MODEL | UPS 120i | UPS 250i | UPS 150 | UPS 300 |
---|---|---|---|---|
RATING | 120 kVA | 250 kVA | 150 kVA | 300 kVA |
120 kW | 200 kW | 120 kW | 240 kW | |
INPUT | ||||
Voltage | 380/400/415 +10 percent / −15 percent (programmable)(1) | 480 +10 percent /−15 percent (programmable) | ||
Frequency - nominal | 50 Hz or 60 Hz | 60 HZ | ||
Input Current - nominal amps | 189/180/173 | 315/299/288 | ||
Input Current - maximum amps | 230 | 440 | 320 | 440 |
Non-Continuous Current | 70 | |||
Power Factor | 0.99 at rated load and nominal voltage | |||
Harmonic Current Distortion | ||||
Linear Load | less than 3 percent at 100 percent linear load | |||
Non-linear Load | less than 8 percent at 100 percent non-linear load | |||
Surge Withstand | Meets IEEE 587/A NSI C62.41 | |||
Walk-in | 1 to 10 seconds (programmable) | |||
O U T P U T | ||||
Frequency-nominal | Input synchronized (normal operation) nominal ±0.2 percent free running | |||
Current | 183/ 173/167 | 380/361/348 | 180 | 361 |
Voltage-nominal amps | Same as input | |||
Voltage Regulation | ||||
Steady State | plus or minus 2 percent for plus or minus 10 percent input and balanced or unbalanced loads | |||
Flywheel Mode | plus or minus 2 percent for steady-state balanced or unbalanced loads | |||
Transient | plus or minus 5 percent for 100 percent load step | |||
Voltage Distortion | less than 3 percent linear loads and less than 5 percent for 100 percent non-linear loads | |||
Overload Capability- (normal operation) | ||||
1000 percent | 10 milliseconds | |||
Up to 150 percent | 2 minutes | |||
Up to 125 percent | 10 minutes | |||
PHYSICAL DATA(2) | ||||
Efficiency | 97 percent | 98 percent | 96 percent | 98 percent |
Heat Rejection (BTU/ Hr) | 14,000/19,000 | 25,000/48,200 | 21,500/38,000 | 25,300/52,200 |
nominal/worst case | ||||
Depth | 34.0 in (865 mm) | |||
Width | 64.6 in (1, 641 mm) | |||
Total Height | 78 in (1980 mm) | |||
Weight | 4835 lb. (2194 kg) | |||
Cable Access | Top or Bottom | |||
ENVIRONMENTAL | ||||
Temperature | ||||
Operating | |
|||
Storage | |
|||
Humidity | 5 percent to 95 percent (non-condensing) | |||
Altitude | up to 914.4 m (3000 ft.) (derated operating temperature range for higher elevations) | |||
Audible Noise | less than 75 dBA at |
|||
Emissions and Immunity | FCC Class A, Subpart J of Part 15 |
Show/hide table
(1) | ± 10 percent max at 380V |
(2) | Weights and dimensions are for 4-wire configurations |
Show/hide table
UPS 120i | ||
---|---|---|
Percent Load | kW | Ride Through Time |
100 | 120 kW | 26 seconds |
75 | 90 kW | 35 seconds |
50 | 60 kW | 52 seconds |
25 | 30 kW | 89 seconds |
Show/hide table
UPS 150 | ||
---|---|---|
Percent Load | kW | Ride-Through Time |
100 | 120 kW | 26 seconds |
75 | 90 kW | 35 seconds |
50 | 60 kW | 52 seconds |
25 | 30 kW | 89 seconds |
Show/hide table
UPS 250i | ||
---|---|---|
Percent Load | kW | Ride-Through Time |
100 | 200 | 17 seconds |
75 | 150 | 22 seconds |
50 | 100 | 32 seconds |
25 | 50 | 61 seconds |
Show/hide table
UPS 300 | ||
---|---|---|
Percent Load | kW | Ride-Through Time |
100 | 240 kW | 13 seconds |
75 | 180 kW | 17 seconds |
50 | 120 kW | 25 seconds |
25 | 60 kW | 50 seconds |
Caterpillar Information System:
3516C and C175-16 Engines Selective Catalytic Reduction Air Assist Pressure Is Low
3516C and C175-16 Engines Selective Catalytic Reduction Air Assist Pressure Is High
UPS 120, UPS 150, UPS 250 and UPS 300 Uninterruptible Power Supplies System Description
UPS 120, UPS 150, UPS 250 and UPS 300 Uninterruptible Power Supplies Model View Illustrations
UPS 120, UPS 150, UPS 250 and UPS 300 Uninterruptible Power Supplies Electrical System
UPS 120, UPS 150, UPS 250 and UPS 300 Uninterruptible Power Supplies General Hazard Information
2012/01/06 The Drain Plugs for Horizontally Mounted Jacket Water Heaters Are Shipped Loose for 3500 and C175 Engines {1383, 7553}
UPS 120, UPS 150, UPS 250 and UPS 300 Uninterruptible Power Supplies Safety Signs and Labels
C18 Generator Set Maintenance Interval Schedule
2012/02/27 A New Air Inlet Housing and Support Bracket Are Used on 3616 and C280-16 Engines {1052, 1071}
C27 PET GEN SET Electric Power Generation and C27 KNOCKDOWN K Petroleum Power Train Package Generator Operation
2012/01/06 Air Compressor on 3054, 3054B, 3054C, 3054E, 3056, 3056E, C3.3, C3.4, C4.4, C4.4 (Mech), C6.6 and C7.1 Engines {1803}
UPS 120, UPS 150, UPS 250 and UPS 300 Uninterruptible Power Supplies UPS View Software
C18 Generator Set Engine Oil Level Gauge - Calibrate
2011/12/23 Proper Measurement for O-Ring Seal Land of Water-Cooled Exhaust Elbows on Certain Commercial Engines {1061}
2011/12/23 A New Bolt and Washers Are Used in the Damper Guard Group of Certain C18 Marine Engines {1205, 7553}
3516C and C175-16 Engines Selective Catalytic Reduction SCR Module Differential Pressure Is High
3516C and C175-16 Engines Selective Catalytic Reduction SCR Module Differential Pressure Is Low
2011/12/23 A New Routing Is Used on Fuel Injector Wiring Harnesses on C9.3 Industrial Engines {1290, 1408, 1900}
C1.7, C1.8 and C2.4 Tier 4 Interim and EU Stage 3A Engines for Caterpillar Built Machines Engine Oil Pump
3512C and 3516C Marine Propulsion Engines Diagnostic Trouble Codes
C1.7, C1.8 and C2.4 Tier 4 Interim and EU Stage 3A Engines for Caterpillar Built Machines Cylinder Block
3512C and 3516C Marine Propulsion Engines Event Codes
Procedures For Using: 127-8781 Transfer Filter Cart , old 9U-7361 (110V, 60 hz), 169-7159 Transfer Filter Cart , old 127-8782 (220V, 50 hz) CE, 174-9158 Transfer Filter Cart , old 129-0849 (Air Motor Driven){0374, 0599, 0680, 0738} Procedures For Using: 127-8781 Transfer Filter Cart , old 9U-7361 (110V, 60 hz), 169-7159 Transfer Filter Cart , old 127-8782 (220V, 50 hz) CE, 174-9158 Transfer Filter Cart , old 129-0849 (Air Motor Driven){0374, 0599, 0680, 0738}