Winding Data for 203-5749 Generator through 324-5120 Generator
203-5749 Generator
Show/hide table
MAIN STATOR AND ROTOR WINDING DATA     | |||||||
---|---|---|---|---|---|---|---|
ITEM     | STATOR     | ROTOR     | |||||
Stack Height     | 444.5 mm (17.5 inch)     |
457.2 mm (18.0 inch)     |
|||||
Slots     | 72     | -     | |||||
Coil Throw     | 1 - 10     | -     | |||||
Turns/Coil     | 5     | -     | |||||
Turns/Pole     | -     | 147.5     | |||||
No. & Wire Size     | 2 - 2.8448 mm (0.112 inch) X 5.4610 mm (0.215 inch)     |
3.6576 mm (0.144 inch) X 7.31520 mm (0.288 inch)     |
|||||
Mean Length Turn     | 1790.7 mm (70.5 inch)     |
1371.6 mm (54.0 inch)     |
|||||
Copper Weight     | 174.2 kg (384 lb)     |
294.4 kg (649 lb)     |
|||||
Inside Connection (1)     | 6 Parallel Star     | Series     | |||||
Line Leads (No. & Size)     | 36 - #4     | -     | |||||
Terminal bolt size     | 3/8 inch     | -     | |||||
Low Voltage connected line resistance at 25 ° C (77 ° F)     | 0.00801 ohms     | -     | |||||
Field lead resistance at 25 ° C (77 ° F)     | -     | 0.814 ohms     | |||||
EXCITER WINDING DATA     | |||||||
Exciter Frequency (Hz)     | 80 Hz     | Permanent Magnet Frequency     | 160 Hz     | ||||
Exciter Poles     | 8     | ||||||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | Permanent Magnet Stator     | ||||
Stack Length     | 88.9 mm (3.5 inch)     |
88.9 mm (3.5 inch)     |
31.8 mm (1.25 inch)     |
||||
Coils/Group     | -     | -     | 1     | ||||
Slots (Coils)     | 8     | 48     | 48     | ||||
Turns (Coils)     | 320     | 8     | 17     | ||||
No. & Size Wire     | 2 - #18.5     | 3 - #16     | 2 - #17     | ||||
Coil Throw     | 1 - 2     | 1 - 6     | 1 - 4     | ||||
Mean Length Turn (Calc.)     | 355.6 mm (14.0 inch)     |
419.1 mm (16.5 inch)     |
221.0 mm (8.7 inch)     |
||||
Copper Weight     | 14.0 kg (30.9 lb)     |
6.4 kg (14 lb)     |
1.8 kg (3.97 lb)     |
||||
Insulation     | Heavy Polyester Polyamide Imide     | ||||||
Connection (2)     | Series     | 2 Parallel Wye     | Series Star     | ||||
Line Leads     | 2 - #14     | 6 - #10     | 3 - #14     |
Show/hide table
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 06 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram I |
203-5751 Generator
Show/hide table
MAIN STATOR AND ROTOR WINDING DATA     | |||||||
---|---|---|---|---|---|---|---|
ITEM     | STATOR     | ROTOR     | |||||
Stack Height     | 584.2 mm (23.0 inch)     |
596.9 mm (23.5 inch)     |
|||||
Slots     | 72     | -     | |||||
Coil Throw     | 1 - 10     | -     | |||||
Turns/Coil     | 4     | -     | |||||
Turns/Pole     | -     | 147.5     | |||||
No. & Wire Size     | 2 - 3.68300 mm (0.145 inch) X 5.4610 mm (0.215 inch)     |
3.6576 mm (0.144 inch) X 7.31520 mm (0.288 inch)     |
|||||
Mean Length Turn     | 2062.5 mm (81.2 inch)     |
1648.5 mm (64.9 inch)     |
|||||
Copper Weight     | 210.5 kg (464 lb)     |
354.3 kg (781 lb)     |
|||||
Inside Connection (1)     | 6 Parallel Star     | Series     | |||||
Line Leads (No. & Size)     | 36 - #2     | -     | |||||
Terminal bolt size     | 3/8 inch     | -     | |||||
Low Voltage connected line resistance at 25 ° C (77 ° F)     | 0.00550 ohms     | -     | |||||
Field lead resistance at 25 ° C (77 ° F)     | -     | 0.980 ohms     | |||||
EXCITER WINDING DATA     | |||||||
Exciter Frequency (Hz)     | 80 Hz     | Permanent Magnet Frequency     | 160 Hz     | ||||
Exciter Poles     | 8     | ||||||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | Permanent Magnet Stator     | ||||
Stack Length     | 88.9 mm (3.5 inch)     |
88.9 mm (3.5 inch)     |
31.8 mm (1.25 inch)     |
||||
Coils/Group     | -     | -     | 1     | ||||
Slots (Coils)     | 8     | 48     | 48     | ||||
Turns (Coils)     | 320     | 8     | 17     | ||||
No. & Size Wire     | 2 - #18.5     | 3 - #16     | 2 - #17     | ||||
Coil Throw     | 1 - 2     | 1 - 6     | 1 - 4     | ||||
Mean Length Turn (Calc.)     | 355.6 mm (14.0 inch)     |
419.1 mm (16.5 inch)     |
221.0 mm (8.7 inch)     |
||||
Copper Weight     | 14.0 kg (30.9 lb)     |
6.4 kg (14 lb)     |
1.8 kg (3.97 lb)     |
||||
Insulation     | Heavy Polyester Polyamide Imide     | ||||||
Connection (2)     | Series     | 2 Parallel Wye     | Series Star     | ||||
Line Leads     | 2 - #14     | 6 - #10     | 3 - #14     |
Show/hide table
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 06 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram I |
203-5753 Generator
Show/hide table
MAIN STATOR AND ROTOR WINDING DATA     | |||||||
---|---|---|---|---|---|---|---|
ITEM     | STATOR     | ROTOR     | |||||
Stack Height     | 736.6 mm (29.0 inch)     |
749.3 mm (29.5 inch)     |
|||||
Slots     | 72     | -     | |||||
Coil Throw     | 1 - 10     | -     | |||||
Turns/Coil     | 3     | -     | |||||
Turns/Pole     | -     | 147.5     | |||||
No. & Wire Size     | 1 - 4.0640 mm (0.160 inch) X 8.6360 mm (0.340 inch)     |
3.6576 mm (0.144 inch) X 7.31520 mm (0.288 inch)     |
|||||
Mean Length Turn     | 2194.6 mm (86.4 inch)     |
1955.8 mm (77.0 inch)     |
|||||
Copper Weight     | 145.6 kg (321 lb)     |
419.6 kg (925 lb)     |
|||||
Inside Connection (1)     | 6 Parallel Wye     | Series     | |||||
Line Leads (No. & Size)     | 36 - #1     | -     | |||||
Terminal bolt size     | 3/8 inch     | -     | |||||
Low Voltage connected line resistance at 25 ° C (77 ° F)     | 0.00440 ohms     | -     | |||||
Field lead resistance at 25 ° C (77 ° F)     | -     | 1.170 ohms     | |||||
EXCITER WINDING DATA     | |||||||
Exciter Frequency (Hz)     | 80 Hz     | Permanent Magnet Frequency     | 160 Hz     | ||||
Exciter Poles     | 8     | ||||||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | Permanent Magnet Stator     | ||||
Stack Length     | 88.9 mm (3.5 inch)     |
88.9 mm (3.5 inch)     |
31.8 mm (1.25 inch)     |
||||
Coils/Group     | -     | -     | 1     | ||||
Slots (Coils)     | 8     | 48     | 48     | ||||
Turns (Coils)     | 320     | 8     | 17     | ||||
No. & Size Wire     | 2 - #18.5     | 3 - #16     | 2 - #17     | ||||
Coil Throw     | 1 - 2     | 1 - 6     | 1 - 4     | ||||
Mean Length Turn (Calc.)     | 355.6 mm (14.0 inch)     |
419.1 mm (16.5 inch)     |
221.0 mm (8.7 inch)     |
||||
Copper Weight     | 14.0 kg (30.9 lb)     |
6.4 kg (14 lb)     |
1.8 kg (3.97 lb)     |
||||
Insulation     | Heavy Polyester Polyamide Imide     | ||||||
Connection (2)     | Series     | 2 Parallel Wye     | Series Star     | ||||
Line Leads     | 2 - #14     | 6 - #10     | 3 - #14     |
Show/hide table
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 06 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram I |
203-5755 Generator
Show/hide table
MAIN STATOR AND ROTOR WINDING DATA     | |||||||
---|---|---|---|---|---|---|---|
ITEM     | STATOR     | ROTOR     | |||||
Stack Height     | 838.2 mm (33.0 inch)     |
850.9 mm (33.5 inch)     |
|||||
Slots     | 90     | -     | |||||
Coil Throw     | 1 - 12     | -     | |||||
Turns/Coil     | 2     | -     | |||||
Turns/Pole     | -     | 163.5     | |||||
No. & Wire Size     | 2 - 3.8100 mm (0.150 inch) x 8.1280 mm (0.320 inch)     |
3.6576 mm (0.144 inch) X 7.31520 mm (0.288 inch)     |
|||||
Mean Length Turn     | 2654.3 mm (104.5 inch)     |
2156.5 mm (84.9 inch)     |
|||||
Copper Weight     | 251.7 kg (555 lb)     |
513.5 kg (1132 lb)     |
|||||
Inside Connection (1)     | 6 Parallel Wye     | Series     | |||||
Line Leads (No. & Size)     | 36 - #1/0     | -     | |||||
Terminal bolt size     | 3/8 inch     | -     | |||||
Low Voltage connected line resistance at 25 ° C (77 ° F)     | 0.00293 ohms     | -     | |||||
Field lead resistance at 25 ° C (77 ° F)     | -     | 1.422 ohms     | |||||
EXCITER WINDING DATA     | |||||||
Exciter Frequency (Hz)     | 80 Hz     | Permanent Magnet Frequency     | 160 Hz     | ||||
Exciter Poles     | 8     | ||||||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | Permanent Magnet Stator     | ||||
Stack Length     | 88.9 mm (3.5 inch)     |
88.9 mm (3.5 inch)     |
31.8 mm (1.25 inch)     |
||||
Coils/Group     | -     | -     | 1     | ||||
Slots (Coils)     | 8     | 48     | 48     | ||||
Turns (Coils)     | 320     | 8     | 17     | ||||
No. & Size Wire     | 2 - #18.5     | 3 - #16     | 2 - #17     | ||||
Coil Throw     | 1 - 2     | 1 - 6     | 1 - 4     | ||||
Mean Length Turn (Calc.)     | 355.6 mm (14.0 inch)     |
419.1 mm (16.5 inch)     |
221.0 mm (8.7 inch)     |
||||
Copper Weight     | 14.0 kg (30.9 lb)     |
6.4 kg (14 lb)     |
1.8 kg (3.97 lb)     |
||||
Insulation     | Heavy Polyester Polyamide Imide     | ||||||
Connection (2)     | Series     | 2 Parallel Wye     | Series Star     | ||||
Line Leads     | 2 - #14     | 6 - #10     | 3 - #14     |
Show/hide table
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 06 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram I |
203-5757 Generator
Show/hide table
MAIN STATOR AND ROTOR WINDING DATA     | |||||||
---|---|---|---|---|---|---|---|
ITEM     | STATOR     | ROTOR     | |||||
Stack Height     | 914.4 mm (36.0 inch)     |
927.1 mm (36.5 inch)     |
|||||
Slots     | 90     | -     | |||||
Coil Throw     | 1 - 12     | -     | |||||
Turns/Coil     | 2     | -     | |||||
Turns/Pole     | -     | 163.5     | |||||
No. & Wire Size     | 2 - 3.4544 mm (0.136 inch) x 6.9088 mm (0.272 inch)     |
3.6576 mm (0.144 inch) X 7.31520 mm (0.288 inch)     |
|||||
Mean Length Turn     | 2560.3 mm (100.8 inch)     |
2311.4 mm (91.0 inch)     |
|||||
Copper Weight     | 191.4 kg (422 lb)     |
549.8 kg (1212 lb)     |
|||||
Inside Connection (1)     | 6 Parallel Wye     | Series     | |||||
Line Leads (No. & Size)     | 36 - #2/0     | -     | |||||
Terminal bolt size     | 3/8 inch     | -     | |||||
Low Voltage connected line resistance at 25 ° C (77 ° F)     | 0.00387 ohms     | -     | |||||
Field lead resistance at 25 ° C (77 ° F)     | -     | 1.522 ohms     | |||||
EXCITER WINDING DATA     | |||||||
Exciter Frequency (Hz)     | 80 Hz     | Permanent Magnet Frequency     | 160 Hz     | ||||
Exciter Poles     | 8     | ||||||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | Permanent Magnet Stator     | ||||
Stack Length     | 88.9 mm (3.5 inch)     |
88.9 mm (3.5 inch)     |
31.8 mm (1.25 inch)     |
||||
Coils/Group     | -     | -     | 1     | ||||
Slots (Coils)     | 8     | 48     | 48     | ||||
Turns (Coils)     | 320     | 8     | 17     | ||||
No. & Size Wire     | 2 - #18.5     | 3 - #16     | 2 - #17     | ||||
Coil Throw     | 1 - 2     | 1 - 6     | 1 - 4     | ||||
Mean Length Turn (Calc.)     | 355.6 mm (14.0 inch)     |
419.1 mm (16.5 inch)     |
221.0 mm (8.7 inch)     |
||||
Copper Weight     | 14.0 kg (30.9 lb)     |
6.4 kg (14 lb)     |
1.8 kg (3.97 lb)     |
||||
Insulation     | Heavy Polyester Polyamide Imide     | ||||||
Connection (2)     | Series     | 2 Parallel Wye     | Series Star     | ||||
Line Leads     | 2 - #14     | 6 - #10     | 3 - #14     |
Show/hide table
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 06 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram I |
225-6314 Generator Ar
Show/hide table
MAIN STATOR AND ROTOR WINDING DATA (4)     | |||||||
---|---|---|---|---|---|---|---|
ITEM     | STATOR     | ROTOR     | |||||
Stack Height     | 584.2 mm (23 inch)     |
596.90 mm (23.5 inch)     |
|||||
Slots     | 96     | 4     | |||||
Coil Throw     | 1-17     | 1-2     | |||||
Turns/Coil     | 1     | -     | |||||
Turns/Pole     | -     | 216.5 (3)     | |||||
No. & Wire Size     | 41 of # 13     | 3.6068 mm (0.142 inch) x 7.7470 mm (0.305 inch)     |
|||||
Mean Length Turn     | 2209.8 mm (87 inch)     |
1765.30 mm (69.5 inch)     |
|||||
Copper Weight     | 241.3 kg (532 lb)     |
400.0 kg (882 lb)     |
|||||
Inside Connection (1)     | 4 Parallel Wye     | Series     | |||||
Line Leads (No. & Size)     | 6 - 8 of # 2/0 ( 48 TOTAL)     | #8     | |||||
Low Voltage connected line resistance at 25° C (77.0° F)     |
0.00189 ohms     | -     | |||||
Field lead resistance at 25° C (77.0° F)     |
-     | 1.003 ohms     | |||||
EXCITER WINDING DATA     | |||||||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | Permanent Magnet Stator     | ||||
Exciter Frequency (Hz)     | 60 Hz     | 80 Hz     | 240 Hz     | ||||
Exciter Poles     | 8     | 8     | 16     | ||||
Stack Length     | 88.90 mm (3.5 inch)     |
88.90 mm (3.5 inch)     |
25.4 mm (1 inch)     |
||||
Coils/Group     | 1     | 1     | 1     | ||||
Turns (Coils)     | 175     | 16     | 12     | ||||
No. & Size Wire     | 2 of #16     | 3 of #16     | 4 of # 18     | ||||
Coil Throw     | 1 - 2     | 1 - 6     | 1-4 29-35Lds     | ||||
Mean Length Turn     | 355.6 mm (14 inch)     |
419.10 mm (16.5 inch)     |
208.28000 mm (8.2 inch)     |
||||
Resistance at 25° C (77.0° F)     |
3.8 ohms     | 0.122 ohms     | 0.239 ohms     | ||||
Copper Weight     | 12.92 kg (28.5 lb)     |
6.3 kg (14 lb)     |
1.791 kg (3.95 lb)     |
||||
Connection (2)     | Series     | 2 Parallel Wye     | Wye     | ||||
Line Leads     | 2 - #14     | 3 of #10     | 3-1 of #14 (3 total)     |
Show/hide table
( 4 ) | For Se Generators Only: Voltage Regulator Leads 20, 22, 24 Are To Be Tapped 4 Turns From Neutral In Pole Groups 3, 1, And 5 Respectively |
( 3 ) | Layer wound with 12.70 mm (0.5 inch) vent openings to be divided at layers 9-8 in the coil head (wind 9 layers - insert spacer - wind last 8 layers) |
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 04 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram D |
226-1216 Generator Ar
Show/hide table
MAIN STATOR AND ROTOR WINDING DATA (4)     | |||||||
---|---|---|---|---|---|---|---|
ITEM     | STATOR     | ROTOR     | |||||
Stack Height     | 520.70 mm (20.5 inch)     |
533.4 mm (21 inch)     |
|||||
Slots     | 60     | 4     | |||||
Coil Throw     | 1-11     | 1-2     | |||||
Turns/Coil     | 1     | -     | |||||
Turns/Pole     | -     | 216.5 (3)     | |||||
No. & Wire Size     | 12 - 3.2512 mm (0.128 inch) x 6.55320 mm (0.258 inch) 2 Wide x 6 High     |
3.6068 mm (0.142 inch) x 7.7470 mm (0.305 inch)     |
|||||
Mean Length Turn     | 2263.14 mm (89.1 inch)     |
1638.30 mm (64.5 inch)     |
|||||
Copper Weight     | 298.9 kg (659 lb)     |
371.9 kg (820 lb)     |
|||||
Inside Connection (1)     | 2 Parallel Wye     | Series     | |||||
Line Leads (No. & Size)     | 6 - 8 of # 1/0 ( 48 TOTAL)     | #8     | |||||
Low Voltage connected line resistance at 25° C (77.0° F)     |
0.00196 ohms     | -     | |||||
Field lead resistance at 25° C (77.0° F)     |
-     | 0.9324 ohms     | |||||
EXCITER WINDING DATA     | |||||||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | Permanent Magnet Stator     | ||||
Exciter Frequency (Hz)     | 60 Hz     | 80 Hz     | 240 Hz     | ||||
Exciter Poles     | 8     | 8     | 16     | ||||
Stack Length     | 88.90 mm (3.5 inch)     |
88.90 mm (3.5 inch)     |
25.4 mm (1 inch)     |
||||
Coils/Group     | 1     | 1     | 1     | ||||
Turns (Coils)     | 175     | 16     | 12     | ||||
No. & Size Wire     | 2 of #16     | 3 of #16     | 4 of # 18     | ||||
Coil Throw     | 1 - 2     | 1 - 6     | 1-4 29-35Lds     | ||||
Mean Length Turn     | 355.6 mm (14 inch)     |
419.10 mm (16.5 inch)     |
208.28000 mm (8.2 inch)     |
||||
Resistance at 25° C (77.0° F)     |
3.8 ohms     | 0.122 ohms     | 0.239 ohms     | ||||
Copper Weight     | 12.92 kg (28.5 lb)     |
6.3 kg (14 lb)     |
1.791 kg (3.95 lb)     |
||||
Connection (2)     | Series     | 2 Parallel Wye     | Wye     | ||||
Line Leads     | 2 - #14     | 3 of #10     | 3-1 of #14 (3 total)     |
Show/hide table
( 4 ) | For Se Generators Only: Voltage Regulator Leads 20, 22, 24 Are To Be Tapped 4 Turns From Neutral In Pole Groups 3, 1, And 5 Respectively |
( 3 ) | Layer wound with 12.70 mm (0.5 inch) vent openings to be divided at layers 9-8 in the coil head (wind 9 layers - insert spacer - wind last 8 layers) |
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 04 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram D |
258-9067 Generator Ar
Show/hide table
MAIN STATOR AND ROTOR WINDING DATA     | |||||||
---|---|---|---|---|---|---|---|
ITEM     | STATOR     | ROTOR     | |||||
Stack Height     | 360.68 mm (14.2 inch)     |
360.68 mm (14.2 inch)     |
|||||
Slots     | 48     | 4     | |||||
Coil Throw     | 1-10     | 1-2     | |||||
Turns/Coil     | 2.5 (2-3-2-3)     | -     | |||||
Turns/Pole     |     | 130     | |||||
No. & Wire Size     | 12 # 14     | #8 Square     | |||||
Mean Length Turn     | 1353.82 mm (53.3 inch)     |
1127.76 mm (44.4 inch)     |
|||||
Copper Weight     | 40.14 kg (88.5 lb)     |
53.61 kg (118.2 lb)     |
|||||
Inside Connection (1)     | 2 Parallel Wye     |     | |||||
Line Leads (No. & Size)     | 12-2 of #2 (24 Total)     | #8     | |||||
Low Voltage connected line resistance at 25° C (77.0° F)     |
0.00574 ohms     | -     | |||||
Field lead resistance at 25° C (77.0° F)     |
-     | 1.115 ohms     | |||||
EXCITER WINDING DATA     | |||||||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | Permanent Magnet Stator     | ||||
Exciter Frequency (Hz)     | 90 Hz     | 90 Hz     | 120 Hz     | ||||
Exciter Poles     | 6     | 6     | 8     | ||||
Stack Length     | 88.90 mm (3.5 inch)     |
88.90 mm (3.5 inch)     |
31.750 mm (1.25 inch)     |
||||
Coils/Group     | 1     | 2     | 24     | ||||
Turns (Coils)     | 150     | 8     | 12     | ||||
No. & Size Wire     | #16     | 2 of #16     | 2#18     | ||||
Coil Throw     | 1 - 2     | 1 - 6     | 1-4     | ||||
Mean Length Turn     | 388.62 mm (15.3 inch)     |
419.10 mm (16.5 inch)     |
330.2 mm (13 inch)     |
||||
Resistance at 25° C (77.0° F)     |
4.63 ohms     | 0.115 ohms     | 0.551 ohms     | ||||
Copper Weight     | 4.12 kg (9.1 lb)     |
2.35 kg (5.2 lb)     |
0.4 kg (1 lb)     |
||||
Connection (2)     | Series     | 2 Parallel Wye     | Wye     | ||||
Line Leads     | 2 - #14     | 3 of #10     | 3 of #14     |
Show/hide table
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 63 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram D |
312-0148 Generator Ar
Show/hide table
MAIN STATOR AND ROTOR WINDING DATA     | |||||||
---|---|---|---|---|---|---|---|
ITEM     | STATOR     | ROTOR     | |||||
Stack Height     | 414.02 mm (16.3 inch)     |
414.02 mm (16.3 inch)     |
|||||
Slots     | 60     | 4     | |||||
Coil Throw     | 1-12     | 1-2     | |||||
Turns/Coil     | 1.4 (1-2-1-2-1) (3)     | -     | |||||
Turns/Pole     |     | 180     | |||||
No. & Wire Size     | 27 # 14     | # 6-1/2 Rd     | |||||
Mean Length Turn     | 1578.864 mm (62.16 inch)     |
1285.24 mm (50.6 inch)     |
|||||
Copper Weight     | 67.1 kg (148 lb)     |
99.7 kg (220 lb)     |
|||||
Inside Connection (1)     | 2 Parallel Wye     | Series     | |||||
Line Leads (No. & Size)     | 6-2 #3/0 (12 total)     | #8     | |||||
Low Voltage connected line resistance at 25° C (77.0° F)     |
0.0085 ohms     | -     | |||||
Field lead resistance at 25° C (77.0° F)     |
-     | 1.44 ohms     | |||||
EXCITER WINDING DATA     | |||||||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | Permanent Magnet Stator     | ||||
Exciter Frequency (Hz)     | 90 Hz     | 90 Hz     |     | ||||
Exciter Poles     | 6     |     |     | ||||
Stack Length     | 127.0 mm (5 inch)     |
127.0 mm (5 inch)     |
    | ||||
Coils/Group     | 1     | 1     |     | ||||
Turns (Coils)     | 140     | 8     |     | ||||
No. & Size Wire     | 15-1/2     | 2 of #16     |     | ||||
Coil Throw     | 1 - 2     | 1 - 6     |     | ||||
Mean Length Turn     | 464.82000 mm (18.3 inch)     |
    |     | ||||
Resistance at 25° C (77.0° F)     |
4.68 ohms     | 0.145 ohms     |     | ||||
Copper Weight     | 5.21 kg (11.5 lb)     |
2.90 kg (6.4 lb)     |
    | ||||
Connection (2)     | Series     | 2 Parallel Wye     |     | ||||
Line Leads     | #14     | 3 of #10     |     |
Show/hide table
( 3 ) | Install 240V regulator tap leads in middle point connection per connection diagram. |
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 63 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram D |
324-5106 Generator Ar
Show/hide table
MAIN STATOR AND ROTOR WINDING DATA (4)     | |||||||
---|---|---|---|---|---|---|---|
ITEM     | STATOR     | ROTOR     | |||||
Stack Height     | 450.850 mm (17.75 inch)     |
463.550 mm (18.25 inch)     |
|||||
Slots     | 72     | 4     | |||||
Coil Throw     | 1-14     | 1-2     | |||||
Turns/Coil     | 1     | -     | |||||
Turns/Pole     | -     | 216 (3)     | |||||
No. & Wire Size     | 37 # 13     | #6 Square     | |||||
Mean Length Turn     | 1925.32 mm (75.8 inch)     |
1463.04 mm (57.6 inch)     |
|||||
Copper Weight     | 141.5 kg (312 lb)     |
187.7 kg (414 lb)     |
|||||
Inside Connection (1)     | 2 Parallel Wye     |     | |||||
Line Leads (No. & Size)     | 12-4 # 2/0 (48 total) Silicone     | #8     | |||||
Low Voltage connected line resistance at 25° C (77.0° F)     |
0.00141 ohms     | -     | |||||
Field lead resistance at 25° C (77.0° F)     |
-     | 1.389 ohms     | |||||
EXCITER WINDING DATA     | |||||||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | Permanent Magnet Stator     | ||||
Exciter Frequency (Hz)     | 60 Hz     | 80 Hz     | 240 Hz     | ||||
Exciter Poles     | 8     | 8     | 16     | ||||
Stack Length     | 88.90 mm (3.5 inch)     |
88.90 mm (3.5 inch)     |
25.4 mm (1 inch)     |
||||
Coils/Group     | 1     | 1     | 1     | ||||
Turns (Coils)     | 175     | 16     | 12     | ||||
No. & Size Wire     | 2 of #16     | 3 of #16     | 4 of # 18     | ||||
Coil Throw     | 1 - 2     | 1 - 6     | 1-4 29-35Lds     | ||||
Mean Length Turn     | 355.6 mm (14 inch)     |
419.10 mm (16.5 inch)     |
304.8 mm (12 inch)     |
||||
Resistance at 25° C (77.0° F)     |
3.8 ohms     | 0.122 ohms     | 0.239 ohms     | ||||
Copper Weight     | 12.92 kg (28.5 lb)     |
6.3 kg (14 lb)     |
1.791 kg (3.95 lb)     |
||||
Connection (2)     | Series     | 2 Parallel Wye     | Wye     | ||||
Line Leads     | 2 - #14     | 3 of #10     | 3-1 of #14 (3 total)     |
Show/hide table
( 4 ) | Special Res. for Global Design with 1320.8 mm (52 inch) leads. |
( 3 ) | Layer wound with 12.70 mm (0.5 inch) vent opening to divide layers 6-6 in coil head. |
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 04 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram D |
324-5114 Generator Ar
Show/hide table
MAIN STATOR AND ROTOR WINDING DATA     | |||||||
---|---|---|---|---|---|---|---|
ITEM     | STATOR     | ROTOR     | |||||
Stack Height     | 450.850 mm (17.75 inch)     |
469.90 mm (18.5 inch)     |
|||||
Slots     | 72     | 4     | |||||
Coil Throw     | 1-14     | 1-2     | |||||
Turns/Coil     | 1     | -     | |||||
Turns/Pole     | -     | 216 (3)     | |||||
No. & Wire Size     | 6 of 3.2512 mm (0.128 inch) X 4.1148 mm (0.162 inch) / 4 of 2.8956 mm (0.114 inch) X 4.1148 mm (0.162 inch)     |
#6 Square     | |||||
Mean Length Turn     | 1925.32 mm (75.8 inch)     |
1478.28 mm (58.2 inch)     |
|||||
Copper Weight     | 161.0 kg (355 lb)     |
180.5 kg (398 lb)     |
|||||
Inside Connection (1)     | 2 Parallel Wye     |     | |||||
Line Leads (No. & Size)     | 6-4 #3/0 (24 total)     | #8     | |||||
Low Voltage connected line resistance at 25° C (77.0° F)     |
0.00394 ohms     | -     | |||||
Field lead resistance at 25° C (77.0° F)     |
-     | 1.401 ohms     | |||||
EXCITER WINDING DATA     | |||||||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | Permanent Magnet Stator     | ||||
Exciter Frequency (Hz)     | 60 Hz     | 80 Hz     | 240 Hz     | ||||
Exciter Poles     | 8     | 8     | 16     | ||||
Stack Length     | 88.90 mm (3.5 inch)     |
88.90 mm (3.5 inch)     |
25.4 mm (1 inch)     |
||||
Coils/Group     | 1     | 1     | 1     | ||||
Turns (Coils)     | 175     | 16     | 12     | ||||
No. & Size Wire     | 2 of #16     | 3 of #16     | 4 of # 18     | ||||
Coil Throw     | 1 - 2     | 1 - 6     | 1-4 29-35Lds     | ||||
Mean Length Turn     | 355.6 mm (14 inch)     |
419.10 mm (16.5 inch)     |
208.28 mm (8.2 inch)     |
||||
Resistance at 25° C (77.0° F)     |
3.8 ohms     | 0.122 ohms     | 0.239 ohms     | ||||
Copper Weight     | 12.92 kg (28.5 lb)     |
6.3 kg (14 lb)     |
1.791 kg (3.95 lb)     |
||||
Connection (2)     | Series     | 2 Parallel Wye     | Wye     | ||||
Line Leads     | 2 - #14     | 3 of #10     | 3-1 of #14 (3 total)     |
Show/hide table
( 3 ) | Layer wound with 12.70 mm (0.5 inch) vent opening to divide layers 6-6 in coil head. |
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 04 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram D |
324-5120 Generator Ar
Show/hide table
MAIN STATOR AND ROTOR WINDING DATA (4)     | |||||||
---|---|---|---|---|---|---|---|
ITEM     | STATOR     | ROTOR     | |||||
Stack Height     | 450.850 mm (17.75 inch)     |
469.90 mm (18.5 inch)     |
|||||
Slots     | 72     | 4     | |||||
Coil Throw     | 1-14     | 1-2     | |||||
Turns/Coil     | 1     | -     | |||||
Turns/Pole     | -     | 216 (3)     | |||||
No. & Wire Size     | 37 # 13     | #6 Square     | |||||
Mean Length Turn     | 1925.32 mm (75.8 inch)     |
1478.28 mm (58.2 inch)     |
|||||
Copper Weight     | 141.5 kg (312 lb)     |
180.5 kg (398 lb)     |
|||||
Inside Connection (1)     | 2 Parallel Wye     |     | |||||
Line Leads (No. & Size)     | 12-4 # 2/0 (48 total) Silicone     | #8     | |||||
Low Voltage connected line resistance at 25° C (77.0° F)     |
0.00141 ohms     | -     | |||||
Field lead resistance at 25° C (77.0° F)     |
-     | 1.401 ohms     | |||||
EXCITER WINDING DATA     | |||||||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | Permanent Magnet Stator     | ||||
Exciter Frequency (Hz)     | 60 Hz     | 80 Hz     |     | ||||
Exciter Poles     | 8     | 8     |     | ||||
Stack Length     | 88.90 mm (3.5 inch)     |
88.90 mm (3.5 inch)     |
    | ||||
Coils/Group     | 1     | 1     |     | ||||
Turns (Coils)     | 175     | 16     |     | ||||
No. & Size Wire     | 2 of #16     | 3 of #16     |     | ||||
Coil Throw     | 1 - 2     | 1 - 6     |     | ||||
Mean Length Turn     | 355.6 mm (14 inch)     |
419.10 mm (16.5 inch)     |
    | ||||
Resistance at 25° C (77.0° F)     |
3.8 ohms     | 0.122 ohms     |     | ||||
Copper Weight     | 12.92 kg (28.5 lb)     |
6.3 kg (14 lb)     |
    | ||||
Connection (2)     | Series     | 2 Parallel Wye     |     | ||||
Line Leads     | 2 - #14     | 3 of #10     |     |
Show/hide table
( 4 ) | Special Res. for Global Design with 1320.8 mm (52 inch) leads. |
( 3 ) | Layer wound with 12.70 mm (0.5 inch) vent opening to divide layers 6-6 in coil head. |
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 04 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram D |
Caterpillar Information System:
SR4 and SR4B Electric Power Generation Rewind Data Winding Data for 173-7078 Generator through 194-6563 Generator
SR4 and SR4B Electric Power Generation Rewind Data Winding Data for 164-0975 Generator through 164-4946 Generator
SR4 and SR4B Electric Power Generation Rewind Data Winding Data for 158-6410 Generator through 163-8546 Generator
SR4 and SR4B Electric Power Generation Rewind Data Winding Data for 149-2447 Generator through 150-9152 Generator
SR4 and SR4B Electric Power Generation Rewind Data Winding Data for 144-1964 Generator through 144-2088 Generator
SR4 and SR4B Electric Power Generation Rewind Data Winding Data for 136-6610 Generator through 136-6641 Generator
SR4 and SR4B Electric Power Generation Rewind Data Winding Data for 144-1666 Generator through 144-1766 Generator
3512C Petroleum Engines with Dynamic Gas Blending Engine Shutdown Occurrence
312D2 and 313D2 Excavators System Pressure Release
SR4 and SR4B Electric Power Generation Rewind Data Winding Data for 141-5534 Generator through 142-9900 Generator
SR4 and SR4B Electric Power Generation Rewind Data Winding Data for 136-6580 Generator through 136-6609 Generator
SR4 and SR4B Electric Power Generation Rewind Data Winding Data for 126-8022 Generator through 128-7424 Generator
SR4 and SR4B Electric Power Generation Rewind Data Winding Data for 6I-0053 Generator through 6I-4860 Generator
2013/11/11 An Improved ARD Combustion Head is Now Used on the Tier 4 Engines of Certain Machines {108B, 108E, 108M}
2013/11/21 An Improved ARD Combustion Head is Now Used on Certain Tier 4 Engines {108B, 108E, 108M}
Installation of G610 Hardware for Cat® Terrain for Motor Graders, Wheel Dozers, and Wheel Loaders {7605} Installation of G610 Hardware for Cat® Terrain for Motor Graders, Wheel Dozers, and Wheel Loaders {7605}
3512C Oil Well Service Engines Air Shutoff - Test
793F and 797F Off-Highway Trucks Braking System Automatic Retarder Control (ARC)
3500E EPA Tier 4 Final and IMO-II/III Switchable Marine Engines Sensor Calibration Required - Test
374F Excavator Hydraulic System General Information (Return System)
SR4 and SR4B Electric Power Generation Rewind Data Winding Data for 109-3776 Generator through 109-7874 Generator
2013/08/30 A New Adapter Is Used on Certain 3512C Petroleum Engines {1157}
966M Tier 4 and 972M Tier 4 Wheel Loaders Power Train Modulating Valve (Torque Converter Lockup Clutch) - Remove and Install
2014/10/10 Engine News Article List for <B>S/N:</B>8LL Engines {1000}