UPS 250 and UPS 300 Uninterruptible Power Supplies Caterpillar


Operating Parameters - Set

Usage:

UPS 250 APZ

Password




    Illustration 1g00856208

  1. Refer to Systems Operation, RENR9558, "General Information (Getting Started)" for information on loading software.

    A screen that is similar to illustration 1 will appear after the software is loaded.

  1. Select the "Enter Password" menu option. The "Enter User Name/Password" menu appears.



    Illustration 2g00787622

  1. Enter a valid username. Enter a valid password. Click on "OK".

Nominal Voltage - Set

  1. Refer to Systems Operation, RENR9558, "User Operations".



    Illustration 3g01100882

  1. Navigate to "Op. Params. Op. Group 1: Nominal Voltage". Select "Nominal Voltage" from the drop-down menu.



    Illustration 4g00856284

  1. Enter the new value that is required by the system in the "Enter new value for Nominal Voltage" field.

    Note: This value must match the settings for the transformer voltage tap. Refer to Operation and Maintenance Manual, SEBU8145, "Transformer Voltage Setup".




    Illustration 5g01100933

  1. Click the "Send" button.

    After the "Send" button has been selected, a text message in the UPS View window confirms the setting of a new "Nominal Voltage" value.

The Nominal Voltage is now set.

"Internal CAN Enable" Set

Note: This procedure is for configuring the communications between the PC and the UPS after the initial start-up of the PC.

Note: During the initial start-up of communications, ignore any alarms until the start-up procedures for communications are complete.

"UPS Net Enable"

  1. Click on "Op Params.".

  1. Click on "Op. Group 5: Internal CAN Enable".



    Illustration 6g00932066

  1. Select "UPS Net Enable".

  1. Set "UPS Net Enable" to a value of "1".

  1. Click on "Send".

UPS View Baud Rate




    Illustration 7g00932106

  1. Click on "Op Params.".

  1. Click on "Op. Group 5: UPS Net Enable".

  1. Set "UPS View Baud Rate" to a value of "38400".

  1. Click "Send".

  1. Proceed to The Setting of the Model Index."Model Index Set".

Model Index Set

Table 1
MODEL     DESCRIPTION -number of MMUs     FREQUENCY     "MODEL INDEX"     SYSTEM CAPACITY (kW)     S/N PREFIX    
UPS300     1 MMU     60 Hz     0     240     CNJ    
UPS250     1 MMU     50 Hz     1     200     APZ    
UPS300E     1 MMU Upgradeable     60 Hz     2     240     CPZ    
UPS250E     1 MMU Upgradeable     50 Hz     3     200     CNM    
UPS300R     1 MMU plus 1 MMU     60 Hz     4     240     CPZ    
UPS250R     1 MMU plus 1 MMU     50 Hz     5     200     CNM    
UPS600     2 MMUs     60 Hz     6     480     CTX    
UPS500I     2 MMUs     50 Hz     7     400     CSE    
UPS600R     2 MMUs plus 1 MMU     60 Hz     8     480     CTX    
UPS500R     2 MMUs plus 1 MMU     50 Hz     9     400     CSE    
UPS900     3 MMUs     60 Hz     10     720     CRY    
UPS750I     3 MMUs     50 Hz     11     600     CPZ    
UPS900R     3 MMUs plus 1 MMU     60 Hz     12     720     CRY    
UPS750R     3 MMUs plus 1 MMU     50 Hz     13     600     CPZ    

  1. Refer to Operations and Maintenance Manual, SEBU8144, "Using Computer Software".



    Illustration 8g01100994

  1. Navigate to "Op. Params. Op. Group 6: Model Index" and select "Model Index" from the drop-down menu. Refer to illustration 8.



    Illustration 9g00856330

  1. Enter the new value that is required by your system in the "Enter new value for Model Index" box. Refer to table 1.

  1. Click the "Send" button.

    After the "Send" button has been selected, a message in the message area of UPS View window will confirm the setting of the new "Model Index" value.

  1. Push the "CTRL" key and the "R" key on the PC sequentially.

    Note: The process will reset the processor.

  1. Press the "Y" key in order to answer yes.

    Note: Steps 2 through 4 will need to be repeated if the programming is not completed.

  1. Repeat "Internal CAN Enable Set" and "Model Index Set" for each additional MMU in your system.

Caterpillar Information System:

UPS 120, UPS 150, UPS 250 and UPS 300 Uninterruptible Power Supplies Symbols
UPS 250 and UPS 300 Uninterruptible Power Supplies Acronyms
C7.1 Industrial Engine Temperature Sensor (DPF Inlet)
2012/07/19 Water Pump Operation on C7.1, C6.6, and C4.4 Engines {1361}
3412 Generator Set Engines Cylinder Head Valves
C13, C15, and C18 Tier 4 Final Engines Air Inlet Elbow
C18 Marine Engine Engine Oil Sample - Obtain
CX48-P2300 Petroleum Transmission Power Train Electronic Control System General Information
CX48-P2300 Petroleum Transmission Power Train Electronic Control System Connector Locations
C32 Marine Engines Closed Crankcase Ventilation (CCV) System
CEM Locomotive Aftertreatment Exhaust Outlet Nitrogen Oxide Sensor - Replace
CX48-P2300 Petroleum Transmission Power Train Electronic Control System Service Tools
794 AC Off-Highway Truck Final Drive Oil Level - Check
C7.1 Industrial Engine Temperature Sensor (Exhaust)
C7.1 Industrial Engine Injector (Diesel Exhaust Fluid)
C7.1 Industrial Engine Nitrogen Oxide Sensor
UPS 250 and UPS 300 Uninterruptible Power Supplies Getting Started
UPS 250 and UPS 300 Uninterruptible Power Supplies Menus
C32 Marine Engines Turbocharger - Inspect
UPS 250 and UPS 300 Uninterruptible Power Supplies Using Computer Software
Using the 223-2454 Tool Group on 3114, 3116, and 3126 Engines with Mechanical Unit Injectors (MUI){0374, 0599, 0701, 0706, 1251, 1252, 1254} Using the 223-2454 Tool Group on 3114, 3116, and 3126 Engines with Mechanical Unit Injectors (MUI){0374, 0599, 0701, 0706, 1251, 1252, 1254}
2012/10/04 A New Rocker Arm Assembly Is Used in Certain C11 and C13 Commercial Engines {1123}
C13 Tier 4 Final Engines Solenoid Valve
G3500 Engines Cylinder Head
Back to top
The names Caterpillar, John Deere, JD, JCB, Hyundai or any other original equipment manufacturers are registered trademarks of the respective original equipment manufacturers. All names, descriptions, numbers and symbols are used for reference purposes only.
CH-Part.com is in no way associated with any of the manufacturers we have listed. All manufacturer's names and descriptions are for reference only.