Status Messages
Show/hide table
Message | Support Load | Status | Description |
---|---|---|---|
Modem: Paging Cancelled. | Y | Normal | Paging was Canceled via UPSView, modem, or user interface. |
Modem: Page Failed:_. | Y | Normal | The pager was not able to be dialed, check the phone line and number. |
Email Sent OK. | Y | Normal | e-mail message sent to server |
EPO Activated (Serial Data). | N | Error | EPO activated via internal serial link. |
Modem: Page Sent OK:_. | Y | Normal | Paging was successful. |
Email Send Failure. | Y | Error | Unable to send e-mail to mail server, check mail server IP |
Cleared Password Enables. | Y | Service | Password cleared via UPSView. |
Invalid Access Passcode Entered. | Y | Service | The incorrect access passcode was entered. A modem connection must be established, a service password must be entered, and then the access passcode can be entered. |
Modbus: Task Suspending. | The Modbus option is enabled but disconnected. | ||
Modbus: Connection Made. | The Modbus option is enabled but disconnected. | ||
Accepted service mode password authorized for 30 minutes. | Y | Normal | Service engineer password has been accepted. |
Remote EPO Activated. | N | Error | Remote EPO is received by remote panel (hard wired). |
Remote Access Enabled. | Y | Normal | All conditions have been met for remote access and the access code has been entered at the User Interface. |
_Password accepted authorized for 30 minutes. | Y | Normal | Password accepted. |
Modbus: Disconnected. | The Modbus option is enabled but disconnected. | ||
Unknown System Message Type Received:_. | This message may appear only during a power-down. | ||
Time Changed | Y | Service | Time change entered via UPSView and accepted. |
Discharge blocked | N | Service | Discharge locked out by service engineer (manual mode). |
Discharge Open. | Y/N | Service | Service engineer has removed the discharge lock out. |
EPO Activated. | N | Error | EPO activated via the EPO button on the front door panel. |
Event Log Erased. | Y | Service | Event log was erased. |
Remote EPO (Serial Data). | N | Error | Remote EPO is received by internal serial link. |
Timeout waiting for Static Switch to walk-in. | N | Error | Static switch failed to walking in AC to utility converter, check the static switch module. |
Modem Telemetry terminated. | Y/N | Normal | Call ended. |
_Field Service password accepted for 30 minutes. | Y | Normal | Service engineers password accepted. |
Password key had expired. | Y | Normal | Internal timer causes the password to expire. |
Invalid password key entered. | Y | Error | Invalid password has been entered. |
APS date is invalid and must be reset. | Y | Error | Password access cannot be granted until date and time are set. |
Phase Rotation Bits in invalid state. | N | Error | At start-up the input phases were in an illegal state. Phase rotation must be clockwise. |
Modem telemetry initiated | Y/N | Normal | Call received over the modem. |
System will not auto-start calibration not complete. | N | Service | Start up or service condition is waiting for completion of calibration. |
Show/hide table
Message | Support Load | Status | Description |
---|---|---|---|
Input Current Overload Cleared high phase:_ | Y | Normal | Overload Condition Cleared. |
Input Overload phase _ of rated input current | Y/N | Error | Overload Condition. Reduce the load. |
System _ Fuse Failure. | A control power fuse in the system cabinet is open. | ||
Output Current Overload 30 Sec.A:_ B:_ C:_ | Y/N | Error | Overload Condition. Reduce the load. |
Input Current Overload 30 Sec.A:_ B:_ C:_ | Y/N | Error | Overload Condition. Reduce the load. |
Output Current Overload Cleared high phase:_ | Y | Normal | Overload Condition Cleared |
Overload Cleared Power at _ KW | Y/N | Error | Overload Condition Cleared |
Bypass Phase Range Err: A:_ B:_ C:_ | In a dual source system the bypass source is available but not within Spec. | ||
Output Current Bypass Overload A:_ B:_ C:_ | Y/N | Error | Overload Condition. Reduce the load. |
Output Current Overload 10 Min.A:_ B:_ C:_ | Overload Condition. Reduce the load. | ||
System Fuse Failure | A control power fuse in the system cabinet is open. | ||
Input Current Overload 10 Min.A:_ B:_ C:_ | Y/N | Error | Overload Condition. Reduce the load. |
Operator switched system keyswitch Online | Y | Normal | Operator turned the keyswitch to the On-Line position. |
Starting walk-in to input source | Y | Normal | Walk-in of load to the input source after discharge. |
Starting voltage phase match | Y | Normal | Phase matching after discharge. |
Zigzag K5 contactor error | Error | In a 4-w system, the neutral contactor did not close during a discharge. | |
Zigzag Circuit Breaker open error | Error | In a 4-w system, the zigzag circuit breaker is not closed. | |
Zigzag Controller lost frequency lock | In a 4-W system, the zigzag controller cannot detect a frequency. Zigzag controller lost frequency loc could be a power-down message. | ||
Zigzag Overload Relay Trip | The Zigzag Overload Relay has Tripped. | ||
Bypass Static Switch Fuse has failed | A Static bypass option fuse is open. | ||
Output Under Voltage: A:_f B:_f C:_ | Y | Discharge | System supporting load with flywheel energy. |
Output Over Voltage: A:_B:_ C:_ | Y | Discharge | System supporting load with flywheel energy. |
Output Current Overload 2 Min.A:_ B:_ C:_ | Y/N | Error | Overload Condition. Reduce the load. |
Ground Fault Detected | A ground fault was detected on a 3-W system. | ||
System PS_ OKAY | Normal | The system cabinet control power supplies are O.K. | |
Zigzag Circuit Breaker Trip | Error | The Zigzag Circuit Breaker is open. | |
Zigzag Fuse Blown | In a 4-W system, the Zigzag neutral fuse is open. | ||
Utility walked in to output power level | Y | Normal | Message at the end of discharge indicating utility power restored. |
Discharge ended max. duration exceeded at_0 RPM | Y | Normal | System was discharged for the maximum duration (2 minutes). |
Operator switched UPS to Bypass at_0 RPM | N | Normal | Operator turned the keyswitch to the Bypass position. |
Overload Cleared _ rated KW | Overload Condition Cleared | ||
10 Min. Overload _ rated KW | Overload Condition. Reduce the load. | ||
Output Overload phase _ of rated output current | Overload Condition. Reduce the load. | ||
2 Min. Overload _ rated KW | Overload Condition. Reduce the load. | ||
Input power has counterclockwise phase rotation | N | Service | Phase rotation is C, B, A. The C, B, A phase rotation is incorrect and must be corrected before continuing with startup. |
Input power has clockwise phase rotation | Y | Normal | Correct phase rotation is A, B, C. |
LOAD IS DISABLED Phase Rotation Error | N | Error | Phase rotation is C, B, A. The incorrect phase rotation must be corrected before continuing with startup. |
Under Frequency Detected at _ Hz | Y | Discharge | Line frequency out of tolerance, flywheel is supporting the load. |
Over Frequency Detected at _ Hz | Y | Discharge | Frequency has deviated outside of the specification, the flywheel is supporting the load. |
30 Sec. Overload _ rated KW | Overload Condition. Reduce the load. | ||
Input Over Voltage: A:_ B:_ C:_ | Y | Discharge | Line voltage is out of tolerance, the flywheel is supporting the load |
Password has expired | Y | Normal | The password must be updated. |
Timeout waiting for _ to change | N | Error | Contactor did not close when command was sent. |
System PS_ Failure | N | Error | System power supply failure. |
UPS in Bypass | N | Normal/ Error | Normal message if keyswitch is in the bypass position, otherwise this message is associated with an error state. |
Discharge Enabled | Y | Normal | System is at 4000 RPM or above and can support the load |
Discharge complete Duration:_ sec. | Y/N | Normal | System completed a discharge and recorded a time |
Discharging | Y | Normal | System supporting load with flywheel energy |
UPS Online | Y | Normal | Flywheel reached discharge enable speed, UPS on-line |
System Power Up | N | Normal | Start-up Message |
Input Under Voltage: A:_ B:_ C:_ | Y | Discharge | Line voltage out of tolerance, flywheel is supporting the load |
Discharge Disabled | N | Normal | System is not at speed to support the load |
Fast Voltage Trip Discharging at _ RPM | Y | Discharge | System supporting load with flywheel energy |
System Fan _ OKAY | Y | Normal | System Fan Failure Cleared |
System Fan _ Failure | Y | Error | System Fan Failure. |
High room temperature reported | Y/N | Error | Room temperature is too high |
Fire Alarm Detected | Y | Normal | Customer supplied input to the SIO has closed |
Building Alarm 4 Detected | Y | Normal | Customer supplied input to the SIO has closed |
Building Alarm 3 Detected | Y | Normal | Customer supplied input to the SIO has closed |
Building Alarm 2 Detected | Y | Normal | Customer supplied input to the SIO has closed |
Building Alarm 1 Detected | Y | Normal | Customer supplied input to the SIO has closed |
Remotely switched UPS Online | Y/N | Normal | Operator placed the UPS on-line via remote contacts |
Remotely switched UPS to Bypass at_Of RPM | N | Normal | Operator placed the UPS is Bypass via remote contacts |
Discharging at_RPM_KW | Y | Normal | System supporting load with flywheel energy |
System will not auto-start AC Voltages not in range | N | Error | Voltage out of range. |
High reported room temperature has cleared | Y | Normal | High room temperature warning cleared |
Input source is now the Utility | Y/N | Normal | The input source is utility |
Fast Voltage Trip Discharge at_RPM_KW | Y | Discharge | System supporting load with flywheel energy |
Discharge Low Trip + DC Bus:_ DC Bus:_ | Y | Discharge | System supporting load with flywheel energy |
Discharge Trip: Low phase _ Volts | Y | Discharge | Fast Voltage Transient out of tolerance, flywheel is supporting the load |
Input source is now the Genset | Y/N | Normal | The input source is the generator |
Discharge High Trip + DC Bus:_ DC Bus:_ | Y | Discharge | System supporting load with flywheel energy |
System will not auto-start power level not in range | N | Error | Power out of range. |
Discharge Trip: High phase _ Volts | Y | Discharge | Fast Voltage Transient out of tolerance, flywheel is supporting the load |
Output Overload_rated KW | Y/N | Error | Overload Condition. Reduce the load. |
Show/hide table
Message | Support Load | Status | Description |
---|---|---|---|
Online Mode Requires _MMUs only _ ready | N | Error | The load is more than the number of on-line units can support. Check the status of the MMUs |
Flywheel Master Enable Bit Low Error | N | Error | Error with the flywheel will not allow the flywheel to spin. |
Static Switch Phase A Shorted | N | Error | The controller has detected a shorted main static switch. |
Static Switch Phase B Shorted | N | Error | The controller has detected a shorted main static switch. |
Static Switch Phase C Shorted | N | Error | The controller has detected a shorted main static switch. |
Operator switched MMU Offline at _Of RPM | N | Error | Operator switched the MMU offline. Place MMU back on-line by turning keyswitch to on-line position. |
Verifying Flywheel signals and status | N | Normal | Startup Sequence |
MMU Overload 2 Min._ rated KW | Y/N | Error | Overload Condition. Reduce the load. |
MMU Overload _ rated KW | Y/N | Error | Overload Condition. Reduce the load. |
MMU Overload 10 Min._ rated KW | Y/N | Error | Overload Condition. Reduce the load. |
MMU Overload Cleared_rated KW | Y | Normal | Overload Condition Cleared |
MMU Overload 30 Sec._ rated KW | Y/N | Error | Overload Condition. Reduce the load. |
MMU Bypass Overload Level _KW | Y/N | Error | Overload Condition. Reduce the load. |
_ sensing failed | N | Error | Contactor position sensing has failed. |
Code update: failed device could not be programmed | N | Service | Firmware has failed to be loaded, check communication connection and setpoints. |
RPS Advance Calibration Done Position: _ | Y/N | Service | Startup/Calibration Message |
Remote Access Jumper Installed | Y | Normal | The necessary jumper for remote access has been installed |
Remote Access Jumper Removed | Y | Normal | The jumper for remote access has been removed |
Code update: receiving data | N | Normal | The firmware is being transferred to the UPS |
Code update: updating flash | N | Normal | The firmware is reprogramming the flash memory |
Operator switched to Voltage Regulation Mode | N | Service | System switched to voltage regulation mode via UPSView |
Code update: abort requested | N | Service | Service engineer requested abort of firmware upload |
Spin down with Voltage Regulation | N | Service | The flywheel is in spin down with voltage regulation |
Code update: failed not in programming mode | N | Service | Firmware not set to receive program upload. |
Code update: failed timed-out waiting for data | N | Service | Firmware has failed to be loaded, check communication connection and setpoints. |
Connected: _ | Y | Normal | UPSView was connected |
Disconnected: _ | Y | Normal | UPSView was disconnected |
Voltage Regulation Only mode | N | Error | Check for other error messages |
Code update: successful | N | Normal | The firmware was successfully reprogrammed |
Discharge ended min. discharge RPM reached at _ RPM | N | Normal | System was fully discharged |
T1 Control Power Failure | N | Error | T1 fuses failure. |
T2 Control Power Failure | N | Error | T2 fuses failure. |
Flywheel preheat not required temp = _ C | N | Normal | Preheat is not required if flywheel is above 30C |
Loaded _ Hz Default Operating Parameters | Y | Normal | The default setting for a specific frequency were loaded (50Hz or 60Hz) |
Output Voltage Phase Error caused by Load Fault | Y/N | Error | A fault occurred on the output of the UPS. |
Operator switched local keyswitch Online | Y | Normal | Operator turned the keyswitch to the On-Line position |
Online Command received from UPSView | Y/N | Service | System placed in On-Line mode via UPSView |
Waiting on ground fault to be cleared | N | Error | |
Waiting on zigzag circuit breaker reset | N | Error | |
MMU in current overload clear high phase: _ | Y | Normal | Overload Condition has cleared |
Power Up | N | Normal | Start-up Sequence |
Discharge blocked | N | Service | Discharge locked out by service engineer (manual mode) |
Discharge open | Y/N | Service | Service engineer has removed the discharge lock out |
MMU Out Current Overload 10 Min. A: _ B: _ C: _ | Y/N | Error | Overload Condition. Reduce the load. |
MMU Out Current Overload 2 Min. A: _B: _C: _ | Y/N | Error | Overload Condition. Reduce the load. |
MMU Out Current Overload 30 Sec. A: _ B: _C: _ | Y/N | Error | Overload Condition. Reduce the load. |
MMU Out Current Overload Clear high phase: _ | Y | Normal | Overload Condition Cleared |
MMU In Current Overload 10 Min.A: _ B: _ C: _ | Y/N | Error | Overload Condition. Reduce the load. |
MMU In Current Overload 30 Sec.A: _ B: _ C: _ | Y/N | Error | Overload Condition. Reduce the load. |
MMU Out Current Overload high phase: _ | Y/N | Error | Overload Condition. Reduce the load. |
MMU In Current Overload high phase: _ | Y/N | Error | Overload Condition. Reduce the load. |
MMU waiting on flywheel error to clear | N | Error | Flywheel Error |
Error cleared energizing flywheel | Y/N | Normal | Error is cleared and the flywheel will be energized |
MMU Out Current Bypass Overload A: _ B: _ C: _ | Y/N | Error | Overload Condition. Reduce the load. |
MMU In Current Bypass Overload A: _ B: _C: _ | Y/N | Error | Overload Condition. Reduce the load. |
MMU Inverter Current Overload A: _ B: _ C: _ | Y/N | Error | Overload Condition. Reduce the load. |
Cleared Inverter Current Overload A: _ B: _ C: _ | Y/N | Error | Overload Condition. Reduce the load. |
MMU In Current Overload 2 Min.A: _ B: _ C: _ | Y/N | Error | Overload Condition. Reduce the load. |
Bottom Field Coil Fault | N | Error | Field coil current error. |
Top Field Coil Timeout | N | Error | Field coil current error. |
Bottom Field Coil Timeout | N | Error | Field coil current error. |
Overspeed Error | N | Error | System reached speed higher than the setpoint. |
RPS Error | Y | Error | |
Skip 1 Error | N | Error | |
Skip 2 Error | N | Error | |
Skip 3 Error | N | Error | |
Error: Contactor _ | |||
Skip A Error | N | Error | |
Skip B Error | N | Error | |
Skip C Error | N | Error | |
Closed K2 | Y | Normal | |
MMU Utility Phase C Error | N | Error | |
MMU Utility Phase B Error | N | Error |
Caterpillar Information System:
C175-16 Marine Engine Air Inlet Manifold
UPS 120, UPS 150, UPS 250 and UPS 300 Uninterruptible Power Supplies Telemetry Parameters
C175-16 Marine Engine Exhaust Elbow
C175-16 Marine Engine Exhaust Manifold
C175-16 Marine Engine Air Shutoff
C175-16 Locomotive Engine Pressure Sensor
C13, C15, and C18 Tier 4 Final Engines Coolant Level Sensor
PL61 Pipelayer Machine Systems Flood Lamp
3508C, 3512C and 3516C Locomotive Engines Engine Oil Cooler Bypass and Cooling Jet Sequence Valves
UPS 120, UPS 150, UPS 250 and UPS 300 Uninterruptible Power Supplies Troubleshooting
C175-16 Marine Engine Air Cleaner
C175-16 Marine Engine Electronic Unit Injector Sleeve
C175-16 Marine Engine Inlet and Exhaust Valve Springs
C175-16 Marine Engine Inlet and Exhaust Valves
C175-16 Marine Engine Inlet and Exhaust Valve Guides
C175-16 Marine Engine Inlet and Exhaust Valve Seals
C175-16 Marine Engines Fuel System Secondary Filter - Replace
Measuring Wear on Bucket Base Edges (Determining Useful Life) {6101} Measuring Wear on Bucket Base Edges (Determining Useful Life) {6101}
C175-16 Marine Engine Engine Oil Cooler
C175-16 Marine Engine Engine Oil Pump
C3.4B Engines for Caterpillar Built Machines Diesel Particulate Filter - Clean
2012/02/08 Turbocharger on Certain C6.6 Engines {1052, 1053, 1348}
C175-16 Marine Engine Water Pump
C175-16 Marine Engines On-Board Replacement Parts