Password
- Refer to Operations and Maintenance Manual, SEBU7464, "Using Computer Software" for information on loading software.
A screen that is similar to illustration 1 will appear after the software is loaded.
Illustration 1 | g00856208 |
- Select "Enter Password" menu option. Refer to illustration 1.
- Enter a valid username. Enter a valid password. Click on "OK". Refer to illustration 2.
Illustration 2 | g00787622 |
Nominal Voltage - Set
Note: This procedure is needed for each MMU that is in the system.
- Refer to Operations and Maintenance Manual, SEBU7464, "Using Computer Software".
- Navigate to "Op. Params. Op. Group 1: Nominal Voltage". Select "Nominal Voltage" from the drop-down menu. Refer to illustration 3.
Illustration 3 | g01100882 |
- Enter the new value that is required by your system in the "Enter new value for Nominal Voltage" box. Refer to illustration 4.
Note: This value must match the settings for the transformer voltage tap. Refer to Operation and Maintenance Manual, "Transformer Voltage Setup".
Illustration 4 | g00856284 |
- Click the "Send" button.
After the "Send" button has been selected, a text message in the UPS View window confirms the setting of a new "Nominal Voltage" value. Refer to illustration 5.
Illustration 5 | g01100933 |
- Repeat steps 1 through 4 for each MMU.
The Nominal Voltage is now set.
Setting the "Automatic Voltage Regulator Seed"
Note: The "Automatic Voltage Regulator Seed" parameter is only valid on Revision E or earlier versions of Firmware. To change this parameter, you will need to contact Caterpillar Technical Support for a password.
Note: This procedure is needed for each MMU that is in the system.
- Refer to Operations and Maintenance Manual, SEBU7464, "Using Computer Software".
- Navigate to "Op. Params. Op. Group 12: Tuning Parameter 1" and select "AVR Seed" from the drop-down menu. Refer to illustration 6.
Illustration 6 | g01100939 |
- Enter the new value that is required by your system in the "Enter new value for AVR Seed" box. Refer to illustration 7.
Show/hide table
Table 1 Operating Parameter     50 HZ     60 HZ     "AVR Seed"     766     920    
Illustration 7 | g00856308 |
- Click on the "Send" button.
After the "Send" button has been selected, a message in the message area of the UPS View window will confirm the setting of the new value for the "AVR Seed".
- Repeat steps 1 through 4 for each MMU.
The "Automatic Voltage Regulator Seed" is set.
Frequency - Set
Note: Change the Operating Parameters only if it is necessary to change the frequency from 50 Hz to 60 Hz or 60 Hz to 50 Hz operation.
Note: This procedure is needed for each MMU that is in the system.
- Refer to Operations and Maintenance Manual, SEBU7464, "Using Computer Software".
- Navigate to "Op. Params. Op. Group 1: Nominal Voltage" and select "Over Frequency Trip" from the drop-down menu. Refer to illustration 8.
Illustration 8 | g01100950 |
- Enter the new value that is required by your system in the "Enter new value for Over Frequency Trip" box. Refer to illustration 9.
Show/hide table
Table 2 Operating Parameter     50 HZ     60 HZ     "Over Frequency Trip"     51.5     62    
Illustration 9 | g00856316 |
- Click the "Send" button.
After the "Send" button is selected, a message in the message area of the UPS View window will confirm the setting of the new "Over Frequency Trip" value.
- Navigate to "Op. Params. Op. Group 1: Nominal Voltage" and select "Under Frequency Trip" from the drop-down menu. Refer to illustration 10.
Illustration 10 | g01100987 |
- Enter the new value that is required by your system in the "Enter new value for Under Frequency Trip" box. Refer to illustration 11.
Show/hide table
Table 3 Operating Parameter     50 HZ     60 HZ     "Under Frequency Trip"     48.5     58    
Illustration 11 | g00856322 |
- Click the "Send" button.
After the "Send" button has been selected, a message in the message area of UPS View window will confirm the setting of the new "Under Frequency Trip" value.
The parameter for setting the frequency is set.
"Internal CAN Enable" Set
Note: This procedure is for configuring the communications between the PC and the UPS after the initial start-up of the PC.
Note: During the initial start-up of communications, ignore any alarms until the start-up procedures for communications are complete.
Internal CAN Enable
Illustration 12 | g01100989 |
- Click on "Op Params.".
- Click on "Op. Group 5: Internal CAN Enable".
- Click on "Internal CAN Enable".
- Set "Internal CAN Enable" to 1.
Illustration 13 | g00931707 |
- Click on "Send".
"Internal CAN Node ID"
- Click on "Op Params.".
- Click on "Op. Group 5: Internal CAN Enable".
- Click on "Internal CAN Node ID".
Illustration 14 | g00931843 |
- Set the "Internal CAN Node ID" for the sequentially numbered MMU that is indicated by the Selector Switch (MMU). Refer to Operations and Maintenance Manual, SEBU7464, "Using Computer Software".
Illustration 15 | g00931842 |
- Click on "Send".
"UPS Net Enable"
- Click on "Op Params.".
- Click on "Op. Group 5: Internal CAN Enable".
- Select "UPS Net Enable".
Illustration 16 | g00932066 |
- Set "UPS Net Enable" to 1.
- Click on "Send".
UPS View Baud Rate
- Click on "Op Params.".
Illustration 17 | g00932106 |
- Click on "Op. Group 5: UPS Net Enable".
- Set "UPS View Baud Rate" to 38400.
- Click "Send".
- Proceed to "The Setting of the "Model Index"".
"Model Index" Set
MODEL     | DESCRIPTION (number of MMU(s))     | FREQUENCY     | "MODEL INDEX"     | SYSTEM CAPACITY (kW)     | S/N PREFIX     |
UPS300     | 1 MMU     | 60 Hz     | 0     | 240     | CNJ     |
UPS250     | 1 MMU     | 50 Hz     | 1     | 200     | APZ     |
UPS300E     | 1 MMU Upgradeable     | 60 Hz     | 2     | 240     | CPZ     |
UPS250E     | 1 MMU Upgradeable     | 50 Hz     | 3     | 200     | CNM     |
UPS300R     | 1 MMU plus 1 MMU     | 60 Hz     | 4     | 240     | CPZ     |
UPS250R     | 1 MMU plus 1 MMU     | 50 Hz     | 5     | 200     | CNM     |
UPS600     | 2 MMU(s)     | 60 Hz     | 6     | 480     | CTX     |
UPS500I     | 2 MMU(s)     | 50 Hz     | 7     | 400     | CSE     |
UPS600R     | 2 MMU(s) plus 1 MMU     | 60 Hz     | 8     | 480     | CTX     |
UPS500R     | 2 MMU(s) plus 1 MMU     | 50 Hz     | 9     | 400     | CSE     |
UPS900     | 3 MMU(s)     | 60 Hz     | 10     | 720     | CRY     |
UPS750I     | 3 MMU(s)     | 50 Hz     | 11     | 600     | CPZ     |
UPS900R     | 3 MMU(s) plus 1 MMU     | 60 Hz     | 12     | 720     | CRY     |
UPS750R     | 3 MMU(s) plus 1 MMU     | 50 Hz     | 13     | 600     | CPZ     |
- Refer to Operations and Maintenance Manual, SEBU7464, "Using Computer Software".
- Navigate to "Op. Params. Op. Group 6: Model Index" and select "Model Index" from the drop-down menu. Refer to illustration 18.
Illustration 18 | g01100994 |
- Enter the new value that is required by your system in the "Enter new value for Model Index" box. Refer to table 4.
Illustration 19 | g00856330 |
- Click the "Send" button.
After the "Send" button has been selected, a message in the message area of UPS View window will confirm the setting of the new "Model Index" value.
- Push the "CTRL" key and the "R" key on the PC sequentially.
Note: This will reset the processor.
- Press the "Y" key in order to answer yes.
Note: Steps 2 through 4 may need to be repeated if the programming is not completed.
- Repeat "Internal CAN Enable" and ""Model Index" Set" for each additional MMU in your system.
Setting the Operating Parameters for UPS Net
Illustration 20 | g00935236 |
Note: The following procedure must be performed for each MMU.
- Connect a PC to the "RS-232/RS-485" port of the MMU that needs to be setup. The port is located on the bottom corner of the System I/O (SIO) Board in the MMU. This must be accomplished prior to the application of high voltage to the system.
Illustration 21 | g00935211 |
- Verify that the jumper "J1" on the System I/O (SIO) Board is in the proper position. UP is for "RS-485" and DOWN is for" RS-232". The default setting is DOWN.
- Verify that the input voltage to the MMU is correct.
- Verify that the phase rotation to the MMU is correct.
- Close the high voltage inputs to the MMU that is being setup.
- Click on the "Enter Password" menu option in order to obtain the "Enter User Name/Password" dialog box.
Note: The system will start. The system will remain in BYPASS. The PC should be communicating with the MMU.
- Enter a valid username. Then, enter a valid password.
- Select "Op. Group 5: Internal CAN Enable" from the "Op. Params." menu.
- Select "Internal CAN enable" and enter a value of 1.
- Select "Op. Group 5: Internal CAN Enable" from the "Op. Params." menu.
- Select "UPS Net Enable". Enter a value of 1.
- Select "Op. Group 5: Internal CAN Enable" from the "Op. Params." menu.
- Select "Internal CAN Node ID". Enter the number that corresponds to that MMU.
- Open the high voltage inputs to the MMU.
- Disconnect the PC from the MMU.
- Return to Step 1. Repeat the process for each consecutive MMU until every MMU is completed. Then, continue to Step 17.
- Proceed to any MMU and connect a PC to the "RS-232/RS-485" port. The port is located on the bottom corner of the System I/O (SIO) Board of the MMU. This must be accomplished prior to the application of high voltage to the system.
Note: The following portion of this procedure only needs to be performed at one MMU. The following portion will update all other MMUs in the system.
- Close all high voltage inputs.
- Allow all MMUs to power up.
- Click on the "Enter Password" menu option in order to obtain the "Enter User Name/Password" dialog box.
- Enter a valid username. Then, enter a valid password.
- Select the "Op. Group 6: Model Index" from "Op. Params." menu.
- Select "Model Index". Enter the correct number from the table 4.
- Select "Op. Group 6: Model Index" from the "Op. Params." menu.
- Select "System Capacity". Enter the correct value from the table 4.
- Open the high voltage inputs to the MMU.
- Disconnect the PC from the MMU.
Ethernet Setup Procedure
- Connect a network cable from the System I/O (SIO) Board in each MMU to the Ethernet Hub that is located in the System Cabinet.
- Proceed to the MMU that needs to be set up. Connect a PC to the "RS-232/RS-485" port. The port is located on the bottom corner of the System I/O (SIO) Board in the MMU. This must be accomplished prior to the application of high voltage to the system.
- Close the high voltage inputs to the MMU that is being setup.
- Click on the "Enter Password" menu option in order to obtain the "Enter User Name/Password" dialog box.
- Click on the "Settings" menu. Select "Remote Notification Settings" and then select "Service E-mail Configuration".
Illustration 22 | g01100997 |
- Input the E-mail Address or Addresses. One to four E-mail addresses can be accepted by the system.
Illustration 23 | g00807349 |
"E-mail Configuration" |
- Click on the "Send" button in order to store the information into flash memory.
- Click on the "Receive" button in order to view the current settings that are stored in flash memory.
- Click on the "Test" button. This will send a test e-mail to the e-mail address in order to ensure that the settings are correct.
- Click on "Settings" menu. Select "Remote Notification Settings" and then select "Network Configuration".
- Input the "UPS IP Address" number.
Illustration 24 | g00807357 |
"Network Configuration" |
- Input the "Mail Server IP Address" number.
- Input the "Subnet Mask" number.
- Input the "Port Number".
- Click on the "Send" button in order to store the information into flash memory.
Note: The above settings are obtained from the Network Administrator.
- Click on the "Receive" button in order to view the current settings that are stored in flash memory.
- Click on the "Test" button. This will send a test e-mail to the e-mail addresses in order to ensure that the settings are correct.
- When all parameters have been entered press "Send" and then Exit.
- Select the "Op. Params." menu and select "Op. Group 5: Internal CAN Enable".
- Select "Network Enable" and enter a value of 1.
- Press "Cntl R" in order to reset the microprocessor.
- Press "Y" in order to confirm the reset.
Note: Each MMU must be programmed with a unique serial number for the network option to function properly.