Winding Data for 136-6610 Generator through 136-6641 Generator
136-6610 Generator Ar
Show/hide table
MAIN STATOR AND ROTOR WINDING DATA     | |||||||
---|---|---|---|---|---|---|---|
ITEM     | STATOR     | ROTOR     | |||||
Stack Height     | 457.2 mm (18 inch)     |
457.2 mm (18 inch)     |
|||||
Slots     | 60     | 4     | |||||
Coil Throw     | 1-14     | 1 - 2     | |||||
Turns/Coil     | 1     | -     | |||||
Turns/Pole     | -     | 193 (3)     | |||||
No. & Wire Size     | 40 # 14     | # 6-1/2 Round     | |||||
Mean Length Turn     | 1828.8 mm (72 inch)     |
    | |||||
Copper Weight     | 82.5 kg (182 lb)     |
113.8 kg (251 lb)     |
|||||
Inside Connection (1)     | 2 Parallel Wye     |     | |||||
Line Leads (No. & Size)     | 12-4 # 1/0 (48 total)     |     | |||||
Low Voltage connected line resistance at 25° C (77.0° F)     |
0.00144 ohms     | -     | |||||
Field lead resistance at 25° C (77.0° F)     |
-     | 1.6 ohms     | |||||
EXCITER WINDING DATA     | |||||||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | Permanent Magnet Stator     | ||||
Exciter Frequency (Hz)     | 90 Hz     | 90 Hz     | 240 Hz     | ||||
Exciter Poles     | 6     |     | 16     | ||||
Stack Length     | 127.0 mm (5 inch)     |
127.0 mm (5 inch)     |
25.4 mm (1 inch)     |
||||
Coils/Group     | 1     | 1     | 1     | ||||
Turns (Coils)     | 140     | 8     | 12     | ||||
No. & Size Wire     | 15-1/2     | 2 - #16     | 4 - #18     | ||||
Coil Throw     | 1 - 2     | 1 - 6     | 1-4 29-35Lds     | ||||
Mean Length Turn     | 464.82 mm (18.3 inch)     |
    | 208.28 mm (8.2 inch)     |
||||
Resistance at 25° C (77.0° F)     |
4.68 ohms     | 0.145 ohms     | 0.239 ohms     | ||||
Copper Weight     | 5.21 kg (11.5 lb)     |
2.90 kg (6.4 lb)     |
1.791 kg (3.95 lb)     |
||||
Connection (2)     | Series     | 2 Parallel Wye     | Wye     | ||||
Line Leads     | #14     | 3 - #10     | 3-1 OF #14 (3 total)     |
Show/hide table
( 3 ) | Layer wound, vent openings to divide layers 4-4-5 in coil head |
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 63 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram D |
136-6612 Generator Ar
Show/hide table
MAIN STATOR AND ROTOR WINDING DATA (4)     | |||||||
---|---|---|---|---|---|---|---|
ITEM     | STATOR     | ROTOR     | |||||
Stack Height     | 457.2 mm (18 inch)     |
457.2 mm (18 inch)     |
|||||
Slots     | 60     | 4     | |||||
Coil Throw     | 1-13     | 1 - 2     | |||||
Turns/Coil     | 3.4 (4-3-3-3-4)     | -     | |||||
Turns/Pole     | -     | 193 (3)     | |||||
No. & Wire Size     | 40 # 14     | # 6-1/2 Round     | |||||
Mean Length Turn     | 1828.8 mm (72 inch)     |
    | |||||
Copper Weight     | 82.5 kg (182 lb)     |
113.8 kg (251 lb)     |
|||||
Inside Connection (1)     | 4 Parallel Wye     |     | |||||
Line Leads (No. & Size)     | 6-4 of #2 (24 total)     |     | |||||
Low Voltage connected line resistance at 25° C (77.0° F)     |
0.010243 ohms     | -     | |||||
Field lead resistance at 25° C (77.0° F)     |
-     | 1.6 ohms     | |||||
EXCITER WINDING DATA     | |||||||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | Permanent Magnet Stator     | ||||
Exciter Frequency (Hz)     | 90 Hz     | 90 Hz     |     | ||||
Exciter Poles     | 6     |     |     | ||||
Stack Length     | 127.0 mm (5 inch)     |
127.0 mm (5 inch)     |
    | ||||
Coils/Group     | 1     | 1     |     | ||||
Turns (Coils)     | 140     | 8     |     | ||||
No. & Size Wire     | 15-1/2     | 2 - #16     |     | ||||
Coil Throw     | 1 - 2     | 1 - 6     |     | ||||
Mean Length Turn     | 464.82 mm (18.3 inch)     |
    |     | ||||
Resistance at 25° C (77.0° F)     |
4.68 ohms     | 0.145 ohms     |     | ||||
Copper Weight     | 5.21 kg (11.5 lb)     |
2.90 kg (6.4 lb)     |
    | ||||
Connection (2)     | Series     | 2 Parallel Wye     |     | ||||
Line Leads     | #14     | 3 - #10     |     |
Show/hide table
( 4 ) | Tap voltage regulator leads 20, 22, 24 six (6) turns (2 coils) from neutral in pole groups 3, 1, and 5 respectively |
( 3 ) | Layer wound, vent openings to divide layers 4-4-5 in coil head |
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 04 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram D |
136-6613 Generator Ar
Show/hide table
MAIN STATOR AND ROTOR WINDING DATA (4)     | |||||||
---|---|---|---|---|---|---|---|
ITEM     | STATOR     | ROTOR     | |||||
Stack Height     | 457.2 mm (18 inch)     |
457.2 mm (18 inch)     |
|||||
Slots     | 60     | 4     | |||||
Coil Throw     | 1-13     | 1 - 2     | |||||
Turns/Coil     | 3.4 (4-3-3-3-4)     | -     | |||||
Turns/Pole     | -     | 193 (3)     | |||||
No. & Wire Size     | 14 # 14     | # 6-1/2 Round     | |||||
Mean Length Turn     | 1828.8 mm (72 inch)     |
    | |||||
Copper Weight     | 104.28 kg (229.9 lb)     |
113.8 kg (251 lb)     |
|||||
Inside Connection (1)     | 4 Parallel Wye     |     | |||||
Line Leads (No. & Size)     | 6-4 of #2 (24 total)     |     | |||||
Low Voltage connected line resistance at 25° C (77.0° F)     |
0.010243 ohms     | -     | |||||
Field lead resistance at 25° C (77.0° F)     |
-     | 1.6 ohms     | |||||
EXCITER WINDING DATA     | |||||||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | Permanent Magnet Stator     | ||||
Exciter Frequency (Hz)     | 90 Hz     | 90 Hz     | 240 Hz     | ||||
Exciter Poles     | 6     |     | 16     | ||||
Stack Length     | 127.0 mm (5 inch)     |
127.0 mm (5 inch)     |
25.4 mm (1 inch)     |
||||
Coils/Group     | 1     | 1     | 1     | ||||
Turns (Coils)     | 140     | 8     | 12     | ||||
No. & Size Wire     | 15-1/2     | 2 - #16     | 4 - #18     | ||||
Coil Throw     | 1 - 2     | 1 - 6     | 1-4 29-35Lds     | ||||
Mean Length Turn     | 464.82 mm (18.3 inch)     |
    | 208.28 mm (8.2 inch)     |
||||
Resistance at 25° C (77.0° F)     |
4.68 ohms     | 0.145 ohms     | 0.239 ohms     | ||||
Copper Weight     | 5.21 kg (11.5 lb)     |
2.90 kg (6.4 lb)     |
1.791 kg (3.95 lb)     |
||||
Connection (2)     | Series     | 2 Parallel Wye     | Wye     | ||||
Line Leads     | #14     | 3 - #10     | 3-1 OF #14 (3 total)     |
Show/hide table
( 4 ) | Tap voltage regulator leads 20, 22, 24 six (6) turns (2 coils) from neutral in pole groups 3, 1, and 5 respectively |
( 3 ) | Layer wound, vent openings to divide layers 4-4-5 in coil head |
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 04 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram D |
136-6614 Generator Ar
Show/hide table
MAIN STATOR AND ROTOR WINDING DATA (4)     | |||||||
---|---|---|---|---|---|---|---|
ITEM     | STATOR     | ROTOR     | |||||
Stack Height     | 457.2 mm (18 inch)     |
457.2 mm (18 inch)     |
|||||
Slots     | 60     | 4     | |||||
Coil Throw     | 1-13     | 1 - 2     | |||||
Turns/Coil     | 3.4 (4-3-3-3-4)     | -     | |||||
Turns/Pole     | -     | 193 (3)     | |||||
No. & Wire Size     | 14 # 14     | # 6-1/2 Round     | |||||
Mean Length Turn     | 1828.8 mm (72 inch)     |
    | |||||
Copper Weight     | 104.28 kg (229.9 lb)     |
113.8 kg (251 lb)     |
|||||
Inside Connection (1)     | 4 Parallel Wye     |     | |||||
Line Leads (No. & Size)     | 6-4 of #2 (24 total)     |     | |||||
Low Voltage connected line resistance at 25° C (77.0° F)     |
0.010243 ohms     | -     | |||||
Field lead resistance at 25° C (77.0° F)     |
-     | 1.6 ohms     | |||||
EXCITER WINDING DATA     | |||||||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | Permanent Magnet Stator     | ||||
Exciter Frequency (Hz)     | 90 Hz     | 90 Hz     | 240 Hz     | ||||
Exciter Poles     | 6     |     | 16     | ||||
Stack Length     | 127.0 mm (5 inch)     |
127.0 mm (5 inch)     |
25.4 mm (1 inch)     |
||||
Coils/Group     | 1     | 1     | 1     | ||||
Turns (Coils)     | 140     | 8     | 12     | ||||
No. & Size Wire     | 15-1/2     | 2 - #16     | 4 - #18     | ||||
Coil Throw     | 1 - 2     | 1 - 6     | 1-4 29-35Lds     | ||||
Mean Length Turn     | 464.82 mm (18.3 inch)     |
    | 208.28 mm (8.2 inch)     |
||||
Resistance at 25° C (77.0° F)     |
4.68 ohms     | 0.145 ohms     | 0.239 ohms     | ||||
Copper Weight     | 5.21 kg (11.5 lb)     |
2.90 kg (6.4 lb)     |
1.791 kg (3.95 lb)     |
||||
Connection (2)     | Series     | 2 Parallel Wye     | Wye     | ||||
Line Leads     | #14     | 3 - #10     | 3-1 OF #14 (3 total)     |
Show/hide table
( 4 ) | Tap voltage regulator leads 20, 22, 24 six (6) turns (2 coils) from neutral in pole groups 3, 1, and 5 respectively |
( 3 ) | Layer wound, vent openings to divide layers 4-4-5 in coil head |
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 04 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram D |
136-6615 Generator Ar
Show/hide table
MAIN STATOR AND ROTOR WINDING DATA     | |||||||
---|---|---|---|---|---|---|---|
ITEM     | STATOR     | ROTOR     | |||||
Stack Height     | 431.8 mm (17 inch)     |
431.8 mm (17 inch)     |
|||||
Slots     | 60     | 4     | |||||
Coil Throw     | 1-12     | 1 - 2     | |||||
Turns/Coil     | 1.4(1-2-1-2-1)     | -     | |||||
Turns/Pole     | -     | 180     | |||||
No. & Wire Size     | 32 # 14     | # 6-1/2 Round     | |||||
Mean Length Turn     | 1701.8 mm (67 inch)     |
1320.292 mm (51.98 inch)     |
|||||
Copper Weight     | 87.0 kg (192 lb)     |
102.46 kg (225.9 lb)     |
|||||
Inside Connection (1)     | 2 Parallel Wye     |     | |||||
Line Leads (No. & Size)     | 12-2 # 4/0 (24 total)     | #8     | |||||
Low Voltage connected line resistance at 25° C (77.0° F)     |
0.00208 ohms     | -     | |||||
Field lead resistance at 25° C (77.0° F)     |
-     | 1.5 ohms     | |||||
EXCITER WINDING DATA     | |||||||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | Permanent Magnet Stator     | ||||
Exciter Frequency (Hz)     | 90 Hz     | 90 Hz     |     | ||||
Exciter Poles     | 6     |     |     | ||||
Stack Length     | 127.0 mm (5 inch)     |
127.0 mm (5 inch)     |
    | ||||
Coils/Group     | 1     | 1     |     | ||||
Turns (Coils)     | 140     | 8     |     | ||||
No. & Size Wire     | 15-1/2     | 2 - #16     |     | ||||
Coil Throw     | 1 - 2     | 1 - 6     |     | ||||
Mean Length Turn     | 464.82 mm (18.3 inch)     |
    |     | ||||
Resistance at 25° C (77.0° F)     |
4.68 ohms     | 0.145 ohms     |     | ||||
Copper Weight     | 5.21 kg (11.5 lb)     |
2.90 kg (6.4 lb)     |
    | ||||
Connection (2)     | Series     | 2 Parallel Wye     |     | ||||
Line Leads     | #14     | 3 - #10     |     |
Show/hide table
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 63 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram D |
136-6616 Generator Ar
Show/hide table
MAIN STATOR AND ROTOR WINDING DATA     | |||||||
---|---|---|---|---|---|---|---|
ITEM     | STATOR     | ROTOR     | |||||
Stack Height     | 431.8 mm (17 inch)     |
431.8 mm (17 inch)     |
|||||
Slots     | 60     | 4     | |||||
Coil Throw     | 1-12     | 1 - 2     | |||||
Turns/Coil     | 1.4(1-2-1-2-1)     | -     | |||||
Turns/Pole     | -     | 180     | |||||
No. & Wire Size     | 32 # 14     | # 6-1/2 Round     | |||||
Mean Length Turn     | 1701.8 mm (67 inch)     |
1320.292 mm (51.98 inch)     |
|||||
Copper Weight     | 87.0 kg (192 lb)     |
102.46 kg (225.9 lb)     |
|||||
Inside Connection (1)     | 2 Parallel Wye     |     | |||||
Line Leads (No. & Size)     | 12-2 # 4/0 (24 total)     | #8     | |||||
Low Voltage connected line resistance at 25° C (77.0° F)     |
0.00208 ohms     | -     | |||||
Field lead resistance at 25° C (77.0° F)     |
-     | 1.5 ohms     | |||||
EXCITER WINDING DATA     | |||||||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | Permanent Magnet Stator     | ||||
Exciter Frequency (Hz)     | 90 Hz     | 90 Hz     | 240 Hz     | ||||
Exciter Poles     | 6     |     | 16     | ||||
Stack Length     | 127.0 mm (5 inch)     |
127.0 mm (5 inch)     |
25.4 mm (1 inch)     |
||||
Coils/Group     | 1     | 1     | 1     | ||||
Turns (Coils)     | 140     | 8     | 12     | ||||
No. & Size Wire     | 15-1/2     | 2 - #16     | 4 - #18     | ||||
Coil Throw     | 1 - 2     | 1 - 6     | 1-4 29-35Lds     | ||||
Mean Length Turn     | 464.82 mm (18.3 inch)     |
    | 208.28 mm (8.2 inch)     |
||||
Resistance at 25° C (77.0° F)     |
4.68 ohms     | 0.145 ohms     | 0.239 ohms     | ||||
Copper Weight     | 5.21 kg (11.5 lb)     |
2.90 kg (6.4 lb)     |
1.791 kg (3.95 lb)     |
||||
Connection (2)     | Series     | 2 Parallel Wye     | Wye     | ||||
Line Leads     | #14     | 3 - #10     | 3-1 OF #14 (3 total)     |
Show/hide table
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 63 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram D |
136-6617 Generator Ar
Show/hide table
MAIN STATOR AND ROTOR WINDING DATA     | |||||||
---|---|---|---|---|---|---|---|
ITEM     | STATOR     | ROTOR     | |||||
Stack Height     | 431.8 mm (17 inch)     |
431.8 mm (17 inch)     |
|||||
Slots     | 60     | 4     | |||||
Coil Throw     | 1-12     | 1 - 2     | |||||
Turns/Coil     | 1.4(1-2-1-2-1)     | -     | |||||
Turns/Pole     | -     | 180     | |||||
No. & Wire Size     | 32 # 14     | # 6-1/2 Round     | |||||
Mean Length Turn     | 1701.8 mm (67 inch)     |
1320.292 mm (51.98 inch)     |
|||||
Copper Weight     | 87.0 kg (192 lb)     |
102.46 kg (225.9 lb)     |
|||||
Inside Connection (1)     | 2 Parallel Wye     |     | |||||
Line Leads (No. & Size)     | 12-2 # 4/0 (24 total)     | #8     | |||||
Low Voltage connected line resistance at 25° C (77.0° F)     |
0.00208 ohms     | -     | |||||
Field lead resistance at 25° C (77.0° F)     |
-     | 1.5 ohms     | |||||
EXCITER WINDING DATA     | |||||||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | Permanent Magnet Stator     | ||||
Exciter Frequency (Hz)     | 90 Hz     | 90 Hz     | 240 Hz     | ||||
Exciter Poles     | 6     |     | 16     | ||||
Stack Length     | 127.0 mm (5 inch)     |
127.0 mm (5 inch)     |
25.4 mm (1 inch)     |
||||
Coils/Group     | 1     | 1     | 1     | ||||
Turns (Coils)     | 140     | 8     | 12     | ||||
No. & Size Wire     | 15-1/2     | 2 - #16     | 4 - #18     | ||||
Coil Throw     | 1 - 2     | 1 - 6     | 1-4 29-35Lds     | ||||
Mean Length Turn     | 464.82 mm (18.3 inch)     |
    | 208.28 mm (8.2 inch)     |
||||
Resistance at 25° C (77.0° F)     |
4.68 ohms     | 0.145 ohms     | 0.239 ohms     | ||||
Copper Weight     | 5.21 kg (11.5 lb)     |
2.90 kg (6.4 lb)     |
1.791 kg (3.95 lb)     |
||||
Connection (2)     | Series     | 2 Parallel Wye     | Wye     | ||||
Line Leads     | #14     | 3 - #10     | 3-1 OF #14 (3 total)     |
Show/hide table
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 63 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram D |
136-6619 Generator Ar
Show/hide table
MAIN STATOR AND ROTOR WINDING DATA     | |||||||
---|---|---|---|---|---|---|---|
ITEM     | STATOR     | ROTOR     | |||||
Stack Height     | 431.8 mm (17 inch)     |
431.8 mm (17 inch)     |
|||||
Slots     | 60     | 4     | |||||
Coil Throw     | 1-12     | 1 - 2     | |||||
Turns/Coil     | 1.2 (1-1-1-2-1)     | -     | |||||
Turns/Pole     | -     | 180     | |||||
No. & Wire Size     | 35 # 14     | # 6-1/2 Round     | |||||
Mean Length Turn     | 1714.50 mm (67.5 inch)     |
1320.292 mm (51.98 inch)     |
|||||
Copper Weight     | 81.6 kg (180 lb)     |
102.46 kg (225.9 lb)     |
|||||
Inside Connection (1)     | 2 Parallel Wye     |     | |||||
Line Leads (No. & Size)     | 12-4 # 1/0 (48 total)     | #8     | |||||
Low Voltage connected line resistance at 25° C (77.0° F)     |
0.00174 ohms     | -     | |||||
Field lead resistance at 25° C (77.0° F)     |
-     | 1.5 ohms     | |||||
EXCITER WINDING DATA     | |||||||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | Permanent Magnet Stator     | ||||
Exciter Frequency (Hz)     | 90 Hz     | 90 Hz     | 240 Hz     | ||||
Exciter Poles     | 6     |     | 16     | ||||
Stack Length     | 127.0 mm (5 inch)     |
127.0 mm (5 inch)     |
25.4 mm (1 inch)     |
||||
Coils/Group     | 1     | 1     | 1     | ||||
Turns (Coils)     | 140     | 8     | 12     | ||||
No. & Size Wire     | 15-1/2     | 2 - #16     | 4 - #18     | ||||
Coil Throw     | 1 - 2     | 1 - 6     | 1-4 29-35Lds     | ||||
Mean Length Turn     | 464.82 mm (18.3 inch)     |
    | 208.28 mm (8.2 inch)     |
||||
Resistance at 25° C (77.0° F)     |
4.68 ohms     | 0.145 ohms     | 0.239 ohms     | ||||
Copper Weight     | 5.21 kg (11.5 lb)     |
2.90 kg (6.4 lb)     |
1.791 kg (3.95 lb)     |
||||
Connection (2)     | Series     | 2 Parallel Wye     | Wye     | ||||
Line Leads     | #14     | 3 - #10     | 3-1 OF #14 (3 total)     |
Show/hide table
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 63 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram D |
136-6622 Generator Ar
Show/hide table
MAIN STATOR AND ROTOR WINDING DATA (4)     | |||||||
---|---|---|---|---|---|---|---|
ITEM     | STATOR     | ROTOR     | |||||
Stack Height     | 431.8 mm (17 inch)     |
431.8 mm (17 inch)     |
|||||
Slots     | 60     | 4     | |||||
Coil Throw     | 1-12     | 1 - 2     | |||||
Turns/Coil     | 1.8 1-2-2-2-2     | -     | |||||
Turns/Pole     | -     | 180     | |||||
No. & Wire Size     | 25 # 14     | # 6-1/2 Round     | |||||
Mean Length Turn     | 1635.76 mm (64.4 inch)     |
1320.292 mm (51.98 inch)     |
|||||
Copper Weight     | 83.0 kg (183 lb)     |
102.46 kg (225.9 lb)     |
|||||
Inside Connection (1)     | 2 Parallel Wye     |     | |||||
Line Leads (No. & Size)     | 6-4 of #2 (24 Total)     | #8     | |||||
Low Voltage connected line resistance at 25° C (77.0° F)     |
0.0121 ohms     | -     | |||||
Field lead resistance at 25° C (77.0° F)     |
-     | 1.5 ohms     | |||||
EXCITER WINDING DATA     | |||||||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | Permanent Magnet Stator     | ||||
Exciter Frequency (Hz)     | 90 Hz     | 90 Hz     | 240 Hz     | ||||
Exciter Poles     | 6     |     | 16     | ||||
Stack Length     | 127.0 mm (5 inch)     |
127.0 mm (5 inch)     |
25.4 mm (1 inch)     |
||||
Coils/Group     | 1     | 1     | 1     | ||||
Turns (Coils)     | 140     | 8     | 12     | ||||
No. & Size Wire     | 15-1/2     | 2 - #16     | 4 - #18     | ||||
Coil Throw     | 1 - 2     | 1 - 6     | 1-4 29-35Lds     | ||||
Mean Length Turn     | 464.82 mm (18.3 inch)     |
    | 208.28 mm (8.2 inch)     |
||||
Resistance at 25° C (77.0° F)     |
4.68 ohms     | 0.145 ohms     | 0.239 ohms     | ||||
Copper Weight     | 5.21 kg (11.5 lb)     |
2.90 kg (6.4 lb)     |
1.791 kg (3.95 lb)     |
||||
Connection (2)     | Series     | 2 Parallel Wye     | Wye     | ||||
Line Leads     | #14     | 3 - #10     | 3-1 OF #14 (3 total)     |
Show/hide table
( 4 ) | Tap voltage regulator leads 20, 22, 24 seven (7) turns from neutral in coil groups 6, 4 and 2 respectively |
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 63 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram D |
136-6623 Generator Ar
Show/hide table
MAIN STATOR AND ROTOR WINDING DATA (4)     | |||||||
---|---|---|---|---|---|---|---|
ITEM     | STATOR     | ROTOR     | |||||
Stack Height     | 431.8 mm (17 inch)     |
431.8 mm (17 inch)     |
|||||
Slots     | 60     | 4     | |||||
Coil Throw     | 1-12     | 1 - 2     | |||||
Turns/Coil     | 1.8 1-2-2-2-2     | -     | |||||
Turns/Pole     | -     | 180     | |||||
No. & Wire Size     | 25 # 14     | # 6-1/2 Round     | |||||
Mean Length Turn     | 1635.76 mm (64.4 inch)     |
1320.292 mm (51.98 inch)     |
|||||
Copper Weight     | 83.0 kg (183 lb)     |
102.46 kg (225.9 lb)     |
|||||
Inside Connection (1)     | 2 Parallel Wye     |     | |||||
Line Leads (No. & Size)     | 6-4 of #2 (24 Total)     | #8     | |||||
Low Voltage connected line resistance at 25° C (77.0° F)     |
0.0121 ohms     | -     | |||||
Field lead resistance at 25° C (77.0° F)     |
-     | 1.5 ohms     | |||||
EXCITER WINDING DATA     | |||||||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | Permanent Magnet Stator     | ||||
Exciter Frequency (Hz)     | 90 Hz     | 90 Hz     | 240 Hz     | ||||
Exciter Poles     | 6     |     | 16     | ||||
Stack Length     | 127.0 mm (5 inch)     |
127.0 mm (5 inch)     |
25.4 mm (1 inch)     |
||||
Coils/Group     | 1     | 1     | 1     | ||||
Turns (Coils)     | 140     | 8     | 12     | ||||
No. & Size Wire     | 15-1/2     | 2 - #16     | 4 - #18     | ||||
Coil Throw     | 1 - 2     | 1 - 6     | 1-4 29-35Lds     | ||||
Mean Length Turn     | 464.82 mm (18.3 inch)     |
    | 208.28 mm (8.2 inch)     |
||||
Resistance at 25° C (77.0° F)     |
4.68 ohms     | 0.145 ohms     | 0.239 ohms     | ||||
Copper Weight     | 5.21 kg (11.5 lb)     |
2.90 kg (6.4 lb)     |
1.791 kg (3.95 lb)     |
||||
Connection (2)     | Series     | 2 Parallel Wye     | Wye     | ||||
Line Leads     | #14     | 3 - #10     | 3-1 OF #14 (3 total)     |
Show/hide table
( 4 ) | Tap voltage regulator leads 20, 22, 24 seven (7) turns from neutral in coil groups 6, 4 and 2 respectively |
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 63 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram D |
136-6624 Generator Ar
Show/hide table
MAIN STATOR AND ROTOR WINDING DATA     | |||||||
---|---|---|---|---|---|---|---|
ITEM     | STATOR     | ROTOR     | |||||
Stack Height     | 414.02 mm (16.3 inch)     |
414.02 mm (16.3 inch)     |
|||||
Slots     | 60     | 4     | |||||
Coil Throw     | 1-12     | 1 - 2     | |||||
Turns/Coil     | 1.4(1-2-1-2-1)     | -     | |||||
Turns/Pole     | -     | 193 (3)     | |||||
No. & Wire Size     | 26 # 14     | # 6-1/2 Round     | |||||
Mean Length Turn     | 1617.98 mm (63.7 inch)     |
    | |||||
Copper Weight     | 66.6 kg (147 lb)     |
106.5 kg (235 lb)     |
|||||
Inside Connection (1)     | 2 Parallel Wye     |     | |||||
Line Leads (No. & Size)     | 12-2 # 4/0 (24 total)     |     | |||||
Low Voltage connected line resistance at 25° C (77.0° F)     |
0.00241 ohms     | -     | |||||
Field lead resistance at 25° C (77.0° F)     |
-     | 1.56 ohms     | |||||
EXCITER WINDING DATA     | |||||||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | Permanent Magnet Stator     | ||||
Exciter Frequency (Hz)     | 90 Hz     | 90 Hz     |     | ||||
Exciter Poles     | 6     |     |     | ||||
Stack Length     | 127.0 mm (5 inch)     |
127.0 mm (5 inch)     |
    | ||||
Coils/Group     | 1     | 1     |     | ||||
Turns (Coils)     | 140     | 8     |     | ||||
No. & Size Wire     | 15-1/2     | 2 - #16     |     | ||||
Coil Throw     | 1 - 2     | 1 - 6     |     | ||||
Mean Length Turn     | 464.82 mm (18.3 inch)     |
    |     | ||||
Resistance at 25° C (77.0° F)     |
4.68 ohms     | 0.145 ohms     |     | ||||
Copper Weight     | 5.21 kg (11.5 lb)     |
2.90 kg (6.4 lb)     |
    | ||||
Connection (2)     | Series     | 2 Parallel Wye     |     | ||||
Line Leads     | #14     | 3 - #10     |     |
Show/hide table
( 3 ) | Layer wound, vent openings to divide layers 4-4-5 in coil head |
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 63 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram D |
136-6625 Generator Ar
Show/hide table
MAIN STATOR AND ROTOR WINDING DATA     | |||||||
---|---|---|---|---|---|---|---|
ITEM     | STATOR     | ROTOR     | |||||
Stack Height     | 414.02 mm (16.3 inch)     |
414.02 mm (16.3 inch)     |
|||||
Slots     | 60     | 4     | |||||
Coil Throw     | 1-12     | 1 - 2     | |||||
Turns/Coil     | 1.4(1-2-1-2-1)     | -     | |||||
Turns/Pole     | -     | 193 (3)     | |||||
No. & Wire Size     | 26 # 14     | # 6-1/2 Round     | |||||
Mean Length Turn     | 1617.98 mm (63.7 inch)     |
    | |||||
Copper Weight     | 66.6 kg (147 lb)     |
106.5 kg (235 lb)     |
|||||
Inside Connection (1)     | 2 Parallel Wye     |     | |||||
Line Leads (No. & Size)     | 12-2 # 4/0 (24 total)     |     | |||||
Low Voltage connected line resistance at 25° C (77.0° F)     |
0.00241 ohms     | -     | |||||
Field lead resistance at 25° C (77.0° F)     |
-     | 1.56 ohms     | |||||
EXCITER WINDING DATA     | |||||||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | Permanent Magnet Stator     | ||||
Exciter Frequency (Hz)     | 90 Hz     | 90 Hz     | 240 Hz     | ||||
Exciter Poles     | 6     |     | 16     | ||||
Stack Length     | 127.0 mm (5 inch)     |
127.0 mm (5 inch)     |
25.4 mm (1 inch)     |
||||
Coils/Group     | 1     | 1     | 1     | ||||
Turns (Coils)     | 140     | 8     | 12     | ||||
No. & Size Wire     | 15-1/2     | 2 - #16     | 4 - #18     | ||||
Coil Throw     | 1 - 2     | 1 - 6     | 1-4 29-35Lds     | ||||
Mean Length Turn     | 464.82 mm (18.3 inch)     |
    | 208.28 mm (8.2 inch)     |
||||
Resistance at 25° C (77.0° F)     |
4.68 ohms     | 0.145 ohms     | 0.239 ohms     | ||||
Copper Weight     | 5.21 kg (11.5 lb)     |
2.90 kg (6.4 lb)     |
1.791 kg (3.95 lb)     |
||||
Connection (2)     | Series     | 2 Parallel Wye     | Wye     | ||||
Line Leads     | #14     | 3 - #10     | 3-1 OF #14 (3 total)     |
Show/hide table
( 3 ) | Layer wound, vent openings to divide layers 4-4-5 in coil head |
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 63 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram D |
136-6626 Generator Ar
Show/hide table
MAIN STATOR AND ROTOR WINDING DATA     | |||||||
---|---|---|---|---|---|---|---|
ITEM     | STATOR     | ROTOR     | |||||
Stack Height     | 414.02 mm (16.3 inch)     |
414.02 mm (16.3 inch)     |
|||||
Slots     | 60     | 4     | |||||
Coil Throw     | 1-12     | 1 - 2     | |||||
Turns/Coil     | 1.4(1-2-1-2-1)     | -     | |||||
Turns/Pole     | -     | 193 (3)     | |||||
No. & Wire Size     | 26 # 14     | # 6-1/2 Round     | |||||
Mean Length Turn     | 1617.98 mm (63.7 inch)     |
    | |||||
Copper Weight     | 66.6 kg (147 lb)     |
106.5 kg (235 lb)     |
|||||
Inside Connection (1)     | 2 Parallel Wye     |     | |||||
Line Leads (No. & Size)     | 12-2 # 4/0 (24 total)     |     | |||||
Low Voltage connected line resistance at 25° C (77.0° F)     |
0.00241 ohms     | -     | |||||
Field lead resistance at 25° C (77.0° F)     |
-     | 1.56 ohms     | |||||
EXCITER WINDING DATA     | |||||||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | Permanent Magnet Stator     | ||||
Exciter Frequency (Hz)     | 90 Hz     | 90 Hz     | 240 Hz     | ||||
Exciter Poles     | 6     |     | 16     | ||||
Stack Length     | 127.0 mm (5 inch)     |
127.0 mm (5 inch)     |
25.4 mm (1 inch)     |
||||
Coils/Group     | 1     | 1     | 1     | ||||
Turns (Coils)     | 140     | 8     | 12     | ||||
No. & Size Wire     | 15-1/2     | 2 - #16     | 4 - #18     | ||||
Coil Throw     | 1 - 2     | 1 - 6     | 1-4 29-35Lds     | ||||
Mean Length Turn     | 464.82 mm (18.3 inch)     |
    | 208.28 mm (8.2 inch)     |
||||
Resistance at 25° C (77.0° F)     |
4.68 ohms     | 0.145 ohms     | 0.239 ohms     | ||||
Copper Weight     | 5.21 kg (11.5 lb)     |
2.90 kg (6.4 lb)     |
1.791 kg (3.95 lb)     |
||||
Connection (2)     | Series     | 2 Parallel Wye     | Wye     | ||||
Line Leads     | #14     | 3 - #10     | 3-1 OF #14 (3 total)     |
Show/hide table
( 3 ) | Layer wound, vent openings to divide layers 4-4-5 in coil head |
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 63 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram D |
136-6628 Generator Ar
Show/hide table
MAIN STATOR AND ROTOR WINDING DATA     | |||||||
---|---|---|---|---|---|---|---|
ITEM     | STATOR     | ROTOR     | |||||
Stack Height     | 414.02 mm (16.3 inch)     |
414.02 mm (16.3 inch)     |
|||||
Slots     | 60     | 4     | |||||
Coil Throw     | 1-12     | 1 - 2     | |||||
Turns/Coil     | 1.2(1-1-2-1-1)     | -     | |||||
Turns/Pole     | -     | 193 (3)     | |||||
No. & Wire Size     | 34 # 14     | # 6-1/2 Round     | |||||
Mean Length Turn     | 1676.4 mm (66 inch)     |
    | |||||
Copper Weight     | 77.5 kg (171 lb)     |
106.5 kg (235 lb)     |
|||||
Inside Connection (1)     | 2 Parallel Wye     |     | |||||
Line Leads (No. & Size)     | 12-4 # 1 (48 total)     |     | |||||
Low Voltage connected line resistance at 25° C (77.0° F)     |
0.00188 ohms     | -     | |||||
Field lead resistance at 25° C (77.0° F)     |
-     | 1.56 ohms     | |||||
EXCITER WINDING DATA     | |||||||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | Permanent Magnet Stator     | ||||
Exciter Frequency (Hz)     | 90 Hz     | 90 Hz     | 240 Hz     | ||||
Exciter Poles     | 6     |     | 16     | ||||
Stack Length     | 127.0 mm (5 inch)     |
127.0 mm (5 inch)     |
25.4 mm (1 inch)     |
||||
Coils/Group     | 1     | 1     | 1     | ||||
Turns (Coils)     | 140     | 8     | 12     | ||||
No. & Size Wire     | 15-1/2     | 2 - #16     | 4 - #18     | ||||
Coil Throw     | 1 - 2     | 1 - 6     | 1-4 29-35Lds     | ||||
Mean Length Turn     | 464.82 mm (18.3 inch)     |
    | 208.28 mm (8.2 inch)     |
||||
Resistance at 25° C (77.0° F)     |
4.68 ohms     | 0.145 ohms     | 0.239 ohms     | ||||
Copper Weight     | 5.21 kg (11.5 lb)     |
2.90 kg (6.4 lb)     |
1.791 kg (3.95 lb)     |
||||
Connection (2)     | Series     | 2 Parallel Wye     | Wye     | ||||
Line Leads     | #14     | 3 - #10     | 3-1 OF #14 (3 total)     |
Show/hide table
( 3 ) | Layer wound, vent openings to divide layers 4-4-5 in coil head |
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 63 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram D |
136-6631 Generator Ar
Show/hide table
MAIN STATOR AND ROTOR WINDING DATA (4)     | |||||||
---|---|---|---|---|---|---|---|
ITEM     | STATOR     | ROTOR     | |||||
Stack Height     | 414.02 mm (16.3 inch)     |
414.02 mm (16.3 inch)     |
|||||
Slots     | 60     | 4     | |||||
Coil Throw     | 1-11     | 1 - 2     | |||||
Turns/Coil     | 2     | -     | |||||
Turns/Pole     | -     | 193 (3)     | |||||
No. & Wire Size     | 26 # 14     | # 6-1/2 Round     | |||||
Mean Length Turn     | 1678.94 mm (66.1 inch)     |
    | |||||
Copper Weight     | 79.78 kg (175.9 lb)     |
106.5 kg (235 lb)     |
|||||
Inside Connection (1)     | 2 Parallel Wye     |     | |||||
Line Leads (No. & Size)     | 6-2 of #00 (12 Total)     |     | |||||
Low Voltage connected line resistance at 25° C (77.0° F)     |
0.01287 ohms     | -     | |||||
Field lead resistance at 25° C (77.0° F)     |
-     | 1.56 ohms     | |||||
EXCITER WINDING DATA     | |||||||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | Permanent Magnet Stator     | ||||
Exciter Frequency (Hz)     | 90 Hz     | 90 Hz     | 240 Hz     | ||||
Exciter Poles     | 6     |     | 16     | ||||
Stack Length     | 127.0 mm (5 inch)     |
127.0 mm (5 inch)     |
25.4 mm (1 inch)     |
||||
Coils/Group     | 1     | 1     | 1     | ||||
Turns (Coils)     | 140     | 8     | 12     | ||||
No. & Size Wire     | 15-1/2     | 2 - #16     | 4 - #18     | ||||
Coil Throw     | 1 - 2     | 1 - 6     | 1-4 29-35Lds     | ||||
Mean Length Turn     | 464.82 mm (18.3 inch)     |
    | 208.28 mm (8.2 inch)     |
||||
Resistance at 25° C (77.0° F)     |
4.68 ohms     | 0.145 ohms     | 0.239 ohms     | ||||
Copper Weight     | 5.21 kg (11.5 lb)     |
2.90 kg (6.4 lb)     |
1.791 kg (3.95 lb)     |
||||
Connection (2)     | Series     | 2 Parallel Wye     | Wye     | ||||
Line Leads     | #14     | 3 - #10     | 3-1 OF #14 (3 total)     |
Show/hide table
( 4 ) | Tap voltage regulator leads 20, 22, 24 four(4) coils (8 turns) from neutral, in pole groups 6, 4, and 2 respectively |
( 3 ) | Layer wound, vent openings to divide layers 4-4-5 in coil head |
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 63 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram D |
136-6632 Generator Ar
Show/hide table
MAIN STATOR AND ROTOR WINDING DATA (4)     | |||||||
---|---|---|---|---|---|---|---|
ITEM     | STATOR     | ROTOR     | |||||
Stack Height     | 414.02 mm (16.3 inch)     |
414.02 mm (16.3 inch)     |
|||||
Slots     | 60     | 4     | |||||
Coil Throw     | 1-11     | 1 - 2     | |||||
Turns/Coil     | 2     | -     | |||||
Turns/Pole     | -     | 193 (3)     | |||||
No. & Wire Size     | 26 # 14     | # 6-1/2 Round     | |||||
Mean Length Turn     | 1678.94 mm (66.1 inch)     |
    | |||||
Copper Weight     | 79.78 kg (175.9 lb)     |
106.5 kg (235 lb)     |
|||||
Inside Connection (1)     | 2 Parallel Wye     |     | |||||
Line Leads (No. & Size)     | 6-2 of #00 (12 Total)     |     | |||||
Low Voltage connected line resistance at 25° C (77.0° F)     |
0.01287 ohms     | -     | |||||
Field lead resistance at 25° C (77.0° F)     |
-     | 1.56 ohms     | |||||
EXCITER WINDING DATA     | |||||||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | Permanent Magnet Stator     | ||||
Exciter Frequency (Hz)     | 90 Hz     | 90 Hz     | 240 Hz     | ||||
Exciter Poles     | 6     |     | 16     | ||||
Stack Length     | 127.0 mm (5 inch)     |
127.0 mm (5 inch)     |
25.4 mm (1 inch)     |
||||
Coils/Group     | 1     | 1     | 1     | ||||
Turns (Coils)     | 140     | 8     | 12     | ||||
No. & Size Wire     | 15-1/2     | 2 - #16     | 4 - #18     | ||||
Coil Throw     | 1 - 2     | 1 - 6     | 1-4 29-35Lds     | ||||
Mean Length Turn     | 464.82 mm (18.3 inch)     |
    | 208.28 mm (8.2 inch)     |
||||
Resistance at 25° C (77.0° F)     |
4.68 ohms     | 0.145 ohms     | 0.239 ohms     | ||||
Copper Weight     | 5.21 kg (11.5 lb)     |
2.90 kg (6.4 lb)     |
1.791 kg (3.95 lb)     |
||||
Connection (2)     | Series     | 2 Parallel Wye     | Wye     | ||||
Line Leads     | #14     | 3 - #10     | 3-1 OF #14 (3 total)     |
Show/hide table
( 4 ) | Tap voltage regulator leads 20, 22, 24 four(4) coils (8 turns) from neutral, in pole groups 6, 4, and 2 respectively |
( 3 ) | Layer wound, vent openings to divide layers 4-4-5 in coil head |
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 63 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram D |
136-6633 Generator Ar
Show/hide table
MAIN STATOR AND ROTOR WINDING DATA     | |||||||
---|---|---|---|---|---|---|---|
ITEM     | STATOR     | ROTOR     | |||||
Stack Height     | 335.28 mm (13.2 inch)     |
335.28 mm (13.2 inch)     |
|||||
Slots     | 60     |     | |||||
Coil Throw     | 1-13     | 1 - 2     | |||||
Turns/Coil     | 1.8 (1-2-2-2-2)     | -     | |||||
Turns/Pole     | -     | 180     | |||||
No. & Wire Size     | 24 # 14     | # 6-1/2 Round     | |||||
Mean Length Turn     | 1584.96 mm (62.4 inch)     |
1127.76 mm (44.4 inch)     |
|||||
Copper Weight     | 77.47 kg (170.8 lb)     |
87.54287 kg (193 lb)     |
|||||
Inside Connection (1)     | 2 Parallel Wye     | Series     | |||||
Line Leads (No. & Size)     | 12-2 # 3/0 (24 total)     | #8     | |||||
Low Voltage connected line resistance at 25° C (77.0° F)     |
0.00288 ohms     | -     | |||||
Field lead resistance at 25° C (77.0° F)     |
-     | 1.27 ohms     | |||||
EXCITER WINDING DATA     | |||||||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | Permanent Magnet Stator     | ||||
Exciter Frequency (Hz)     | 90 Hz     | 90 Hz     |     | ||||
Exciter Poles     | 6     |     |     | ||||
Stack Length     | 127.0 mm (5 inch)     |
127.0 mm (5 inch)     |
    | ||||
Coils/Group     | 1     | 1     |     | ||||
Turns (Coils)     | 140     | 8     |     | ||||
No. & Size Wire     | 15-1/2     | 2 - #16     |     | ||||
Coil Throw     | 1 - 2     | 1 - 6     |     | ||||
Mean Length Turn     | 464.82 mm (18.3 inch)     |
    |     | ||||
Resistance at 25° C (77.0° F)     |
4.68 ohms     | 0.145 ohms     |     | ||||
Copper Weight     | 5.21 kg (11.5 lb)     |
2.90 kg (6.4 lb)     |
    | ||||
Connection (2)     | Series     | 2 Parallel Wye     |     | ||||
Line Leads     | #14     | 3 - #10     |     |
Show/hide table
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 63 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram D |
136-6634 Generator Ar
Show/hide table
MAIN STATOR AND ROTOR WINDING DATA     | |||||||
---|---|---|---|---|---|---|---|
ITEM     | STATOR     | ROTOR     | |||||
Stack Height     | 335.28 mm (13.2 inch)     |
335.28 mm (13.2 inch)     |
|||||
Slots     | 60     |     | |||||
Coil Throw     | 1-13     | 1 - 2     | |||||
Turns/Coil     | 1.8 (1-2-2-2-2)     | -     | |||||
Turns/Pole     | -     | 180     | |||||
No. & Wire Size     | 24 # 14     | # 6-1/2 Round     | |||||
Mean Length Turn     | 1584.96 mm (62.4 inch)     |
1127.76 mm (44.4 inch)     |
|||||
Copper Weight     | 77.47 kg (170.8 lb)     |
87.54287 kg (193 lb)     |
|||||
Inside Connection (1)     | 2 Parallel Wye     | Series     | |||||
Line Leads (No. & Size)     | 12-2 # 3/0 (24 total)     | #8     | |||||
Low Voltage connected line resistance at 25° C (77.0° F)     |
0.00288 ohms     | -     | |||||
Field lead resistance at 25° C (77.0° F)     |
-     | 1.27 ohms     | |||||
EXCITER WINDING DATA     | |||||||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | Permanent Magnet Stator     | ||||
Exciter Frequency (Hz)     | 90 Hz     | 90 Hz     | 240 Hz     | ||||
Exciter Poles     | 6     |     | 16     | ||||
Stack Length     | 127.0 mm (5 inch)     |
127.0 mm (5 inch)     |
25.4 mm (1 inch)     |
||||
Coils/Group     | 1     | 1     | 1     | ||||
Turns (Coils)     | 140     | 8     | 12     | ||||
No. & Size Wire     | 15-1/2     | 2 - #16     | 4 - #18     | ||||
Coil Throw     | 1 - 2     | 1 - 6     | 1-4 29-35Lds     | ||||
Mean Length Turn     | 464.82 mm (18.3 inch)     |
    | 208.28 mm (8.2 inch)     |
||||
Resistance at 25° C (77.0° F)     |
4.68 ohms     | 0.145 ohms     | 0.239 ohms     | ||||
Copper Weight     | 5.21 kg (11.5 lb)     |
2.90 kg (6.4 lb)     |
1.791 kg (3.95 lb)     |
||||
Connection (2)     | Series     | 2 Parallel Wye     | Wye     | ||||
Line Leads     | #14     | 3 - #10     | 3-1 OF #14 (3 total)     |
Show/hide table
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 63 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram D |
136-6635 Generator Ar
Show/hide table
MAIN STATOR AND ROTOR WINDING DATA     | |||||||
---|---|---|---|---|---|---|---|
ITEM     | STATOR     | ROTOR     | |||||
Stack Height     | 335.28 mm (13.2 inch)     |
335.28 mm (13.2 inch)     |
|||||
Slots     | 60     |     | |||||
Coil Throw     | 1-13     | 1 - 2     | |||||
Turns/Coil     | 1.8 (1-2-2-2-2)     | -     | |||||
Turns/Pole     | -     | 180     | |||||
No. & Wire Size     | 24 # 14     | # 6-1/2 Round     | |||||
Mean Length Turn     | 1584.96 mm (62.4 inch)     |
1127.76 mm (44.4 inch)     |
|||||
Copper Weight     | 77.47 kg (170.8 lb)     |
87.54287 kg (193 lb)     |
|||||
Inside Connection (1)     | 2 Parallel Wye     | Series     | |||||
Line Leads (No. & Size)     | 12-2 # 3/0 (24 total)     | #8     | |||||
Low Voltage connected line resistance at 25° C (77.0° F)     |
0.00288 ohms     | -     | |||||
Field lead resistance at 25° C (77.0° F)     |
-     | 1.27 ohms     | |||||
EXCITER WINDING DATA     | |||||||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | Permanent Magnet Stator     | ||||
Exciter Frequency (Hz)     | 90 Hz     | 90 Hz     | 240 Hz     | ||||
Exciter Poles     | 6     |     | 16     | ||||
Stack Length     | 127.0 mm (5 inch)     |
127.0 mm (5 inch)     |
25.4 mm (1 inch)     |
||||
Coils/Group     | 1     | 1     | 1     | ||||
Turns (Coils)     | 140     | 8     | 12     | ||||
No. & Size Wire     | 15-1/2     | 2 - #16     | 4 - #18     | ||||
Coil Throw     | 1 - 2     | 1 - 6     | 1-4 29-35Lds     | ||||
Mean Length Turn     | 464.82 mm (18.3 inch)     |
    | 208.28 mm (8.2 inch)     |
||||
Resistance at 25° C (77.0° F)     |
4.68 ohms     | 0.145 ohms     | 0.239 ohms     | ||||
Copper Weight     | 5.21 kg (11.5 lb)     |
2.90 kg (6.4 lb)     |
1.791 kg (3.95 lb)     |
||||
Connection (2)     | Series     | 2 Parallel Wye     | Wye     | ||||
Line Leads     | #14     | 3 - #10     | 3-1 OF #14 (3 total)     |
Show/hide table
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 63 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram D |
136-6636 Generator Ar
Show/hide table
MAIN STATOR AND ROTOR WINDING DATA     | |||||||
---|---|---|---|---|---|---|---|
ITEM     | STATOR     | ROTOR     | |||||
Stack Height     | 335.28 mm (13.2 inch)     |
335.28 mm (13.2 inch)     |
|||||
Slots     | 60     |     | |||||
Coil Throw     | 1-12     | 1 - 2     | |||||
Turns/Coil     | 1.6 (2-1-2-1-2)     | -     | |||||
Turns/Pole     | -     | 180     | |||||
No. & Wire Size     | 26 # 14     | # 6-1/2 Round     | |||||
Mean Length Turn     | 1524.0 mm (60 inch)     |
1127.76 mm (44.4 inch)     |
|||||
Copper Weight     | 71.6 kg (158 lb)     |
87.54287 kg (193 lb)     |
|||||
Inside Connection (1)     | 2 Parallel Wye     | Series     | |||||
Line Leads (No. & Size)     | 12-2 # 4/0 (24 total)     | #8     | |||||
Low Voltage connected line resistance at 25° C (77.0° F)     |
0.00261 ohms     | -     | |||||
Field lead resistance at 25° C (77.0° F)     |
-     | 1.27 ohms     | |||||
EXCITER WINDING DATA     | |||||||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | Permanent Magnet Stator     | ||||
Exciter Frequency (Hz)     | 90 Hz     | 90 Hz     |     | ||||
Exciter Poles     | 6     |     |     | ||||
Stack Length     | 127.0 mm (5 inch)     |
127.0 mm (5 inch)     |
    | ||||
Coils/Group     | 1     | 1     |     | ||||
Turns (Coils)     | 140     | 8     |     | ||||
No. & Size Wire     | 15-1/2     | 2 - #16     |     | ||||
Coil Throw     | 1 - 2     | 1 - 6     |     | ||||
Mean Length Turn     | 464.82 mm (18.3 inch)     |
    |     | ||||
Resistance at 25° C (77.0° F)     |
4.68 ohms     | 0.145 ohms     |     | ||||
Copper Weight     | 5.21 kg (11.5 lb)     |
2.90 kg (6.4 lb)     |
    | ||||
Connection (2)     | Series     | 2 Parallel Wye     |     | ||||
Line Leads     | #14     | 3 - #10     |     |
Show/hide table
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 63 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram D |
136-6637 Generator Ar
Show/hide table
MAIN STATOR AND ROTOR WINDING DATA     | |||||||
---|---|---|---|---|---|---|---|
ITEM     | STATOR     | ROTOR     | |||||
Stack Height     | 335.28 mm (13.2 inch)     |
335.28 mm (13.2 inch)     |
|||||
Slots     | 60     |     | |||||
Coil Throw     | 1-12     | 1 - 2     | |||||
Turns/Coil     | 1.6 (2-1-2-1-2)     | -     | |||||
Turns/Pole     | -     | 180     | |||||
No. & Wire Size     | 26 # 14     | # 6-1/2 Round     | |||||
Mean Length Turn     | 1524.0 mm (60 inch)     |
1127.76 mm (44.4 inch)     |
|||||
Copper Weight     | 71.6 kg (158 lb)     |
87.54287 kg (193 lb)     |
|||||
Inside Connection (1)     | 2 Parallel Wye     | Series     | |||||
Line Leads (No. & Size)     | 12-2 # 4/0 (24 total)     | #8     | |||||
Low Voltage connected line resistance at 25° C (77.0° F)     |
0.00261 ohms     | -     | |||||
Field lead resistance at 25° C (77.0° F)     |
-     | 1.27 ohms     | |||||
EXCITER WINDING DATA     | |||||||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | Permanent Magnet Stator     | ||||
Exciter Frequency (Hz)     | 90 Hz     | 90 Hz     | 240 Hz     | ||||
Exciter Poles     | 6     |     | 16     | ||||
Stack Length     | 127.0 mm (5 inch)     |
127.0 mm (5 inch)     |
25.4 mm (1 inch)     |
||||
Coils/Group     | 1     | 1     | 1     | ||||
Turns (Coils)     | 140     | 8     | 12     | ||||
No. & Size Wire     | 15-1/2     | 2 - #16     | 4 - #18     | ||||
Coil Throw     | 1 - 2     | 1 - 6     | 1-4 29-35Lds     | ||||
Mean Length Turn     | 464.82 mm (18.3 inch)     |
    | 208.28 mm (8.2 inch)     |
||||
Resistance at 25° C (77.0° F)     |
4.68 ohms     | 0.145 ohms     | 0.239 ohms     | ||||
Copper Weight     | 5.21 kg (11.5 lb)     |
2.90 kg (6.4 lb)     |
1.791 kg (3.95 lb)     |
||||
Connection (2)     | Series     | 2 Parallel Wye     | Wye     | ||||
Line Leads     | #14     | 3 - #10     | 3-1 OF #14 (3 total)     |
Show/hide table
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 63 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram D |
136-6639 Generator Ar
Show/hide table
MAIN STATOR AND ROTOR WINDING DATA (3)     | |||||||
---|---|---|---|---|---|---|---|
ITEM     | STATOR     | ROTOR     | |||||
Stack Height     | 335.28 mm (13.2 inch)     |
335.28 mm (13.2 inch)     |
|||||
Slots     | 72     |     | |||||
Coil Throw     | 1-13     | 1 - 2     | |||||
Turns/Coil     | 2     | -     | |||||
Turns/Pole     | -     | 180     | |||||
No. & Wire Size     | 17 # 14     | # 6-1/2 Round     | |||||
Mean Length Turn     | 1447.8 mm (57 inch)     |
1127.76 mm (44.4 inch)     |
|||||
Copper Weight     | 67.1 kg (148 lb)     |
87.54287 kg (193 lb)     |
|||||
Inside Connection (1)     | 2 Parallel Wye     | Series     | |||||
Line Leads (No. & Size)     | 6-2 of #1/0 (12 Total)     | #8     | |||||
Low Voltage connected line resistance at 25° C (77.0° F)     |
0.0203 ohms     | -     | |||||
Field lead resistance at 25° C (77.0° F)     |
-     | 1.27 ohms     | |||||
EXCITER WINDING DATA     | |||||||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | Permanent Magnet Stator     | ||||
Exciter Frequency (Hz)     | 90 Hz     | 90 Hz     |     | ||||
Exciter Poles     | 6     |     |     | ||||
Stack Length     | 127.0 mm (5 inch)     |
127.0 mm (5 inch)     |
    | ||||
Coils/Group     | 1     | 1     |     | ||||
Turns (Coils)     | 140     | 8     |     | ||||
No. & Size Wire     | 15-1/2     | 2 - #16     |     | ||||
Coil Throw     | 1 - 2     | 1 - 6     |     | ||||
Mean Length Turn     | 464.82 mm (18.3 inch)     |
    |     | ||||
Resistance at 25° C (77.0° F)     |
4.68 ohms     | 0.145 ohms     |     | ||||
Copper Weight     | 5.21 kg (11.5 lb)     |
2.90 kg (6.4 lb)     |
    | ||||
Connection (2)     | Series     | 2 Parallel Wye     |     | ||||
Line Leads     | #14     | 3 - #10     |     |
Show/hide table
( 3 ) | Tap voltage regulator leads 20, 22, 24 Nine (9) turns from neutral (4 coils and 1 turn) in coil groups 6, 4, 2 respectively |
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 63 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram D |
136-6640 Generator Ar
Show/hide table
MAIN STATOR AND ROTOR WINDING DATA (4)     | |||||||
---|---|---|---|---|---|---|---|
ITEM     | STATOR     | ROTOR     | |||||
Stack Height     | 335.28 mm (13.2 inch)     |
335.28 mm (13.2 inch)     |
|||||
Slots     | 72     |     | |||||
Coil Throw     | 1-13     | 1 - 2     | |||||
Turns/Coil     | 2     | -     | |||||
Turns/Pole     | -     | 180     | |||||
No. & Wire Size     | 17 # 14     | # 6-1/2 Round     | |||||
Mean Length Turn     | 1447.8 mm (57 inch)     |
1127.76 mm (44.4 inch)     |
|||||
Copper Weight     | 67.13132 kg (148 lb)     |
87.54287 kg (193 lb)     |
|||||
Inside Connection (1)     | 2 Parallel Wye     | Series     | |||||
Line Leads (No. & Size)     | 6-2 of #1/0 (12 Total)     | #8     | |||||
Low Voltage connected line resistance at 25° C (77.0° F)     |
0.0203 ohms     | -     | |||||
Field lead resistance at 25° C (77.0° F)     |
-     | 1.27 ohms     | |||||
EXCITER WINDING DATA     | |||||||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | Permanent Magnet Stator     | ||||
Exciter Frequency (Hz)     | 90 Hz     | 90 Hz     | 240 Hz     | ||||
Exciter Poles     | 6     |     | 16     | ||||
Stack Length     | 127.0 mm (5 inch)     |
127.0 mm (5 inch)     |
25.4 mm (1 inch)     |
||||
Coils/Group     | 1     | 1     | 1     | ||||
Turns (Coils)     | 140     | 8     | 12     | ||||
No. & Size Wire     | 15-1/2     | 2 - #16     | 4 - #18     | ||||
Coil Throw     | 1 - 2     | 1 - 6     | 1-4 29-35Lds     | ||||
Mean Length Turn     | 464.82 mm (18.3 inch)     |
    | 208.28 mm (8.2 inch)     |
||||
Resistance at 25° C (77.0° F)     |
4.68 ohms     | 0.145 ohms     | 0.239 ohms     | ||||
Copper Weight     | 5.21 kg (11.5 lb)     |
2.90 kg (6.4 lb)     |
1.791 kg (3.95 lb)     |
||||
Connection (2)     | Series     | 2 Parallel Wye     | Wye     | ||||
Line Leads     | #14     | 3 - #10     | 3-1 OF #14 (3 total)     |
Show/hide table
( 4 ) | Tap voltage regulator leads 20, 22, 24 Nine (9) turns from neutral (4 coils and 1 turn) in coil groups 6, 4, 2 respectively |
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 63 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram D |
136-6641 Generator Ar
Show/hide table
MAIN STATOR AND ROTOR WINDING DATA (4)     | |||||||
---|---|---|---|---|---|---|---|
ITEM     | STATOR     | ROTOR     | |||||
Stack Height     | 335.28 mm (13.2 inch)     |
335.28 mm (13.2 inch)     |
|||||
Slots     | 72     |     | |||||
Coil Throw     | 1-13     | 1 - 2     | |||||
Turns/Coil     | 2     | -     | |||||
Turns/Pole     | -     | 180     | |||||
No. & Wire Size     | 17 # 14     | # 6-1/2 Round     | |||||
Mean Length Turn     | 1447.8 mm (57 inch)     |
1127.76 mm (44.4 inch)     |
|||||
Copper Weight     | 67.13132 kg (148 lb)     |
87.54287 kg (193 lb)     |
|||||
Inside Connection (1)     | 2 Parallel Wye     | Series     | |||||
Line Leads (No. & Size)     | 6-2 of #1/0 (12 Total)     | #8     | |||||
Low Voltage connected line resistance at 25° C (77.0° F)     |
0.0203 ohms     | -     | |||||
Field lead resistance at 25° C (77.0° F)     |
-     | 1.27 ohms     | |||||
EXCITER WINDING DATA     | |||||||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | Permanent Magnet Stator     | ||||
Exciter Frequency (Hz)     | 90 Hz     | 90 Hz     | 240 Hz     | ||||
Exciter Poles     | 6     |     | 16     | ||||
Stack Length     | 127.0 mm (5 inch)     |
127.0 mm (5 inch)     |
25.4 mm (1 inch)     |
||||
Coils/Group     | 1     | 1     | 1     | ||||
Turns (Coils)     | 140     | 8     | 12     | ||||
No. & Size Wire     | 15-1/2     | 2 - #16     | 4 - #18     | ||||
Coil Throw     | 1 - 2     | 1 - 6     | 1-4 29-35Lds     | ||||
Mean Length Turn     | 464.82 mm (18.3 inch)     |
    | 208.28 mm (8.2 inch)     |
||||
Resistance at 25° C (77.0° F)     |
4.68 ohms     | 0.145 ohms     | 0.239 ohms     | ||||
Copper Weight     | 5.21 kg (11.5 lb)     |
2.90 kg (6.4 lb)     |
1.791 kg (3.95 lb)     |
||||
Connection (2)     | Series     | 2 Parallel Wye     | Wye     | ||||
Line Leads     | #14     | 3 - #10     | 3-1 OF #14 (3 total)     |
Show/hide table
( 4 ) | Tap voltage regulator leads 20, 22, 24 Nine (9) turns from neutral (4 coils and 1 turn) in coil groups 6, 4, 2 respectively |
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 63 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram D |
Caterpillar Information System:
SR4 and SR4B Electric Power Generation Rewind Data Winding Data for 144-1666 Generator through 144-1766 Generator
3512C Petroleum Engines with Dynamic Gas Blending Engine Shutdown Occurrence
312D2 and 313D2 Excavators System Pressure Release
SR4 and SR4B Electric Power Generation Rewind Data Winding Data for 141-5534 Generator through 142-9900 Generator
SR4 and SR4B Electric Power Generation Rewind Data Winding Data for 136-6580 Generator through 136-6609 Generator
SR4 and SR4B Electric Power Generation Rewind Data Winding Data for 126-8022 Generator through 128-7424 Generator
C1.7, C1.8 and C2.4 Tier 4 Interim and EU Stage 3A Engines for Caterpillar Built Machines Engine Oil Pressure Switch
CX31 and CX31 HT On-Highway Transmissions (Cat Truck) Transmission Hydraulic Control
2013/09/20 A Rework Procedure for the Power Access Stairway (PAS) On Certain Off-Highway Trucks is Now Available {7253}
2013/09/27 New Software Is Now Available for All Cat® Products With The Product Link 522 System {7606}
Rework Procedure for the PAS (Powered Access Stairway) on Certain Off-Highway Trucks{0679, 7253, 7254, 7255} Rework Procedure for the PAS (Powered Access Stairway) on Certain Off-Highway Trucks{0679, 7253, 7254, 7255}
LC5000, LC6100, and LC7000 Electric Power Generation Exciter Armature - Remove and Install
SR4 and SR4B Electric Power Generation Rewind Data Winding Data for 144-1964 Generator through 144-2088 Generator
SR4 and SR4B Electric Power Generation Rewind Data Winding Data for 149-2447 Generator through 150-9152 Generator
SR4 and SR4B Electric Power Generation Rewind Data Winding Data for 158-6410 Generator through 163-8546 Generator
SR4 and SR4B Electric Power Generation Rewind Data Winding Data for 164-0975 Generator through 164-4946 Generator
SR4 and SR4B Electric Power Generation Rewind Data Winding Data for 173-7078 Generator through 194-6563 Generator
SR4 and SR4B Electric Power Generation Rewind Data Winding Data for 203-5749 Generator through 324-5120 Generator
SR4 and SR4B Electric Power Generation Rewind Data Winding Data for 6I-0053 Generator through 6I-4860 Generator
2013/11/11 An Improved ARD Combustion Head is Now Used on the Tier 4 Engines of Certain Machines {108B, 108E, 108M}
2013/11/21 An Improved ARD Combustion Head is Now Used on Certain Tier 4 Engines {108B, 108E, 108M}
Installation of G610 Hardware for Cat® Terrain for Motor Graders, Wheel Dozers, and Wheel Loaders {7605} Installation of G610 Hardware for Cat® Terrain for Motor Graders, Wheel Dozers, and Wheel Loaders {7605}
3512C Oil Well Service Engines Air Shutoff - Test
793F and 797F Off-Highway Trucks Braking System Automatic Retarder Control (ARC)