delivery System (WDS) and 777G WTR OEM Off-Highway Truck/Tractor Pump Drive - Assemble
3516C and C175-16 Engines Selective Catalytic Reduction Configuration Parameters
C3.4B Engines Electrical Power Supply - Test
C7.1 Marine Engine Flywheel Housing
C7.1 Marine Engine Flywheel
C7.1 Marine Engine Turbocharger
C7.1 Marine Engine Fuel Injection Lines
C7.1 Marine Engine Fuel Filter Base
Back to top
The names Caterpillar, John Deere, JD, JCB, Hyundai or any other original equipment manufacturers are registered trademarks of the respective original equipment manufacturers. All names, descriptions, numbers and symbols are used for reference purposes only.
CH-Part.com is in no way associated with any of the manufacturers we have listed. All manufacturer's names and descriptions are for reference only.